Using carbon fiber reinforced polymer grids as confinement reinforcement for concrete

University of Florida Institutional Repository

PAGE 1

USING CARBON FIBER REINFORCED PO LYMER GRIDS AS CONFINEMENT REINFORCEMENT FOR CONCRETE By ANTONIS PETROU MICHAEL A DISSERTATION PRESENTED TO THE GRADUATE SCHOOL OF THE UNIVERSITY OF FLOR IDA IN PARTIAL FULFILLMENT OF THE REQUIREMENTS FOR THE DEGREE OF DOCTOR OF PHILOSOPHY UNIVERSITY OF FLORIDA 2006

PAGE 2

Copyright 2006 by Antonis Petrou Michael

PAGE 3

This dissertation is dedicated to my family for their love and support all these years that kept me going and to my new born nephe w Theodosis that I hope to meet soon.

PAGE 4

iv ACKNOWLEDGMENTS I would like to thank my advisor, Dr. H. R. Hamilton III, for giving me the opportunity to come to the University of Florida. His help, support and encouragement were invaluable to the completion of my work. I would like also to thank Mr. Marc Ansl ey for giving me the opportunity to work and conduct research with him at FDOT structur es laboratory. I will always be grateful to Marc for the opportunity he gave me. Not only have I gained valuable experience working with him but also made a great friend. Thanks are also due to the staff of the F DOT structures center for their help in completing the experimental work for this dissertation. The contri butions of Steve Eudy who set up and ran the data acquisition systems for all of my tests are greatly appreciated. Frank Cobb, Tony Johnston, Paul Tighe, and Davi d Allen all offered great assistance in specimen manufacturing and prepara tion of testing apparatus. I Thank TechFab for donating materials (CFRP grid) for my specimens and Accord Industries for accepting the challenge to built FRP spun cast piles. Lastly I would like to th ank Dr Gary Consolazio, Dr Ronald Cook, Dr Andrew Boyd, and Dr Bhavani Sankar, for serving on my committee.

PAGE 5

v TABLE OF CONTENTS page ACKNOWLEDGMENTS.................................................................................................iv LIST OF TABLES...........................................................................................................viii LIST OF FIGURES.............................................................................................................x ABSTRACT....................................................................................................................xvii CHAPTER 1 INTRODUCTION............................................................................................................1 2 LITERATURE REVIEW.................................................................................................5 FRP Flexural Reinforcement........................................................................................5 Carbon FRP Grids.........................................................................................................6 Durability of FRP Reinforcement.................................................................................7 FRP Concrete Confinement..........................................................................................8 Concrete Confinement Failure Criteria and Modeling...............................................10 Ductility Factors.........................................................................................................13 Non-Linear Static (Push-Over) Analysis....................................................................19 Plastic Hinge Length...................................................................................................20 Conclusions.................................................................................................................21 3 CARBON GRID CONFINED CYLINDERS................................................................23 Introduction.................................................................................................................23 Manufacturing.............................................................................................................24 Experimental Program................................................................................................26 CFRP Grid Testing..............................................................................................26 Cylinder Testing Details......................................................................................29 Cylinder Results and Discussion................................................................................30 Empirical Confin ement Model...................................................................................35 Conclusions.................................................................................................................39 4 RECTANGULAR CONCRETE SECTION WITH CFRP GRID TUBES....................41 Introduction.................................................................................................................41 Experimental Program................................................................................................41

PAGE 6

vi Specimen Construction........................................................................................41 Test Set-Up and Procedure..................................................................................45 Instrumentation....................................................................................................47 Results and Discussion........................................................................................49 Cylinder tests................................................................................................49 Beam tests....................................................................................................50 Fiber Model Analysis.................................................................................................52 Analysis of Strain Data...............................................................................................55 Measured Rotations....................................................................................................61 Moment-Curvature Analysis......................................................................................63 Ductility Factors.........................................................................................................68 Conclusions.................................................................................................................71 5 CAST IN PLACE CONCRETE SECTI ONS WITH FRP BARS AND GRID..............73 Introduction.................................................................................................................73 Experimental Program................................................................................................74 Pile Specimen Construction................................................................................74 Test Set-Up and Procedure..................................................................................77 Instrumentation....................................................................................................79 Material Properties..............................................................................................80 Results, Observations and Discussion.................................................................81 Experimental and Theoretical Peak Loads..........................................................86 Moment-Curvature Analysis......................................................................................88 Ductility Factors.........................................................................................................92 Conclusions.................................................................................................................95 6 SPUN CAST CONCRETE PILES WI TH CFRP GRID AND BARS...........................97 Introduction.................................................................................................................97 Specimen Design and Construction............................................................................98 Design..................................................................................................................98 Manufacturing.....................................................................................................99 Shear Reinforcement.........................................................................................107 Test Set-Up...............................................................................................................108 Test Procedure..........................................................................................................110 Instrumentation.........................................................................................................111 Material Properties....................................................................................................114 Results and Observations..........................................................................................115 Strain Data Analysis.................................................................................................121 Experimental and Fiber Model Moment Capacity...................................................127 Moment-Curvature Analysis....................................................................................130 Ductility Factors.......................................................................................................132 Conclusions...............................................................................................................134 7 SYSTEM BEHAVIOR OF PILES C ONSTRUCTED WITH CFRP COMPOSITES.........................................................................................................136

PAGE 7

vii Introduction...............................................................................................................136 Static Non-Linear (Push Over) Analysis..................................................................137 Pile Bent Model Description.............................................................................138 Results for Load Case 1.....................................................................................141 Ductility of Pile Bent Systems..........................................................................145 Results for Load Case 2.....................................................................................147 Static Non Linear Analysis of Prototype Pile Bents.................................................149 Conclusions...............................................................................................................157 8 PROPOSED CONCRETE MODEL.............................................................................159 Introduction...............................................................................................................159 Unconfined Concrete Model.....................................................................................159 Confined Concrete Model.........................................................................................171 Discussion.................................................................................................................178 Conclusions...............................................................................................................180 9 CONCLUDING REMARKS AND FUTURE REASERCH........................................181 Dissertation Summary..............................................................................................181 Summary of Conclusions..........................................................................................182 Future Research........................................................................................................185 LIST OF REFERENCES.................................................................................................187 BIOGRAPHICAL SKETCH...........................................................................................195

PAGE 8

viii LIST OF TABLES Table page 3-1. Cylinder test matrix....................................................................................................25 3-2. Results for CFRP grid specimens...............................................................................28 3-3. Cylinder results.......................................................................................................... .32 3-4. Area under stress-strain curve....................................................................................34 4-1. Test matrix for tube beams.........................................................................................42 4-2. Experimental results from cylinders tests...................................................................50 4-3. Experimentally calculate d top compressive strains....................................................57 4-4. Steel strains calculated using experimental data........................................................59 4-5. Rotations measured by tilt meters..............................................................................61 4-6. Rotations calculated based on the displacement profiles...........................................62 5-1. Specimen details for cast in place pile specimens......................................................74 5-2. Results from cylinders tests........................................................................................80 5-3. FRP reinforcement material properties.......................................................................81 5-4. Experimental and theoretical moment capacities.......................................................87 5-5. Experimental displacement ductility factors..............................................................93 5-6. Experimental curvature ductility factors....................................................................94 5-7. Theoretical curvatur e ductility factors........................................................................94 6-1. Spun cast specimen details.......................................................................................100 Table 6-2. Cylinders test results.......................................................................................115 6-3. FRP reinforcement material properties.....................................................................115

PAGE 9

ix 6-4. Experimental and theoretical moment capacities.....................................................130 6-5. Experimental displacement ductility factors............................................................133 6-6. Experimental curvature ductility factors..................................................................134 7-1. Plastic hinge length of various types of piles...........................................................139 7-2. Ductility factors for pile bents (load case 1).............................................................146 7-3. Section details for protot ype FRP reinforced piles...................................................150 7-4. Reinforcement details for prototype FRP reinforced piles.......................................151 7-5. Ductility factors for prototype pile bents..................................................................155 8-1. Parameters used to model behavior of unconfined conc rete cylinder in compression............................................................................................................171

PAGE 10

x LIST OF FIGURES Figure page 2-1. Mohr-coulomb failure criterion..................................................................................11 2-2. Schematic for ductility factor component definitions................................................15 2-3. Schematic for energy method ductility factor............................................................16 2-4. Schematic for deformation method ductility factor....................................................18 3-1. CFRP grid round tubes...............................................................................................25 3-2. CFRP grid cylinder casting in the field......................................................................25 3-3. CFRP grid................................................................................................................. ..26 3-4. CFRP strand tests........................................................................................................27 3-5. Stress-strain curves of CFRP grid strands..................................................................28 3-6. Typical load head movement rate for control cylinders.............................................29 3-7. Typical load rate for control cylinders.......................................................................30 3-8. CFRP grid cylinder test set-up....................................................................................30 3-9. Cylinders after testing.................................................................................................31 3-10. Stress-strain curves for control cylinders.................................................................32 3-11. Stress-strain curves for grid cylinders 1, 2 and 3.....................................................33 3-12. Stress-strain curves for grid cylinders 4, 5 and 6.....................................................33 3-13. Stress-strain curves for typi cal control and grid cylinders.......................................34 3-14. Cylindrical pressure vessel.......................................................................................36 3-15. Modified Hognestad stress-strain curve...................................................................38 3-16. Experimental and empirica l model stress-strain curves...........................................39

PAGE 11

xi 4-1. Longitudinal (top) and cross-sectional (bottom) views of control beam....................42 4-2. Longitudinal (top) and cr oss-sectional (bottom) vi ews of grid tube beam.................43 4-3. Formation of CFRP grid tubes....................................................................................44 4-4. Control beam..............................................................................................................44 4-5. Concrete placing (tube beam).....................................................................................45 4-6. Concrete cylinder casting...........................................................................................46 4-7. Test set-up for both beams..........................................................................................46 4-8. Strain gage arrangement (side vi ew of center portion of the beam)...........................48 4-9. Strain gage arrangement (top view of center portion of the beam)............................48 4-10. Test set-up for both beams before testing.................................................................49 4-11. Load-displacement curves for control and tube beams............................................50 4-12. Compression zones for both beams after testing......................................................51 4-13. Tube beam compression zone after testing...............................................................52 4-14. Tube beam cross-sectional fiber model....................................................................53 4-15. Load-strain curves for strain gage s at opposing locations (control beam)...............55 4-16. Load-strain curves for control beam.........................................................................56 4-17. Compressive strain pr ofile for control beam............................................................57 4-18. Assumed strain distribution......................................................................................58 4-19. Transverse expansive strains for control beam.........................................................60 4-20. Measured rotations at incr easing loads (control beam)............................................63 4-21. Measured rotations at increasing loads (tube beam)................................................63 4-22. Displacement curve and fitted polynomial line for control beam at 43.7 kips.........64 4-23. Experimental and theoretical Mcurves for control beam....................................67 4-24. Experimental and theoretical Mcurves for tube beam.........................................68 4-25. Experimental Mcurves for both beams...............................................................69

PAGE 12

xii 4-26. Curvature ductility f actor for control beam..............................................................70 5-1. Longitudinal view of specimen 2...............................................................................74 5-2. Cross-sectional view...................................................................................................75 5-3. Cross-sectional view at mid-span...............................................................................75 5-4. Longitudinal view of specimen 3...............................................................................76 5-5. Placement of concrete (specimens 2, 3 and 4)............................................................76 5-6. Placement of concrete (specimen 1)...........................................................................77 5-7. Schematic of test set up for specimen 1.....................................................................77 5-8. Schematic of test set up for specimen 2.....................................................................78 5-9. Schematic of test set up for specimen 3.....................................................................78 5-10. Schematic of test set up for specimen 4...................................................................79 5-11. Load-displacement curves for specimens 1 and 2 (mid-span).................................82 5-12. Crushed cover concrete (specimen 2).......................................................................82 5-13. Specimen 2 after the end of the test..........................................................................82 5-14. Ruptured CFRP grid and GFRP reinforcing bar (specimen 2).................................83 5-15. Specimen 3 after testing...........................................................................................84 5-16. Specimen 4 after testing...........................................................................................85 5-17. Moment-displacement curves for specimens 3 and 4...............................................86 5-18. Self weight distribution for cast in place piles.........................................................87 5-19. Illustration of the nume rical differential method......................................................89 5-20. Moment-curvature curves for specimen 1................................................................90 5-21. Moment-curvature curves for specimen 2................................................................90 5-22. Moment-curvature curves for specimen 3................................................................91 5-23. Moment-curvature curves for specimen 4................................................................91 5-24. Calculation of displacement ductility factors for specimens 1.................................93

PAGE 13

xiii 5-25. Calculation of curvature duct ility factors for specimens 1.......................................93 6-1. Elevation of midspan section of SCG piles..............................................................100 6-2. Elevation of midspan section of SCC piles..............................................................101 6-3. Cross sectional view A-A.........................................................................................101 6-4. Attachment of carbon rein forcing bars to steel rings...............................................102 6-5. Placement of CFRP grid...........................................................................................103 6-6. Reinforcement cage inside the mold........................................................................103 6-7. Concrete casting.......................................................................................................104 6-8. Concrete at the tip of the pile....................................................................................104 6-9. Sealing the mold.......................................................................................................105 6-10. Placement of mold onto the spinning platform......................................................106 6-11. Mold spinning on the spinning platform................................................................106 6-12. Pile release............................................................................................................. .106 6-13. Shear reinforcement for specimens SCC1 and SCG1............................................108 6-14. Shear reinforcement for specimens SCC2 and SCG2............................................108 6-15. Shear reinforcement for specimens SCC3 and SCG3............................................108 6-16. Test set-up for specimens SCC1, SCG1, SCC2 and SCG2....................................109 6-17. Test set-up for specimens SCC3 and SCG3...........................................................109 6-18. Steel saddle at north support...................................................................................110 6-19. Strain gage arrangement for specimens SCC2 and SCG2 (side view of center portion of the pile)..................................................................................................111 6-20. Strain gage arrangement for specime ns SCC2 and SCG2 (top view of center portion of the pile)..................................................................................................112 6-21. Strain gage arrangement for specimens SCC2 and SCG2......................................112 6-22. Strain gage arrangement for specimens SCC3 and SCG3 (side view of center portion of the pile)..................................................................................................113

PAGE 14

xiv 6-23. Strain gage arrangement for specime ns SCC3 and SCG3 (top view of center portion of the pile)..................................................................................................113 6-24. Strain gage arrangement for specimens SCC3 and SCG3......................................114 6-25. Load-displacement curves for piles SCC1, SCC2 and SCC3................................116 6-26. Load-displacement curves for piles SCG1 and SCG3............................................117 6-27. Load-displacement curves for piles SCC1 and SCG1............................................118 6-28. Pile specimens after testing....................................................................................118 6-29. Pile specimens after testing....................................................................................119 6-30. Pile specimens after testing....................................................................................120 6-31. Top cover concrete (pile SCG3).............................................................................120 6-32. Load-strain relationship for specimens SCC1, SCC2 and SCC3...........................121 6-33. Load-strain relationship for specimens SCG1 and SCG3......................................122 6-34. Strains at opposing sides for specimen SCC3........................................................122 6-35. Compression zone load-strain curv es for specimens SCC1 and SCG1..................123 6-36. Compression zone load-strai n curves for specimen SCC2.....................................124 6-37. Compression zone load-strain curv es for specimens SCC3 and SCG3..................124 6-38. Strain profile of comp ression zone for pile SCC3..................................................125 6-39. Strain profile of comp ression zone for pile SCG3.................................................125 6-40. Typical compression zone strain profile for specimens SCC3 and SCG3.............126 6-41. Transverse expansive strains for specimens SCC1 and SCG1...............................127 6-42. Spun cast cross-sec tional fiber model....................................................................128 6-43. Self weight distribution of spun cast piles..............................................................129 6-44. Experimental Mcurves for piles SCC3..............................................................131 6-45. Experimental Mcurves for piles SCG3.............................................................132 6-46. Calculation of displacement ductility factors for specimen SCC3.........................133 6-47. Calculation of curvature duct ility factors for specimen SCC3...............................133

PAGE 15

xv 7-1. Typical pile bent system...........................................................................................137 7-2. Typical model pile bent system................................................................................138 7-3. Visual analysis structural model...............................................................................140 7-4. Visual analysis model pile bent system (load case 2)..............................................141 7-5. Load-displacement curves of prestressed pile bents and pile bents using cast in place piles reinforced with GFRP bars and CFRP grid..........................................142 7-6. Load-displacement curves of prestressed pile bents and pile bents using cast in place piles reinforced with CFRP bars and grid.....................................................143 7-7. Load-displacement curves of prestressed pile bents and pile bents using spun cast piles reinforced with CFRP bars and grid..............................................................144 7-8. Load-displacement curves of the prestressed pile bent with minor corrosion.........148 7-9. Typical pile section sche matic for prototype piles...................................................150 7-10. Pile bent load-displacement curves for CSPP, CPCP1 and CPGP1 piles..............152 7-11. Pile bent load-displacement curves for CSPP, SCCP1 and SCGP1 piles..............152 7-12. Pile bent load-displacement curves for CSPP, PCPCP1 and PCPGP1 piles..........153 7-13. Pile bent load-displacement curves for CSPP, PCPCP2 and PCPCP3 piles..........153 7-14. Pile bent load-displacement curves for CSPP, SCPCP1 and SCPGP1 piles..........153 7-15. Pile bent load-displacement curves for CSPP, SCPCP2 and SCPGP3 piles..........154 8-1. Cracked concrete cylinder........................................................................................160 8-2. Concrete cylinder slice.............................................................................................161 8-3. Distribution of acoustic em issions for mortar beams...............................................163 8-4. Crack profile of concrete cyli nder (longitudinal cross-section)...............................164 8-5. Concrete cylinder micro columns.............................................................................165 8-6. Micro column assumed cross sectional shape..........................................................166 8-7. Determining the length of the side of the trapezoid using trigonometry..................166 8-8. Cylinder set up for total strain determination...........................................................168

PAGE 16

xvi 8-9. Sensitivity of model to the number of micro columns.............................................170 8-10. Experimental and calculated stress-st rain curves for unconfined control cylinders.................................................................................................................171 8-11. Restraint of micro columns by CFRP grid strand...................................................172 8-12. Geometry of micro column restrained by the CFRP grid.......................................173 8-13. Lateral stiffness of CFRP grid ring.........................................................................174 8-14. Stress-strain curves for grid diameter of 5.25 in....................................................176 8-15. Stress-strain curves for grid diameter of 5.5 in......................................................177 8-16. Stress-strain curves for di fferent amounts of CFRP grid.......................................177

PAGE 17

xvii Abstract of Dissertation Pres ented to the Graduate School of the University of Florida in Partial Fulfillment of the Requirements for the Degree of Doctor of Philosophy USING CARBON FIBER REINFORCED PO LYMER GRIDS AS CONFINEMENT REINFORCEMENT FOR CONCRETE By Antonis Petrou Michael August 2006 Chair: Homer R. Hamilton III Major Department: Civil and Coastal Engineering Prestressed concrete piles are widely us ed in marine environments to support docks, piers, bridges and other waterfront structures. Corrosion of the reinforcement caused by the penetration of the sea salts through the c oncrete can cause severe deterioration. Corrosion eventually forces re placement of the pile and the structure it supports. Carbon fiber reinforced polymer (CFRP) re inforcement has been researched for a number of years as a potentia l replacement for steel reinforcement. The significant advantage that CFRP reinforcement holds ove r steel is that it is highly resistant to deterioration in a harsh marine environment. One of the primary reasons, however, that the CFRP reinforcement has not seen wider use is its lack of ductility. Rather than attempting to improve the CFRP ductility, which is very difficult to do, the primary focus of the research reported in this dissertation was to improve the member flexural ductility by confini ng the concrete in the compre ssion zone. For that purpose a

PAGE 18

xviii CFRP grid has been investigated for use as confinement reinforcement in FRP reinforced concrete members. The grid was used in different confi gurations to confine concrete in the compression zone and improve flexural member ductility. The grid was used to confine concrete cylinders that were tested in axia l compression. The results showed a significant increase in the ultimate axial strain of th e CFRP confined concrete of approximately 100%. Another application of the grid wa s the embedment of grid tubes in the compression zone of beams that resulted in an improvement of th e ductility factors of approximately 20%. The grid was also used to fu lly wrap concrete pile s that were cast in place or spun cast. The ductility of the piles was improved by as much as 20%. Therefore improvement of the member fle xural ductility by confining the concrete in the compression zone is feasible. Howeve r the improvement in the ductility of the concrete elements was not enough to compar e favorably with the ductility of steel reinforced concrete member. More improve ment is required for the FRP reinforced members to be accepted and used to replace steel reinforced members.

PAGE 19

1 CHAPTER 1 INTRODUCTION Prestressed concrete piles are widely us ed in marine environments to support docks, piers, bridges and other waterfront structures. Corrosion of the reinforcement caused by the penetration of the sea salts through the c oncrete can cause severe deterioration. Corrosion of the steel reinforcem ent reduces the structural capacity of the concrete pile rendering it, in extreme cases, unable to perform the function for which it was designed. Furthermore, corrective or pr otective measures that can slow corrosion rates have to be adopted which results in higher maintenance costs. Corrosion will eventually force replacement of the pile and the structure it supports. Therefore, the service life of the whole structure is de pendent upon the service life of the piles supporting it. Even if repair and protective meas ures are employed to extend the life of the structure, they are costly, time consumi ng and rarely add signifi cantly to the service life. Carbon fiber reinforced polymer (CFRP) re inforcement has been researched for a number of years as a potentia l replacement for steel reinforcement. CFRP reinforcement is formed by bundling carbon fibers into a r ound shape and saturating with an appropriate resin. These bars can be fabric ated to have strength and sti ffness comparable to that of steel. The significant advantage that CFRP reinforcement holds over steel is that it is highly resistant to deterioration in a hars h marine environment. One of the primary reasons, however, that the CFRP reinforcemen t has not seen wider use is its lack of ductility. CFRP bars when loaded in tension, exhibit linear stress-st rain behavior up to

PAGE 20

2 rupture. There is no yield point and associated plateau to provide a ductile response when used as tensile reinforcement in concrete. There have been attempts to improve the ductility of CFRP with little or no success. Rather than attempting to improve the CFRP ductility, the primary focus of the research reported in this dissertation was to improve the member flexural ductility by confining the concrete in the compression zone. One of the challenges was locating CFRP th at could be used to confine concrete. In steel reinforced concrete, smaller steel bars are usually bent to form hoops to enclose the concrete and provide confinement. CFRP loses strength when bent sharply so a unique approach using a prefabricated CFRP gr id was used. The grid, unlike FRP wraps, can be embedded into concrete prior to cas ting because it has open space through which fresh concrete can flow. Light carbon grid me sh occupies approximately 31% of the grid area, leaving a 69% open area through which c oncrete can pass relatively easily. The grid is easily formed into a tubular shape, which avoids sharp bends and makes efficient use of the tensile cap acity of the grid. The research objective is to develop and ev aluate the use of CFRP grid to confine concrete. To accomplish this objective, a number of cross-sectional shapes were constructed and tested to evaluate the use of CFRP grid for confin ement. One of these was a full scale concrete ta pered pile using the spun-ca st construction method. These piles were hollow and circular in cross-secti on and were reinforced with CFRP composite grid and bars. Confinement models available in the literature were investigated for use in predicting behavior observed in the structural tests. The selected model was calibrated using concrete cylinder tests. The confinem ent model was also used to calculate the

PAGE 21

3 member behavior. In addition, system behavi or was investigated an alytically using the test results and confinement model. Finally, an entirel y new approach for modeling confinement was developed. This dissertation is organized into nine chapters. In these chapters different methods by which the CFRP grid can be used to confine concrete are presented. The methods are presented along with the experime ntal work and results for each method. A model based on a new approach that predicts the behavior of unc onfined and confined concrete is also presented. Chapter 2 contains a summary of the literatur e review. Several topics that relate to this dissertation were explored to find any mate rial that could be helpful in the process of completing the necessary research. In chapter 3 the experimental testing a nd experimental results from concrete cylinders that were confined using the CF RP grid are presented. The cylinders were tested in axial compression. In chapter 4 the constructi on and testing of two reinfo rced concrete beams using CFRP grid tubes in the compression zone to confine concrete are described. The experimental findings from the fle xural tests are also presented. In chapter 5 and 6 the construction and test ing details of FRP reinforced concrete piles that use the CFRP grid as conf inement reinforcement are presented. The experimental results from the tests are also presented. In chapter 7 a static non-linea r analysis of pile bents us ing both prestressing steel and FRP reinforced piles is discussed. A descri ption of the static non -linear analysis and the results are presented.

PAGE 22

4 In chapter 8 a new concrete confinement m odel is presented. The results from the model are compared to the available experimental results. Chapter 9 provides a summary of the findi ngs presented in this dissertation.

PAGE 23

5 CHAPTER 2 LITERATURE REVIEW Several areas were investigated in the lite rature review. One area was that of the ductility of carbon fiber-reinforced polymer (CFRP) reinforcement and what has been done to measure as well as improve it. Anot her area was to determine the extent to which CFRP grid has been investigated for use in confinement of concrete. Yet another was to identify and evaluate the existing confinement models for use in anal ytically predicting member and system behavior. Finally, some review was done on ductility computation and measurement. FRP Flexural Reinforcement A number of researchers have indicated th at the lack of ductile behavior exhibited by FRP reinforced members is a limiting factor to their use. Rooney and Taylor (2004), Toutanji and Deng (2003), Grace et al. (1998) Theriault and Benmokrane (1998) and Chaallal and Benmokrane (1996) found that the post cracking beam behavior was linear to failure in concrete beams reinforced with glass FRP rods. El-S alakawy et al. (2003) tested concrete deck slabs reinforced w ith both carbon and glass FRP bars. The carbon FRP bars were placed on the bottom in the ma in (transverse) direction while on top of the main direction as well as in both top and bo ttom of the secondary (longitudinal) direction glass FRP bars were used. The slab had a linear post cracking behavior until failure occurred. Thiagarajan (2003) compared the moment curvature behavior of concrete beams reinforced with carbon rods and mild steel. Although the st eel reinforced beams were found to be significantly more ductile, it was noted that the carbon FRP reinforced

PAGE 24

6 beams exhibited some ductility, which was attributed to concrete crushing in compression. Zou (2003) and Abdelrahman and Rizkalla (1999) tested prestressed concrete beams reinforced with carbon FRP ba rs. The load deflection curves of the beams were linear to failure. Some beams tested by Zou failed by rupture of the prestressing CFRP bars and some by crushing concrete. Carbon FRP Grids Heavy carbon grids with thickne sses of half an inch or more have been produced and have been used as primary reinforcement in concrete slabs or bridge decks in an effort to address the problem of corrosion due to the use of deicing salts during the winter months. Rahman et al. (2000) used these car bon grids as reinforcement in a section of concrete deck manufactured in a laboratory. The deck wa s supported on Steel I beams. They reported that the behavior of the deck was satisfactory and the carbon grid could replace steel reinforcement in bridge decks. Yost et al. ( 2001) used the same type of heavy carbon grid as reinforcement in concrete beams. The use of the grid as flexural reinforcement resulted in brittle failure si nce the carbon has no yiel d point and is linear elastic to failure. Light carbon grids (thickness 3 to 4 hundred ths of an inch) are also available and are used primarily for crack control in conc rete structures. Harries and Gassman (2003) conducted tests on reinforced concrete ba sin knockout panels that employed a light carbon grid to control cracking. The grid reduced cracking of the panel. Shao et al. (2003) used the same light carbon grid to control pl astic shrinkage cracki ng in concrete. They concluded that the plastic shrinkage crack reduction was in the range of 50% to 65%.

PAGE 25

7 Durability of FRP Reinforcement Glass fiber reinforced polymer (GFRP) materials are sensitive to salt water. If salt water comes to contact with the glass fibers it will attack them and can destroy them in a short period of time. It is not unusual for a GFRP bar to lose approximately 50% of its strength once the fibers are exposed. Even t hough GFRP reinforcing bars have an epoxy coating that provides protect ion against such attack, cr acking of the epoxy protective layer can allow saltwater to penetrate and dest roy the fibers. It is therefore dangerous to use GFRP bars for such applications. On the other hand carbon fibers are immune to attack by saltwater and therefore well suited for marine structures. Even in the case of cracking in the matrix material of carbon fi ber reinforced polymer (CFRP) bars their strength will not be compromised. Micelli and Nanni (2004) tested bo th GFRP and CFRP rods for durability in various environments and reported problems with GFRP rods but no problems were unveiled for the CFRP rods. Jansons et al. (2002) exposed carbon FRP composites to salt water at elevated temper atures with no noticeable changes to the strength and modulus of the composites. Myer s et al. (2002) tested both glass and carbon FRP rods in tension after alkali exposure or a combined effect of Ultra Violet (UV) radiation, high temperature cycles and high moisture (environmenta l cycles). Although the environmental cycles did not have any e ffect on the tensile stre ngth of neither the glass nor the carbon rods, the al kali exposure had a significant impact on one of the glass rod types. A reduction in the tensile strength of 41% was observed after alkali exposure for 42 days at a temperature of 60 oC. No significant loss of tens ile strength was reported for the carbon rods. Carbon fibers are not infl uenced by alkaline environments even when in direct contact, while glass fibers will deteri orate once they come into contact with such an environment (Malvar 1998).

PAGE 26

8 FRP Concrete Confinement Confinement of concrete is not a new c oncept but rather has been practiced for many years. Confinement of concrete can be achieved by wrapping the concrete, therefore providing resistance in the hoop direct ion of a concrete element in compression. A concrete element loaded in compression in addition to the displacement in the direction of the applied compression load it also displa ces in the hoop direction (the direction that is perpendicular to the applied load) due to the Poisson effect. If the concrete is unconfined the expansion developed in the hoop direction will eventually result to the failure of the concrete element. On the othe r hand, if a concrete element is confined, a confining pressure develops which restrain s the hoop direction e xpansion and therefore prevents the failure of the concrete element until a different mode of failure occurs. This has two primary effects on the behavior of the c oncrete element. First it increases the load at which the concrete element fails and s econdly increases the am ount of displacement required to produce failure. As a consequence of the second effect the concrete element can dissipate higher amounts of energy, which makes it more ductile, compared with the unconfined concrete element. Abdel-Fattah and Ahmad (1989) tested 3 x 9 in. (the unsupported length was 6 in.) concrete cylindrical specimens confined by steel rings spaced at 0.5 in. with the cylinders exhibiting highly ductile behavior Mei et al. (2001) tested 4 x 8 in. cylinders with a steel sleeve on the outside. Axial compressive load wa s applied only to the concrete core. The improvement to the concrete properties was apparent with concrete properties further improving with an increase to the thic kness of the steel sleeve. When fiber reinforced polymer (FRP) ma terials became widely available in the civil sector, they started replac ing steel as external confinement reinforcement. One of the

PAGE 27

9 primary applications of FRP ma terials is retrofit of concrete elements, primarily columns, to improve their ductility. This is done ma inly in seismic regions where concrete structures experience large deformations. Column wrapping improves the strength and ductility of the concrete and improves its performance under earthquake loads. Xiao and Wu (2000 and 2003) wrapped concre te cylinders using various materials and methods. Some were wrapped with carbon fi ber fabrics, while others were wrapped with glass fiber fabrics. They also wrapped cylinders using a machine that tightly wound carbon fibers around the cylinders. The results showed a significant improvement both in strength and ductility. Lam and Teng (2004), Li et al. (2003) a nd Harries and Kharel (2002) wrapped cylinders with carbon fabrics with similar re sults as Xiao and W u. Harries and Kharel (2002) had some of their cylinders wrapped w ith glass fabrics. Li and Hadi (2003) and Campione and Miraglia (2003) tested round co ncrete columns wrapped with either glass or carbon fiber fabric sheets in a polymer matrix. In doing so they improved the ductility of the columns. Campione and Miraglia (2003) also wrapped, in the same manner, square columns and square columns with round corners with the same results. It was found that the round shape is the most effective shape fo r confinement while th e square with sharp corners the least effec tive of the three. Teng et al. (2002) wrapped bridge columns in the field using FRP wraps. Laboratory specimens were also tested with the columns exhibiting a ductile behavior. Shahawy et al. (2000) tested standard concrete cylinders wrapped with carbon fiber fabrics in an e poxy matrix. The results varied depending on the number of carbon layers applied. For an unconfined concrete strength of 41.4 MPa the confined strength of cy linders was increased to 70 MP a for the 1-layer wrap and 110

PAGE 28

10 MPa for the 4-layer wrap. The ultimate strain for the 1-layer wrap was 0.007 and for the 4-layer wrap 0.016. Pantelides et al. (1999) wrapped a bridge pier with carbon fiber composites and tested it in situ. An unwrapped pier was al so tested. The pier wrapped with carbon was able to accommodate movements two times larger than the unwrapped pier. Prefabricated FRP tubes can be filled with concrete and serve at the same time as formwork, flexural reinforcement and confin ement reinforcement. Davol et al. (2001) tested prefabricated round shells filled with concrete in flexure with satisfactory results. The concrete filled FRP shells exhibited a ductile behavior. Mirm iran et al. (1998) manufactured round and square FR P tubes that were filled with concrete and then tested in compression. The round tubes increased the peak axial stress by as much as 2.5 times the peak axial stress of unconfined concre te and reached axial strains 12 times higher than the axial strain at peak stress of unconfined concrete. Concrete Confinement Failure Criteria and Modeling In order to determine the failure stress of confined concrete a failure criterion is necessary. Researchers have used the M ohr-Coulomb failure criterion due to its simplicity and relative accuracy (Li et al. 2003; Mei et al. 2001; Gandappa et al. 2001). This failure criterion is based on the well-know n Mohrs circle. Once concrete is loaded in axial compression a stress state consisting of normal stresses develops. Concrete is assumed to fail when its compressive capacity is reached. The shear stresses are due to the Poisson effect that causes tension in conc rete in the hoop direction which also causes vertical cracking. When confinement is present the concrete is in a triaxial stress state that counteracts the tensi on stress in the hoop direction caused by the Poisson effect delaying failure. This is reflected in the higher axial compressive load required to

PAGE 29

11 produce failure (see Fig. 2-1). The two lines intersecting at point O represent the MohrCoulomb failure envelope. The points of tange ncy between the two circles and the failure lines are the points at which the combinat ion of the axial compressive and Poisson tension stress state for the unconfined and the triaxial compression stress state for the confined concrete produces failure. O Unconfined Concrete Confined Concrete fcc fc fl fc unconfined strength fl confinement pressure fcc confined strength Figure 2-1. Mohr-coulomb failure criterion Assuming the concrete is in triaxial compression due to the presence of the confining pressure, the confined compressi on strength of concrete in terms of the confining pressure and the unconfined strength is expressed as follows: l c ccf k f f (2-1) where fcc is the compression strength of confined concrete, fc is the compression strength of unconfined concrete, k is a constant also referred to as the effectiveness coefficient and fl is the confining pressure.

PAGE 30

12 One of the shortcomings of the Mohr-Coulomb failure criterion is that it will predict the failure load as being the peak load which is usually accurate when concrete is highly confined but it will not work for low confinement concrete because most of the ductility of such concrete is produced after reaching the peak strength. Highly confined concrete is usually produced when re latively high amounts of FRP confinement reinforcement are used. Other failure criteria have been used to determine when failure of confined concrete occurs. Richarts failure criteri on is similar to the Mohr-Coulomb failure criterion as expressed in Equation 2-1 with k equal to 4.1 (Xiao and Wu 2003; Li and Hadi 2003; Xiao and Wu 2000; Sa maan et al. 1998). Tsai-Wu fa ilure criterion is a failure criterion that focuses on the FRP laminate fail ure and takes into account the interaction of the axial compressive and tensile hoop stresses that produces an earlie r failure of the FRP encasement compared with ignoring the axia l compressive stress and accounting only for the hoop tensile stress (Mandal et al. 2005; Cho et al. 2005; Barbero 1998). The Tsai-Hill failure criterion is similar to the Tsai Wu failure criterion with the difference that the stress values used can only be tensile or compressive but not both (Cho et al. 2005; Barbero 1998). For example if pure tension stre ss state is assumed in all directions the Tsai-Hill criterion yields the same results as the Tsai-Wu criterion. Confinement models to predict the maximu m stress or the whole stress-strain curve of confined concrete have been develope d (Campione and Miraglia 2003; Li and Hadi 2003; Li et al. 2003; Xiao a nd Wu 2000, 2003; Fam and Rizk alla 2001). Most models that describe the whole stress-strain curve of FRP confined concrete employ a bilinear curve (second portion of the curve ascending) that in most cases works well. Most

PAGE 31

13 models have been refined using data from concrete that is confined by FRP composite materials that their amount and properties pr oduce such behavior. Cases with lower grade material or smaller amounts of FRP compos ites are scarce and have not been used to demonstrate the applicability of the available models. Ductility Factors Two ductility factors are usually used to measure the ductility of structural components. The displacement ductility factor ( ) is defined as the ratio of the ultimate displacement ( u) over the displacement at first yield ( y). u y (4-1) The second factor is the cu rvature ductility factor ( ) defined as the ratio of the ultimate curvature ( u) over the curvature at first yield ( y). u y (4-2) The definition of ultimate and yield displacem ents or curvatures is simple when the behavior is elasto-plastic. De finition of these parameters is more complicated when the behavior is not elasto-p lastic. Usually the behavior of re inforced concrete is not perfectly elasto-plastic. Therefore, the need for a consistent definition of the ultimate and yield displacements or curvatures was realized. Researchers have proposed definitions of ultimate and yield displacement and curvature as well as instructions on how to calculate them. The ultimate displacement (or curvature) has been defined as the displacement (or curvature) at which the lateral load in th e descending portion of the load-displacement curve is not less than 80 % of the maximum load, Pu, (Priestley and Park 1987; Zahn, et

PAGE 32

14 al. 1990; Sheikh and Khoury 1993; Yeh et al. 2002). Park and Pauley (1975(b)) have argued that the available ultimate deformati on is not necessarily the deformation that corresponds to the maximum load capacity. They further said that when survival without collapse is the criterion, it is too conservative to define ultimate deformation as the deformation corresponding to the maximum load-carrying capacity. It would seem reasonable to recognize at least some of th is deformation capacity after the maximum load has been reached and to define and to define the available ultimate deformation as that deformation when the load-carrying cap acity has reduced by some arbitrary amount after maximum load. For example, a 10 or 20% reduction in maximum load-carrying capacity could be tolerated in many cases, but the exact amount would depend on the particular case. The yield displacement is defined as the displacement at the intersection of the horizontal line representing the ideal lateral capacity, Pi, (nominal capacity using the ACI 318 approach and a reduction factor of unity ) and the straight lin e that passes through zero and the point in the load -displacement curve at 75% of the ideal lateral capacity (Priestley and Park 1987; Za hn et al. 1990; Sheikh and K houry 1993). The definitions of yield and ultimate displacemen ts are depicted in Fig. 2-2. Because FRP reinforced concrete exhibit different behavior than steel reinforced concrete due to the absence of a yield point of the FRP re inforcement researchers have attempted to produce ductility factors also call ed deformability factors that apply to FRP reinforced concrete. There is the notion that FRP reinforced concrete structures have to be treated in a different way in terms of ductility than what traditionally has been done with steel reinforcement. Two basic methods have been proposed.

PAGE 33

15 The first method is an energy based method in which the ratio of total energy of the structural system to the elastic energy is us ed to calculate an ener gy ductility factor (see Fig 2-3). This was first introduced by Jeong (1994) that proposed the following expression for determining the energy ductility factor ( E): 1 5 0ela tot EE E (2-2) where Etot is the total energy under the load-displacement curve and Eela is the portion of the total energy which is considered elastic. d P Pi 0.75 Pi Pu 0.8 Pu d y or d c d u 0 Figure 2-2. Schematic for ductility factor component definitions Many researchers have used this method to characterize the ductility of FRP reinforced concrete structures Grace and Sayed (1998) tested bridge models prestressed with CFRP tendons and used the energy method to determine ductility. However, they had to measure the amount of inelastic energy of their bridge models. They did that by subjecting their bridge models to loading and unloading cycles near 90% of their ultimate

PAGE 34

16 capacity. Others have also used the energy me thod to determine ductility factors for FRP reinforced concrete structures without havi ng to measure the amount of inelastic energy. They estimated the elastic energy as the area under a straight line drawn from the point representing failure load a nd having a slope equal to the average of the initial and secondary slopes of the load-displacement diagram of the stru cture (Alsayed and Alhozaimy 1998; Vijay and Ganga Rao 2001; Li and Wang 2002). or P P3 0 S1 S2 S3 P1 P2 S Inelastic Energy Elastic Energy S=[P1S1+(P2-P1)S2]/P2 Figure 2-3. Schematic for ener gy method ductility factor Grace et al. (1998) however discovered that the average slope used to estimate the elastic energy was different that the one meas ured from their tests for a number of their specimens and proposed the introduction of f our more parameters to eliminate the differences between the experimentally meas ured slopes and the average slope based on the initial and secondary slope s. This made the process complicated and also raised questions about the reliability of this particular method and whether it can be used to

PAGE 35

17 determine ductility factors without having to experimentally measure the slope. It should also be noted that using the initial and secondary slopes of the displacement diagram is not as simple as it might be at first th ough. Typically there are no distinct slopes which mean that a decision on which slopes to use has to be made which is subjective and dependent upon the person that makes the de cision. This can generate inconsistent results. The second method that has been propos ed is a deformation based method. The ductility factor, also referred to as J-factor is the product of a st rength factor and a deformability factor. The strength factor takes into account the increase in the moment or load capacity while the deformability factor take s into account the increase in either the curvature or the displacement of the struct ure relative to a specific load level. This specific load level has been defined as the lo ad at which the concrete compressive strain is equal to 0.001 (Fig. 2-4) (Theriault a nd Benmokrane 1998; Wang and Belarbi 2005) or the cracking load (Zou 2003) or th e service load (Newhook et al. 2002). Based on the diagram in Fig. 2-4 the load f actor (LF) and deformability factor (DF) are the following: 001 0P P LFu (2-3) where Pu is the ultimate load and P0.001 is the load at a concrete compressive strain equal to 0.001. 001 0 uDF (2-4) where u is the ultimate load and 0.001 is the load at a concrete compressive strain equal to 0.001.

PAGE 36

18 The J-factor (JF) is then calculated as the product of the load factor and the deformability factor as follows: DF LF JF (2-5) There is no general agreement as to the lo ad or deformability point with which the ultimate values are compared to calculate th e strength and deformability factors needed to determine the J-factor. Therefore, the result s obtained using this method, are based on an arbitrary selection of a starting point whic h makes them unreliable. Li and Wang 2002 also pointed out that the use of J-factor values seemed to contradict experimental results that indicated higher ductility for specimens th at had low J-factors. Another shortcoming of this method is the fact that a large J-fact or can be obtained even for a perfectly linear load displacement diagram which goes agains t conventional ductility definition which is the amount of plastic deformability of the structure. P Pu0 P0.001 0.001 u Figure 2-4. Schematic for deformation method ductility factor

PAGE 37

19 The ductility factors calculated based on the above mentioned methods for FRP reinforced concrete can not be directly co mpared to the ductility factors for steel reinforced concrete because they are based on different approaches. For the case of the CFRP grid reinforced concrete a method that can produce ductility factors in the spirit of the ductility factors for steel reinforced c oncrete is needed. Such a method will be a measure of the inelastic deformations of the FRP reinforced structure that take place due to concrete confinement. Non-Linear Static (Push-Over) Analysis Push-over analysis is a practical met hod of analyzing a structure for dynamic loading such as impact and seismic loading. Push-over analysis uses monotonic loads that represent the dynamic loads a nd a non-linear description of the structure. The nonlinearity of the structure can be de rived from the moment-curvature (M) relationships of the piles or columns. Although push-over an alysis is not itself a dynamic analysis it can produce accurate results especially in the case were the fundamental mode of vibration is predominately tr anslational which is the case for single degree of freedom systems (SDOF). The California Department of transportation allows the use of an inelastic static analysis (ISA), or push over, for the seismi c analysis of bridge s (Caltrans 2004(a)). Mackie and Stojadinovi (2003) successfully used static push over analysis to investigate seismic demand for performance based design of bridges. Fenves and Ellery (1998) also used nonlinear static analysis to analyze a multi-frame highway bridge that failed in the 1994 Northridge earthquake. They were able to construct the load-dis placement curves of the bridge frames and to determine that the failure of the bridge frames was due to

PAGE 38

20 inadequate shear capacity which prevented the bridge from utilizing the ductility available for a flexure failure mode. Hasan et al. (2002) used pus h-over analysis based on the nonlinear relationship of the Mcurves for the analysis of two steel fr ame multistory buildings and were able to determined overall ductility demands and identify the existence of soft stories in the buildings. They were also able to assess the adequacy of the earthquake-resistance capacity of the buildings. Halabian et al. (2002) used push-over analysis to analy ze free standing reinforced concrete TV towers. They used the Mrelationships to account concrete cracking and reinforcement yielding. Their analysis compar ed well to the time history analyses from three earthquakes. Saatcioglou and Razvi (2002) conducted push over analyses on confined concrete columns and the results were a good match with the availabl e experimental data from reinforced concrete columns. Plastic Hinge Length Determination of the plastic hinge length is a complicated matter and no universal equation exists. Researchers have introduced empirical equations that can be used to estimate the plastic hinge length (lp) that for the most part are related to the effective depth and the distance of the cr itical section from the point of contra-flexu re (Baker and Amarakone 1964; Corley 1966; Sawyer 1964; Ba ker 1956;). The experimental research by the above researchers was conducted on re inforced concrete beams and frames. Priestly and Park (1987) tested concrete bridge columns under seismic loading and proposed an equation for estimating plasti c hinge length. The equation estimates the plastic hinge length as a function of the distan ce of the critical sect ion from the point of

PAGE 39

21 contra-flexure and the diameter of the longitudinal rein forcing steel. The experimental average plastic hinge length was found to be eq ual to approximately one half the diameter or depth of pile section. Watson and Park ( 1994) performed similar tests on reinforced concrete columns and used the same empiri cal equation proposed by Priestly and Park (1987) for estimating the length of the plastic hinge. Budek et al. (2000) proposed an empirical expression for estimating the length of the plastic hinge which was derived based on tests conducted on bridge drilled-shaft reinforced concrete piles. The plastic hinge length in that expression was a function of the pile/column diameter and the above grade hei ght of the pile or column. The California Department of Transportation also provides e quations for the estimation of plastic hinge lengths for use in the design of structures undergoing dynamic loading such as seismic (Caltrans 2004(b)). For columns and type II shafts Caltrans requires using an empirical equation based on the length of the column or sh aft and the yield strength and the size of the longitudinal steel reinforcement. For type one pile shafts/colum ns Caltrans requires using a different empirical equation that is based on the diameter or the least dimension of the pile shaft and the length of the p ile shaft/column from the point of maximum moment to the point of contra-flexure. Conclusions Based on the information obtained from the lit erature review of previous research the following conclusions can be drawn: Testing has shown that when the CFRP com posites are used as flexural reinforcement the elements generally behave in a non-ductile manner. Confinement of concrete using FRP wraps or jackets improves concrete ductility and strength. It was found that if enough FRP reinforcement is us ed to confine concrete its strength can be improved up to 150% and its ductility up to a factor of ten.

PAGE 40

22 No evidence of CFRP grid use as co nfinement reinforcement was found, but the available research suggests that it could be possible to improve concrete ductility by using the CFRP grid as confinement reinforcement. CFRP composite materials do not seem to ha ve any serious issues with durability in marine or alkaline rich environments. Howe ver, it has been suggested that if glass fibers are exposed to marine or alkaline environments serious degradation is likely. Therefore the use of GFRP reinforcement in these environments is risky and should be avoided. The methods used to determine ductility factors for FRP reinforced concrete structures are different than the methods used for st eel reinforced concrete and therefore the factors from the different methods are not comparable. A similar method to the one used currently for steel reinforced concrete is needed to provide comparable factors for the FRP reinforced concrete. Non-linear static analysis can be used to analyze structural systems under dynamic loads and can produce good results.

PAGE 41

23 CHAPTER 3 CARBON GRID CONFINED CYLINDERS Introduction Column wrapping with CFRP composites is a popular a lternative for improving the seismic resistance of columns. Fiber fabrics and prefabricated FRP composite jackets or tubes cover the entire area of the concrete element and therefore cannot be embedded in concrete. The carbon grid has approximately 69% open surface area a llowing the grid to be embedded in the concrete. Light grids are easily formed into a tubular shape and can provide more effective confinement than wr aps that are forced to follow the column cross-section, which might be square or rectangular. It has been suggested that rather than wrapping the columns with CFRP fabrics confinement of concrete can be provided by embedding carbon grid. The effectiveness of the carbon grid in confining concrete was not known. Therefore, nine standard (6 x12 in.) cylinders were tested in axial compression to investigate the level of confinement provided by the grids. The CFRP grid improved both the strength and ductility of the concrete. The CFRP grid did not produce highly confined concre te because the amount of CFRP material provided by the grid was low due to its large openings. Significant improvement was observed in the ductility of the concrete cylinders with embedd ed CFRP grid. The ultimate strain for the CFRP grid reinforced cylinders was approximately two times larger compared to the control cylinders. Grid confinement also resulted in an increase in the concrete strength of approximately 11%.

PAGE 42

24 An empirical model was developed usi ng available knowledge from research on concrete confined using FRP sheets and pref abricated jackets or shells. The empirical model is presented in this chapter. The model was in good agreement with the experimental data available from the CFRP grid cylinder tests. Manufacturing Nine standard (6 in x 12 in) cylinders were cast. Table 31 contains the test matrix of the cylinders. Two layers of grid, formed into concentric tubular configurations and held with plastic ties, were cast into si x of the specimens while the remaining three cylinders were cast without reinforcement. The cylinders with the CFRP grid were designated as grid cylinders. Th e grid cylinders were divided into two groups (3 cylinders in each group) with each group having a different grid diameter. The CFRP grid for the first group was formed into a tubular confi guration that was approximately 11.4-in long with a diameter of 5.25-in and a diameter of 5.5-in for the sec ond grid cylinder group (Fig. 3-1). Two layers of the grid were appl ied with the grid lapping the 2 layers for an additional 7 in for development purposes. The gr id openings were aligne d to facilitate the flow of concrete through the grid. The CFRP grid round tubes were placed inside plastic cylinder molds and concrete was added (Fig. 3-2). A Class II standard FDOT bridge deck c oncrete mixture was used to make the cylinders. The specified minimum compressive strength of this concrete at 28 days is 5000 psi. Concrete was sampled as per ASTM C172 (ASTM 2004). Both the control and grid cylinders were cast in the field according to ASTM C31 except they were ambient cured rather than moist cured (ASTM 2003). All concrete cylinders were allowed to cure in the field inside the plastic mold for approximately one month and were then take n to the laboratory where they remained

PAGE 43

25 until two weeks before testing. At that time they were removed from their molds and sulfur cement caps were placed on each e nd. The total curing time for all cylinder specimens was 125 days. Table 3-1. Cylinder test matrix Cylinder type Number of specimens CFRP grid Grid layers Grid dia. (in.) Control 3 No 0 N/A Grid 3 Yes 2 5.25 Grid 3 Yes 2 5.5 (a) (b) Figure 3-1. CFRP grid round tube s: (a) cross sectional view and (b) longitudinal view (a) (b) Figure 3-2. CFRP grid cylinder casting in the field: (a) beginning and (b) end CFRP Grid Cylinders

PAGE 44

26 Experimental Program CFRP Grid Testing The CFRP composite grid tested in this program was fabricated from carbon fibers embedded in an epoxy matrix. It was supplied in the form of rolls that were 41 inches wide and 300 yards long. The strand spacing in the longitudinal dire ction was 1.8 inches and in the transverse directi on 1.6 inches (see Fig. 3-3). Th e CFRP grid had an openness of 69% which means that only 31% of the su rface area was covered by the carbon fibers. (a) (b) Figure 3-3. CFRP grid: (a) rolls and (b) tubular configuration Tensile properties of the grid were dete rmined by testing two strands from each direction using the specimen configuration shown in Fig. 34(a). Each end of the strand was embedded into a short sec tion of steel pipe for approxima tely 4 in. The pipe was then filled with an expansive grout leaving a free le ngth of approximately 8 in. Two foil strain gauges were placed near the middle of the free-length of the specimen. Steel angles welded to the opposing ends of the pipe anchor s were used to attach the specimen to the loading apparatus (Fig. 3-4(b)). Loading apparatus consisted of a hydraulic actuator mounted to a stiff steel frame in which load was measured with a ring load cell. The average load rate for the four specimens wa s approximately 33 lbf per second with data acquired approximately every half second.

PAGE 45

27 (a) (b) Figure 3-4. CFRP strand tests: (a) CFRP grid strand specimen and (b) test set-up Table 3-2 shows the results of the tensile tests. Strands taken from the longitudinal direction are designated longit udinal (L) and strands taken fro m the transverse direction are designated transverse (T). All the specime ns ruptured at peak load. Three specimens ruptured away from the anchor and only one close to the anchor. All specimens ruptured at an interception of a longitudinal and a tr ansverse strand. The av erage peak load per strand was approximately 951 lbf and was approximately 16% lower than the load provided by the manufacturer which was 1100 lbf (TechFab 2004). The average cross sectional area was approximately 0.097 in2. The average strength was approximately 100.8 ksi and the average tensile modulus 9235 ksi. The strength of each specimen was calculated by dividing the peak load by the cross sectional areas while the modulus was determined by a linear regression of the stress -strain data (Fig. 3-5). The average of the two strain gages was used as the strain for each stress level. The data shown in Fig. 3-5 do not extend to the rupture strength of the specimen because the strain capacity of the strain gauges was exceeded. Steel An g le Steel Pi p e CFRP Grid Strand Strain Gauges Hand Hydraulic Pum p Hydraulic Jack Ring Load Cell

PAGE 46

28 Table 3-2. Results for CFRP grid specimens Specimen Grid roll direction Area (in2) Peak load (lbf) Strength (ksi) Modulus (ksi) T1 Transverse 0.0123841.5 68.5 7433 T2 Transverse 0.00911147.5126.2 8514 L1 Longitudinal 0.0094924.8 98.0 9486 L2 Longitudinal 0.0080891.0 110.8 11508 y = 7665.4x y = 8548.9x y = 9671.2x y = 11516x0 20 40 60 80 100 120 00.0030.0060.0090.012 Strain (in/in)Stress (ksi) T1 T2 L1 L2 Figure 3-5. Stress-strain curv es of CFRP grid strands Although insufficient tests were conducted to reveal statistical significance, some indication of strength consistency can be dete rmined from the test data. The coefficient of variance (COV) for the strength was 24.2% while for the tensile modulus 17.4%. Both COVs were high and were attributed to the variability between th e CFRP strands. Some strands had a thick layer of epoxy resin covering them, which resulted in a lower fiber volume fraction. According to the manufact uring company (TechFab 2004) strands in both the longitudinal and tran sverse direction have the same capacity. Tests conducted here indicated 9% higher capacity for the longitudinal strands compared to the transverse strands but that was attributed to the high variability and th e small number of specimens in each direction.

PAGE 47

29 Cylinder Testing Details Nine cylinders (three control and six gr id) were tested in displacement control mode in order to capture the post peak behavior of the specimens. The smallest rate that the MTS loadin g frame could handle was approximately 0.06 in. per minute that resulted in a load rate of approximately 106 psi per second. This load rate was approximately two times higher than the maximum load rate allowed by ASTM C39 (ASTM 2001). Typical load head movement rate and load rate curves from the control cylinders can be seen in Figs 3-6 and 3-7 respectively. The same load head movement rate was used for all cylinder specimens tested in displacement control mode. 0.00 0.03 0.06 0.09 0.12 020406080100 Time (sec)Movement (in) Figure 3-6. Typical load head move ment rate for control cylinders For the cylinder specimens to be tested in displacement control the 500 kip loading frame was used. Two Linear Variable Displa cement Transducers (LVDTs) were used to continuously record the length change of the specimens as load was applied. The two LVDTs were placed on opposing sides of the cylinder to determine the average length change of the cylinder specimen (Fig. 3-8).

PAGE 48

30 Load and movement data from the loading head as well as data from the LVDTs were collected using a data acquisition program at a rate of 50 Hz. This high rate was necessary to capture the post p eak behavior of the cylinders. 0 1 2 3 4 5 6 7 020406080 Time (sec)Axial Stress (ksi) Figure 3-7. Typical load ra te for control cylinders Figure 3-8. CFRP grid cylinder test set-up Cylinder Results and Discussion The average strength for the control cylinders tested in displacement control mode was 6.83 ksi and the COV 1.1%. Results from the control cylinders can be found in Table Load Head LVDT

PAGE 49

31 3-3. The control cylinders did not exhibit any significant post peak behavior but rather crushed after reaching the peak load. Typical control cylinder types of fracture were: (a) cone and split and (b) cone and shear. A cont rol cylinder after testing can be seen in Fig. 3-9(a). The stress-strain curves for the control cylinders ar e depicted in Fig. 3-10. The first control cylinder after reaching its peak load lost approximately half its strength almost immediately but did not fall apart and continued to carry load contrary to the other two control cylinders th at lost all load carry ing capacity abruptly soon after peak load. (a) (b) Figure 3-9. Cylinders after testi ng: (a) control, and (b) grid (arrows indicate ruptured CFRP grid strands) The average strength of the grid cylinders was 7.67 ksi with a COV of 8.5%. Table 3-3 contains results from all grid cylinders. Grid cylinders typically failed when CFRP grid strands ruptured. As exp ected, the concrete c over spalled off of the grid specimens before the peak load was reached but the cyli nders maintained most of their load carrying capacity until grid strand s started rupturing which took plac e in sequential rather than in an abrupt manner.

PAGE 50

32 0 2 4 6 8 10 0.0000.0040.0080.0120.016 Axial Strain (in/in)Axial Stress (ksi) Control 1 Control 2 Control 3 Figure 3-10. Stress-strain cu rves for control cylinders Table 3-3. Cylinder results Type Grid dia. (in.) Peak load (kip) Strain at peak load (in/in) Conc. core area (in2) Peak stress (ksi) Aver. stress (ksi) COV (%) Control 1 N/A 192.33 0.00251 28.274 6.80 Control 2 N/A 191.97 0.00232 28.274 6.78 Control 3 N/A 195.88 0.00236 28.274 6.92 6.83 1.1 Grid 1 5.25 184.65 0.00281 21.647 8.53 Grid 2 5.25 146.33 0.00200 21.647 6.76 Grid 3 5.25 178.16 0.00256 21.647 8.23 Grid 4 5.5 167.19 0.00279 23.221 7.20 Grid 5 5.5 174.39 0.00256 23.221 7.51 Grid 6 5.5 180.66 0.00279 23.221 7.78 7.67 8.5 The carbon fibers in the CFRP grid are embe dded in an epoxy matr ix that creates a smooth surface on the outside faces of the CFRP strands, which may have contributed to spalling. A grid cylinder after testing with ruptured hoop CFRP grid strands can be seen in Fig. 3-9(b). Experimental stress-axial st rain curves for specimens Grid 1 to 3 and specimens Grid 4 to 6 were plotted in Figs 3-11 and 3-12 respectively. The stress values for the grid cylinders were ca lculated based on the area of th e concrete core enclosed by the CFRP grid and the axial strain was calcu lated as the average change in the length,

PAGE 51

33 measured by the two LVDTs mounted on the lo ading plattens, of the cylinder over the original length. 0 2 4 6 8 10 0.0000.0040.0080.0120.016 Axial Strain (in/in)Axial Stress (ksi) Grid 1 Grid 2 Grid 3 Figure 3-11. Stress-strain curves for grid cylinders 1, 2 and 3 0 2 4 6 8 10 0.0000.0040.0080.0120.016 Axial Strain (in/in)Axial Stress (ksi) Grid 4 Grid 5 Grid 6 Figure 3-12. Stress-strain curves for grid cylinders 4, 5 and 6 The post peak behavior for all grid cylinde rs was different than that of control cylinders. Grid cylinders reached high er peak loads and accommodated larger displacements than the control cylinders. This is especially evident in Fig. 3-13 where typical experimental stress-axia l strain curves from both control and grid specimens were plotted. The areas of the stress-strain curves are presented in Table 3-4. The area under the stress-strain curve of the grid cylinders was typically 2.5 times larger than the area of

PAGE 52

34 the control cylinders. Specimens Grid 4, 5 and 6 had approximately 25% more area under the stress-strain curve than specimens Grid 1, 2 and 3. 0 2 4 6 8 10 0.0000.0040.0080.0120.016 Axial Strain (in/in)Axial Stress (ksi) Control 2 Grid 3 Grid 5 Figure 3-13. Stress-strain curves for typical control and grid cylinders Table 3-4. Area under stress-strain curve Type Area (ksi in/in) Aver. area (ksi in/in) Control 1 0.0169 Control 2 0.0157 Control 3 0.0124 0.015 Grid 1 0.0341 Grid 2 0.0368 Grid 3 0.0304 0.0338 Grid 4 0.0395 Grid 5 0.0412 Grid 6 0.0456 0.0421 All grid cylinders reached a peak axial load followed by a descending post peak curve. Other researchers observed such a beha vior in lightly confined concrete. Harries and Kharel (2003) made similar observations for their one and twoply E-Glass confined cylinders. Sfer et al. (2002) studied the behavior of concre te under triaxial compression and their axial stress-strain curves at low confining pressures had a descending post peak curve. The increase in the concrete strengt h was between 10% and 20%, which compares to the 11% increase observed for our cylinders In the case of the CFRP grid confined

PAGE 53

35 concrete even with the two grid layers the concrete was still considered lightly confined since the two CFRP grid layers added up to less than one layer of carbon fiber fabric when the CFRP grid strand thickness was spr ead uniformly over the surface area of the concrete core. In addition the strength and modulus of the CFRP grid was found to be lower than typical carbon composites, which further reduces its confinement effectiveness. The post peak behavior observe d for the CFRP grid cylinders verified the observations made by Harries and Khar el (2003) and Sfer et al. (2002). Empirical Confinement Model Most models for concrete confined with CFRP reinforcement assume a single layer of carbon fabric will provide adequate reinforc ement to sufficiently confine the concrete. When the CFRP grid is used as confinement reinforcement it is expected that the confining pressure and confinement effectiveness will be less than that of a fully jacketed system. Therefore models developed using data from relatively highly confined concrete may not be adequate. Some of the models inve stigated calculated a stress-strain curve for the grid confine concrete that was bilinear with ascending portions which contradicts the experimental curves. Several existing models were investigated to model the behavior of CFRP grid confined concrete. All of the existing mode ls examined are based on a constant thickness of the FRP material that fully covers the external surface of the concrete. The hoop grid strands only cover part of th e area. One approach when usi ng the existing models is to determine an equivalent full coverage thickn ess for the hoop strands. The equivalent grid thickness (teg) was calculated based on the following expression: h t b n n tg g gs l eg (3-1)

PAGE 54

36 where nl was the number of CFRP grid layers, ngs was the number of grid strands, bg was the width of the grid strands, tg was the thickness of the grid strands and h was the height of the cylinder. The secant modulus of elastic ity of concrete (Ec) was calculated based on existing empirical expressions (Nawy 2003): '57c cf E (3-2) where fc was the minimum specified compressive stre ngth of concrete, in psi, at 28 days and Ec is in ksi. To determine the confinement strength (fru) simple pressure vessel mechanics were used (see Fig. 3-14). The equilibrium conditi on required the force from the confining strength be equal to the fo rce in the FRP encasement. dg frufgu tegfgu teg tegteg Carbon grid Figure 3-14. Cylindrical pressure vessel The equilibrium condition for the confined cylinder was expressed as follows: gu eg g ruf t d f 2 (3-3)

PAGE 55

37 where fru was the confinement strength, dg was the diameter of the CFRP grid tube and fgu was the ultimate strength of the CFRP grid strands. By rearranging equation 3-3 the confinement strength ( fru) was calculated using the following: gu g eg ruf d t f 2 (3-4) Assuming that the confined concrete was in a triaxial stress state, the increase in strength provided by the confinement was reflected in the maximum stress ( fcc) for a cylindrical specimen, which was de fined as (Mander et al.1988): ru c ccf k f f 1 ' (3-5) where k1 was the confinement effectiveness coe fficient. The confinement effectiveness coefficient for concrete confined by steel is usually taken between 2.8 and 4.1. Campione and Miraglia (2003) found that the above values overestimate the confinement effectiveness coefficient for concrete wra pped with FRP. They found the confinement effectiveness coefficient for FRP wrapped concrete to be two. Therefore, the confinement effectiveness coefficient was assumed to be equal to two. The axial strain of CFRP grid confined concrete at the peak stress (co) was determined in a similar manner as unconfined concrete using the following expression (MacGregor 1997): c cc coE f' '8 1 (3-6) Equations 3-5 and 3-6 were combined with the modified Hognestad (Park and Paulay 1975(a)) stress-strain equation as follows:

PAGE 56

38 2 '2co c co c cc cf f (3-7) co c c cc cD f f 1' (3-8) where c was the concrete strain, o was the strain at peak st ress of unconfined concrete and cu was the ultimate strain. These equations were plotted in Fig. 3-15. The modified Hognestad equations model the ascending branch (AB) with a parabo lic relationship and the descending branch BC with a linearly de scending curve. The equation for region BC is based on the deterioration constant (Dc) that controls the slope of the line. A B C Stress fcStrain c' cfocuRegion AB 2 '2o c o c c cf f Region BC o c c c cD f f 1' Figure 3-15. Modified Hogne stad stress-strain curve The material properties of the CFRP grid strands were used to construct the stressstrain curve of the CFRP grid confined c oncrete. The average strength of the control cylinders tested in displacement control mode was taken as the st rength of unconfined concrete (fc). An average CFRP grid tube diameter of 5.375 in. was used. The ultimate concrete strain cu was assumed to be 0.0061 in/in. The average stress-strain curve for the CFRP grid confined concrete was calculated using data from all grid cylinders. The

PAGE 57

39 deterioration constant was taken equal to 120 to match post peak experimental data. The experimental and empirical model stress-strain cu rves are depicted in Fig. 3-16. 0 2 4 6 8 10 0.0000.0030.0060.0090.012 Axial Strain (in/in)Axial Stress (ksi) Exper. (aver. of 6 tests) Empirical model Figure 3-16. Experimental and empirical model stress-strain curves The modified Hognestad curve calculated using the empirical model matches well with the average experimental curve calculate d from the data available from the CFRP grid confined cylinders. The average experiment al peak stress was 7.7 ksi while the peak stress calculated from the empirical model was 7.5 ksi. The calculated value was 2% lower than the experimental average. The aver age experimental strain at the peak stress was 0.00259 in/in while the model predicted a strain of 0.00288 in/in at peak stress. The predicted strain value was 11% higher th an the average experimental value. Conclusions Based on the results presented the following conclusions were drawn: The CFRP grid does not produce a highly confin ed concrete. This was expected since the amount of CFRP material provided by the grid is low due to its large openings. Significant improvement, however, was observe d in the ductility of the concrete cylinders with embedded CFRP grid. The ultim ate strain for the grid cylinders was 2 times the ultimate strain of the control cylinders. Grid confinement also resulted in an increase in the concrete strength of approximately 11%.

PAGE 58

40 The larger CFRP grid diameter cylinders were more ductile compared to the smaller CFRP grid diameter cylinders with the ex ception of cylinder Grid 2. However the difference in diameters and the number of cylinders was small and therefore this conclusion is drawn with caution. The equivalent grid thickness was a valid wa y of converting the concentrated thickness of the CFRP grid to an equivalent thickne ss over the surface area of the concrete core. The modified Hognestad provides an accurate empirical prediction of the behavior of concrete confined with the CFRP grid.

PAGE 59

41 CHAPTER 4 RECTANGULAR CONCRETE SECTI ON WITH CFRP GRID TUBES Introduction Two rectangular beams were built and tested to evaluate the e ffect of grid tubes made from CFRP grid on the behavior of a non-ductile beam. The purpose of the beams was to measure the amount of ductility that confinement of the compression zone can produce in a compression controlled beam and to improve beam ductility. Testing of these beams verified the a ssumption that confinement and therefore concrete ductility can be achie ved without having to wrap th e whole beam with the CFRP grid but by confining the compression zone with a series of carbon grid tubes. Both beams were designed to fail by conc rete crushing. The beam with the grid tubes had an improved ductility compared to th e beam with no grid tubes due to concrete confinement of the compression zone. The cove r concrete in the compression zone of the tube beam crushed earlier than the conc rete inside the CFRP grid tubes. Experimental Program Specimen Construction Table 4-1 contains some of the constructi on details for the two rectangular beams. The first beam had no grid tubes and served as the control beam (S ee Fig. 4-1) and the second beam (tube beam) had two grid tubes placed in the compression zone (See Fig. 42). The width of the beams was 12 in. and th e height 18 in. The flexural reinforcement consisted of 8 #10 steel reinforcing bars (60 ksi, 1.25 in. diameter) placed in two rows (Figs 4-1 and 4-2). The amount of steel used in the beams is large because the beams

PAGE 60

42 were designed to be overeinforced to force the failure into the compression zone. Steel stirrups (0.375 inches) were spaced at 3 in. to provide shear resistance. Stirrups were not placed in the center portion of the beams (see Fi gs 4-1 and 4-2). In the case of the tube beam the two CFRP grid tubes were placed next to each other approximately 0.75 in. from the top of the beam (Fig. 4-2). The tubes did not extend to the ends of the beam but rather were cut short approximately 1.5 ft from each end. The CFRP grid tubes had a diameter of 6 in. and were made w ith two CFRP grid layers. Table 4-1. Test matrix for tube beams Beam Grid tube No. of grid tubes No. of grid layers Dia. of grid tubes (in) Control No 0 0 N/A Tube Yes 2 2 6 3" 5" 6' 3" 6' 3" 2' 8" 16' 1' 6" 1" Clear 1" Clear 18"#3 Stirrups 8 #10 Bars12" 2" Clear 1.5" 2.75" 3" Figure 4-1. Longitudinal (top ) and cross-sectional (botto m) views of control beam

PAGE 61

43 The CFRP grid was formed into a circular tube using a 6 in. diameter plastic pipe and was held in place by a thin rope wra pped around the tube along its length (See Fig. 43). The CFRP grid was laid in the sun for a few hours to soften the epoxy matrix and facilitate the formation of the tubes. More de tails on the properties of the CFRP grid can be found in chapter 3. 5" 1' 6" 6' 3" 6' 3" 2' 8" 16' 8 #10 Bars 13' 1.5" 1" Clear 1" Clear 18"#3 Stirrups12" 2" Clear 2.75" 3" 6" 0.75" Figure 4-2. Longitudinal (top) and cross-sectional (bottom) views of grid tube beam Both beams were cast using ready-mix c oncrete with 28-day design strength of 5000 psi, and maximum aggregate size of 0.375 in. The control beam (See Fig. 4-4(a)) concrete was placed and vibrated in typical manner (Fig. 4-4(b)). One grid tube was inserted in the tube beam before concrete placement began to allow room for placing and vibrating the conc rete (see Fig. 4-5). When the concrete reached the bottom of the first grid tube the second tube was installed next to the first

PAGE 62

44 grid tube and the remainder of the concrete was placed. Vibration was also applied to the tube beam. Figure 4-3. Formation of CFRP grid tubes (a) (b) Figure 4-4. Control beam: (a) concrete casting, and (b) co ncrete vibration

PAGE 63

45 Once the form was full, the top of the beams was finished and the beams were left in the laboratory to cure. The beams were allo wed to cure for a total of 44 days before testing. Figure 4-5. Concrete placing (tube beam) Eight standard (6 x 12 in.) cylinders were cast along with the beams (see Fig. 4-6). The cylinders were tested on the same day as the beams to determine the actual concrete strength at testing. Test Set-Up and Procedure The two beams were tested in a simply supported four-point bending configuration (see Fig. 4-7) in displacement control mode, that is, a constant displacement rate was

PAGE 64

46 applied independently of the amount of load The span length between the two supports was 14 ft, whereas the total le ngth of the beams was 16 ft. Figure 4-6. Concrete cylinder casting LVDT 60 mm Foil Gauge Spreader Beam Tilt Meter Actuator Load Cell 5' 6" 3'5' 6" 1' 6" South Support North SupportD1 D2 D3 D4 D5 D6 D7 D8 D9 D10 D11 D12 D13 D14 D15 1' Typ. Figure 4-7. Test set-up for both beams

PAGE 65

47 A hydraulic actuator was used to apply the displacement to the beams. The applied displacement was distributed to the two load points using a steel spreader beam. From the spreader beam the displacement was transferre d to the beam using two steel rollers. The rollers allowed the loading mechanism to fo llow the rotation of the beam as the load increased, whereas steel plates distributed the load to avoid localized failure of the concrete material that could ha ppen if the load was applied to a very small area or single point. A load cell was used to measure the applied force. The load points were located 5.5 ft from each support. This created a 3-ft region in the center of the span with pure flexure. The beams were loaded at a rate of 0.004-in. per second. The displacement was applied monotonically until the beam coul d no longer sustain a significant load. Instrumentation A series of 15 linear variable differen tial transducers (LVDTs) were placed at 12in. intervals to measure the displacement of the beam at differ ent locations along the length of the beams (see Fig. 4-7). The LVDTs were labeled from north to south as D1 through D15. Four tilt meters, two at the supports and two at 3 ft from the supports, were used to measure the rotation of the beams at those lo cations (see Fig. 4-7). The tilt meters were labeled from north to south as T1 through T4. Foil strain gages were attached on the sides of the beams at mid-span (Fig. 4-8) and on top of the beam (Fig. 4-9). The strain gages at the side of the beams were labeled from the top down as SE1 through SE7 for the east side and SW1 trough SW7 for the west side of the beam. The two bottom strain gages on the sides of the beams were located approximately at the same level as the two layers of the steel flexural reinforcement and

PAGE 66

48 they were place there to measure the strains in the concrete at those locations. Before concrete cracking the strains in the concrete and the steel are the same. The strain gages on the top of the beams were labeled from north to south as ST1 through ST3. Beam Top Beam Centerline 1" 4 @ 1.5" 3" 2.8" SE3 SE2 SE1 SE4 SE5 SE6 SE7 Figure 4-8. Strain gage arrangement (s ide view of center portion of the beam) Load Points 8" 8" ST3 ST2 ST1 Figure 4-9. Strain gage arrangement (t op view of center portion of the beam) The strain gages on the side of the beams were used to measure strain across the cross-section of the beams whereas the stra in gages on top to measure any transverse expansion of the compression zone due to the Poisson effect. Data from all instrumentation devices were recorded using a data acquisition system at a rate of 4 Hz.

PAGE 67

49 The actual test set-up with all the instrumentation placed at the appropriate locations is depicted in Fig. 4-10. Figure 4-10. Test set-up for both beams before testing Results and Discussion Cylinder tests The cylinders were tested on the same day as the beams. A total of 8 cylinders were tested using a cylinder tester. All cylinders tested were capped using a sulfur cement cap at each end to uniformly distribute the load from the loading head to the concrete cylinder. Table 4-2 contains the results from th e cylinder tests. The average compression strength for the cylinders tested was 6.06 ks i and the coefficient of variance was 2.3%. Typical cylinder types of fracture were: (a ) cone and (b) cone and shear. The low coefficient of variance was an indication of strength consistency of the concrete.

PAGE 68

50 Therefore, the unconfined strength of the concre te in the beams to be tested was taken as the average of the 8 cylinders. Beam tests The load-displacement (P) curve for the control beam was bilinear (Fig. 4-11). Two distinct slopes can be distinguished: The slope of the initial part of the Pcurve remains constant up to a load of approximate ly 100 kips. The slope of the curve from 100 kip total load to peak load was lower possibly due to the reduction of the effective crosssection caused by the growth of concrete cracks It was evident that the lack of any post peak behavior exhibited by the control b eam resulted in a non-ductile failure. Table 4-2. Experimental re sults from cylinders tests Cylinder Peak load (kip) Concrete area (in2) Peak stress (ksi) Aver. stress (ksi) COV (%) 1 172.16 28.274 6.09 2 175.89 28.274 6.22 3 164.70 28.274 5.83 4 173.17 28.274 6.13 5 167.54 28.274 5.93 6 173.10 28.274 6.12 7 168.31 28.274 5.95 8 174.90 28.274 6.19 6.06 2.3 0 20 40 60 80 100 120 140 160 0.00.30.60.91.21.51.8 Displacement (in)Total Load (kips) Control Tube Figure 4-11. Load-displacement curves for control and tube beams

PAGE 69

51 The curve for the tube beam was also bilinear up to peak load (Fig. 4-11). However, the post peak behavior of the tube beam was significantly different compared to the behavior of the cont rol beam. Although the tube beam did loose a portion of its load bearing capacity instantly when it reach peak load it maintained most of its capacity, approximately 88% of peak and continued to displace. The peak loads were approximately 148 kips for the control beam and 153 kips for the tube beam. There was a nominal increase in the peak load of the tube beam of approximately 3% compare to the control beam. The control beam failed due to concrete cr ushing in the constant moment region at peak load (See Fig. 4-12(a)). The tube beam also failed due to c oncrete crushing in the constant moment region (See Fig. 4-12(b)). However, the amount of damage to the compression zone of the control beam was more severe than that of the tube beam (See Fig. 4-12). The visual evidence also point towa rds a better performance of the tube beam compared to the control beam. (a) (b) Figure 4-12. Compression zones for both beams after testing: (a) control beam and (b) tube beam

PAGE 70

52 The concrete inside the CFRP grid tubes ma intained the circular shape of the tube even after the tube failed and confinement was lost (Fig. 4-13). The CFRP grid ruptured at a particular location and not throughout the constant moment region which was why the concrete maintained that shape. Figure 4-13. Tube beam compression zone after testing Fiber Model Analysis The peak loads for both beams were calcula ted using a fiber model analysis of the beam cross-section. The compression zone of the tube beam was separated into two regions with regard to concre te properties. The first region was the concrete cover on top of the CFRP grid tubes and the second region was from the neutral axis to the top of the CFRP grid tubes (see Fig. 4-14). The first region was extended approximately 0.25 in. below the top of the CFRP grid tubes to acc ount for the unconfined concrete at the sides and between the grid tubes. The first regi on was assigned unconfined concrete properties and the second region confined pr operties. The concrete area from the neutral axis to the

PAGE 71

53 bottom of the grid tubes was unconfined but was treated as confined concrete for simplicity and because the strain s in that area close to the neutral axis were small and therefore the effect on the strength was mi nor. The unconfined region was divided into one rectangular fiber layer while the confined region into eight rect angular fiber layers. For the control beam case the compression zone was treated as an unconfined concrete region and was divided in to eight fiber layers. Some of the assumptions employed in this fiber model in clude perfect bond between concrete and the reinforcing bars (s train compatibility), plain sections remain plain (linear strain distributi on), the area below the neutral axis was considered cracked and was ignored in the force and mome nt calculation and monotonic loading and deformation of the section. c 1" N. A. 1" Unconfined concrete Confined concrete 0.75" Grid Tube Figure 4-14. Tube beam cr oss-sectional fiber model

PAGE 72

54 The compressive force in each fiber layer was calculated as the product of the area of the fiber layer and the average stress. Th e average stress was determined based on the strain in the fiber layer and the stress-strain curves of c oncrete. The Hognestad parabola was used to calculate the stress-strain cu rve of unconfined concrete. The modified Hognestad was used to calcula te the stress-strain curve of confined concrete. The parameters of the modified Hognestad were determined based on the available data from confined concrete cylinder tests. The tensile force was calculated as the product of the area of steel reinforcement and the steel stress which was determined ba sed on the average strain of the two steel layers. The steel stress was calculated base d on an assumed elastic perfectly plastic stress-strain curve with yield strength of 60 ksi and modulus of elasticity of 29000 ksi. The moment in the cross-section for the applied curvature distribution was determined by summing moments about the neutral axis. The moment curvature diagram was calcula ted by applying increasingly larger top concrete compressive strains (c) to the cross-section and varying the location of the neutral axis (c) until equilibrium of the axial forces (zero) in the cross-section for the applied strain was achieved. The curvature of the section ( = c / c) was then calculated based on the concrete compressive strain and the location of the neutral axis. The fiber model peak loads were 151 kips for the control beam and 156 kips for the tube beam. The experimental peak loads were 148 kips and 153 kips for the control and tube beams respectively. Therefore the fibe r model calculated the peak loads for both beams and could be used to calculate peak loads for beams utilizing the CFRP grid tubes. The fiber model peak loads were approxima tely 2% higher that the actual loads.

PAGE 73

55 Analysis of Strain Data The strains on the two opposite beam sides (east and west) were the same as it is evident from Fig. 4-15. This was typical for all strain gages in th e compression zone of the each beam. Based on the fact that the strains on the two opposite beam sides were the same, the strain at each gage location wa s taken as the average of th e two strain gages at that location. For example, the strain at 1 in. from the top of the beam (S1) was taken as the average of SE1 and SW1. The same appro ach was used for all other locations. 0 20 40 60 80 100 120 140 160 01000200030004000 Compressive Strain (microstrains)Total Load (kips) SE1 SW1 Figure 4-15. Load-strain curves for strain gages at opposing locations (control beam) The maximum average strain at peak load recorded during the te st for the control beam was at S1 location and was approximately 2840 (see Fig. 4-16). The other average strains were smaller as expected, been closer to the neutral axis of the beam, but when concrete crushing started the average measured strains at S2, S3, S4 and S5 increased rapidly due to the f act that the loss of concrete moved the extreme compression closer to their location. This was typical fo r the tube beam as well. However the strains recorded for the tube beam were smaller than the strains for the control beam. The maximum average strain recorded at peak load for the tube beam was at location S1 and

PAGE 74

56 was approximately 2550 which was approximately 10% lower than the strain recorded for the control beam. 0 20 40 60 80 100 120 140 160 01000200030004000 Compressive Strain (microstrains)Total Load (kips) S1 S2 S3 S4 S5 Figure 4-16. Load-strain cu rves for control beam The compressive strain for the extreme conc rete fiber can be calculated by plotting the strain profile (see Figs 4-17) of the beam. Assuming a linear distribution of strain through the beam cross-section a straight line can be fitted and the equation of the fitted line can be used to determine the strain at the extreme concrete fiber. The fitted lines were in good agreement with the experimental results as it was evident in Figs 4-17. The average R2 value (the proportion of th e variance in y attributable to the variance in x) of the fitted lines for the tu be beams was 0.999 which was close to a perfect match (R2 = 1). This was typical for both the control and tube beams. The high R2 values support the assumption of a linear distribution of strain through the beam cross-section which also suggests that plane sections remain plain. The strains at the extreme concrete fiber in compression at increasing load levels were calculated based on the fitted line e quations and are presented in Table 4-3. The strain at the extreme compression fiber at peak load (crushing strain) for the control beam was approximately 3170 whereas for the tube beam was 3010 The crushing strain

PAGE 75

57 for the tube beam was approximately 5% lower than the crushing strain calculated for the control beam. -10 -8 -6 -4 -2 0 01000200030004000 Strain (microstrains)Strain Gage Location (in) P = 21.9 kips P = 43.7 kips P = 65.6 kips P = 87.3 kips P = 109.0 kips P = 148.0 kips Figure 4-17. Compressive strain profile for control beam Table 4-3. Experimentally calcu lated top compressive strains Beam Load (kips) Experimentally calculated top strain ( ) 21.9 333 43.7 681 65.6 1048 87.3 1436 109.0 1883 Control 148.0 3167 22.4 421 45.4 770 67.4 1127 89.2 1481 110.2 1891 Tube 152.3 3010 Design codes usually assume a c oncrete crushing strain of 3000 (ACI Committee 318), which agrees well with th e crushing strains calculated from the experimental data. Typically, concrete crushing strains vary from 3000 to 4000 (Nawy 2005; Hasoun and Al-Manaseer 2005; Hassoun 2002; MacGregor 1997). Lower strength concretes (less than 5000 psi) are typically more ductile and have higher crushing strains

PAGE 76

58 than higher concrete strengths (more than 5000 psi) that tend to be more brittle and have lower crushing strains. The strength of the concrete used in these beams was approximately 6100 psi which was relatively high. Based on the crushi ng strain values it ca n be concluded that the concrete used in this beams was brittle as expected based on its high strength. The compressive strains were reduced due to the presence of the CFRP grid. This was attributed to the fact that the CFRP grid restrains concrete movement which is manifested in the reduction of the strains. As the concrete in the compression zone is compressed it also expands laterally. That la teral expansion of the tube beam however was restrained by the CFRP grid which also reduced the longitudinal shortening of the compression zone hence the reduction in the measured strain. Assuming that plane sections remain plan e the strains at each steel layer can be determined using similar triangles (see Fig. 418). Strains for both st eel layers using this procedure are presented in Table 4-4. d c c d N. A.cs Figure 4-18. Assumed strain distribution

PAGE 77

59 Table 4-4. Steel strains calculat ed using experimental data Beam Load (kips) Steel strain layer 1 ( ) Steel strain layer 2 ( ) 21.9 248 141 43.7 550 324 65.6 850 502 87.3 1150 676 109.0 1452 840 Control 148.0 2008 1059 22.4 418 264 45.4 812 522 67.4 957 575 89.2 1199 707 110.2 1442 831 Tube 152.3 1829 942 The strain in steel layer 1 at peak load was approximately 2010 for the control beam and 1830 for the tube beam. This represents a difference of approximately 9%. Both values were close to the yield strain the 60 ksi steel calculated based on Youngs modulus as 2070 In reality the CFRP grid tubes reduce the rotations of the tube beam which also means a reduction in the curvature of the b eam. The lower curvature obviously causes a reduction in the compressive strains as well as the tensile steel strain. Three strain gages (ST1, ST2 and ST3) on the top of the beams were used to determine transverse expansion of the compre ssion zone due to Poisson effect. The rate of strain increase was relatively small up to a load of 120 kips and increased after that (see Fig. 4-19). The rate was higher for gage ST2 located at mid-span. Very close to peak load the transverse strain at the mid-span lo cation increased very ra pidly an indication of an imminent concrete failure. This was typi cal behavior for both the control and tube beams.

PAGE 78

60 The reason gages ST1 and ST3 did not record a rapid increase of st rain as did gage ST2 was due to their location. Gages ST1 and ST3 were located close to the load plates that provided confinement to the surrounding co ncrete. The confining effect of the load plates was much higher close to the load point s and decreased away from the load points. At the mid-span location that was located the farther from the load points than any other point inside the consta nt moment region the effect of th e load platens was much smaller. The confinement from the load plates restra ined the tensile lateral expansion of the concrete and reduced the lateral strains at the two locations close to the load points. 0 20 40 60 80 100 120 140 160 01000200030004000 Top Poisson Strain (microstrains)Total Load (kips) ST1 ST2 ST3 Figure 4-19. Transverse expansive strains for control beam The strain gages attached to the top of bot h beams in the transverse direction were able to detect the impending concrete failure as the data from gage ST2 indicated. However the peak strains recorded by gage ST2 for the control and tube beams were significantly different in magnitude. The peak strain of the control beam was approximately 3170 while the peak strain for the tube beam was 2230 That difference can be explained by the presence of the CFRP grid tubes. As the concrete tries to expand laterally, due to the Poisson effect, th e CFRP grid tubes rest rain and resist that

PAGE 79

61 movement. That results in a reduction of the lateral expa nsion which is obvious by the lower recorded strain. Measured Rotations Four tilt meters were used to measure the rotations of the beams. The rotations for both the control and tube beams at increas ing loads are reported in Table 4-5. The measured rotations of the contro l beam were lower that the m easured rotations of the tube beam for the same amount of load. That wa s due to the CFRP grid tubes improving the resistance of the tube beam against rotation. The differences in rotation grew as the load increased from approximately 20% for a load of 21.9 kips to approximately 25% for a load of 109.1 kips. Table 4-5. Rotations measured by tilt meters Beam Load (kips) Tilt meter T1 (degrees) Tilt meter T2 (degrees) Tilt meter T3 (degrees) Tilt meter T4 (degrees) 21.9 -0.1377 -0.1209 -0.1244 -0.1528 43.7 -0.2979 -0.2660 -0.2628 -0.3240 65.6 -0.4705 -0.4239 -0.4100 -0.5066 87.3 -0.6530 -0.5942 -0.5749 -0.7011 109.1 -0.8590 -0.7987 -0.7735 -0.9144 Control 148.0 -1.3169 -1.2593 -1.2236 -1.3776 21.9 -0.1080 -0.0943 -0.0977 -0.1218 43.7 -0.2350 -0.2089 -0.2045 -0.2511 65.6 -0.3685 -0.3283 -0.3176 -0.3868 87.3 -0.5106 -0.4595 -0.4456 -0.5326 109.1 -0.6678 -0.6136 -0.5948 -0.6894 Tube 152.8 -1.0527 -1.0000 -0.9724 -1.0675 The rotations of the two beams based on the displacement profiles were also calculated by fitting a 6th order polynomial curve to the displacement profiles and then taking the first derivative of the polynomial equation. The calculated rotations for the same loads and locations are presented in Table 4-6.

PAGE 80

62 The rotations calculated based on the disp lacement profiles typically exhibited the same trends as the rotations recorded by the tilt meters. The tilt meter rotations were higher than the rotations calculated based on the displacement profiles. That could be due to the fact that the tilt rotations were essentially the rotations of the beam at the point the tilt meters were located whereas the calculated rotations were based on a line that was f itted through several points along the entire length of the beam. On the average the tilt meter rotations were approximately 24% higher than the rotations calculated from the displacement profiles from the control beam (see Fig 4-20) and approximately 10% for the tube beam (see Fig. 4-21). The rotations for the T2 location were graphically presented for both th e control and tube beam and were used to demonstrate the differences. These differences we re typical for all four rotation locations. Table 4-6. Rotations calculated based on the displacement profiles Beam Load (kips) Rotation at T1 location (degrees) Rotation at T2 location (degrees) Rotation at T3 location (degrees) Rotation at T4 location (degrees) 21.9 -0.1027 -0.0909 -0.0858 -0.1530 43.7 -0.2306 -0.2002 -0.1914 -0.2968 65.6 -0.3425 -0.3193 -0.3094 -0.3991 87.3 -0.4611 -0.4485 -0.4287 -0.5429 109.0 -0.6073 0.6016 -0.5717 -0.7047 Control 148.0 -0.9282 -0.9626 -0.9110 -1.1150 22.4 -0.0549 -0.0867 -0.0776 -0.1402 45.4 -0.1728 -0.1966 -0.1814 -0.2667 67.4 -0.2999 -0.3116 -0.2931 -0.4008 89.2 -0.4202 -0.4388 -0.4147 -0.5301 110.2 -0.5346 -0.5901 -0.5611 -0.6704 Tube 152.3 -0.8938 -0.9798 -0.9397 -1.0600 Based on the rotation data it can be concl uded that the calculati on of beam rotations from the displacement profiles was valid. The fact that the two methods of determining

PAGE 81

63 beam rotations yielded comparable results makes both methods acceptable. Therefore, determining the curvature of the beams using the displacement profiles was also validated based on the rotation results. If rotation results were valid then curvature results were also valid because the same basic equations were used to determine both. 0 20 40 60 80 100 120 140 160 -1.5-1.2-0.9-0.6-0.30.0 Rotation (degrees)Total Load (kips) T2-Tilt T2-Displ. Figure 4-20. Measured rotations at increasing loads (control beam) 0 20 40 60 80 100 120 140 160 -1.5-1.2-0.9-0.6-0.30.0 Rotation (Degrees)Total Load (kips) T2-Tilt T2-Displ. Figure 4-21. Measured rotati ons at increasing loads (tube beam) Moment-Curvature Analysis The LVDT measurements, at different lo cations along the lengt h of the beams, were used to construct the displacement profil e curves (see Fig. 4-22) at increasing loads. The displacement profile equation was genera ted by fitting a sixth order polynomial line

PAGE 82

64 to the displacement profile curves (Fig. 4-22). The fitted lines were in good agreement with the displacement data (average R2 = 0.997). The polynomial displacement profile equation of the beam was used to determin e the curvature at specific points along the length of the pile. The second derivative of the polynomial displacement profile equation is the curvature equation. y = 2.6E-13x6 1.3E-10x5 + 2.1E-08x4 1.3E-06x3 + 3.6E-05x2 4.0E-03x 5.8E-02-0.4 -0.3 -0.2 -0.1 0 0306090120150180 Displacement Location fr om North Support (in)Displacement (in) P = 43.7 kips Poly. (P = 43.7 kips) Figure 4-22. Displacement curve and fitted polynomial line for control beam at 43.7 kips To model the behavior of the beams a program that generated the sectional moment-curvature (M) relationship was used (Cons olazio, Fung and Ansley 2004). The program describes cross sectional geom etry using piecewise linear segments for both the exterior and interior boundaries of the section. Interi or boundaries represent voids in the section. Curved boundaries such as the boundaries of circular sections are approximated by using multiple linear segments The reinforcing bars are modeled as cross-sectional areas locate d at specific locations. Some of the assumptions associated with the program are the following: Sign convention is positive for co mpression and negative for tension Plain sections remain plain which means th at the strain distribution for the crosssection is linear

PAGE 83

65 Perfect bond between the reinforcement a nd the concrete (strain compatibility) Monotonic loading and deformations of the section Ignore confining effect on concrete The internal section forces of the cross-section are gene rated for a specified section curvature and a specified axis location. Th e elastic centroid of the cross-section is choosen as an arbitrary reference centroid. The flexural moments of the section are computed with reference to axes that pass through the reference centroid. The contribution to the axial force a nd moment of the compression zone of the concrete is determined by first meshing the geometry into trapezoids and then applying numeric integration procedures. By numerical ly integrating the concrete stress surface over each trapezoid in the meshed section th e contributing force from each trapezoid is found. The sum of all the trapezoid forces is the contribution of the concrete to the internal axial force. The moment contribu tions are computed by multiplying the force from each trapezoid with the distance between the reference centroid and the force. The strain in the reinforcing bars is assumed to be uniform and is used in conjunction with the reinforcement stress-strain diagram to compute the stress. The force in the bar is the area of the bar times the st ress taking into account concrete displaced by the reinforcement bars. The sum of all bar forces is the contribution of the reinforcement to the internal axial force. The moment cont ributions of the reinforcement are computed in the same manner as for concrete using the distance from the reference centroid. The total internal axial force is the summation of all the concrete and reinforcement axial forces with their respective signs. The total moment of the section is the summation of the moment contributions of concrete and reinforcement.

PAGE 84

66 The complete moment-curvature diagra m is calculated by applying increasingly larger levels of section curvature to the cr oss-section using a mome nt curvature algorithm to find the location of the neutral axis by iteration. For the case of the tube beam a concrete confinement model was integrated into the Mprogram. However, the Mprogram is not configured to assign different material properties for confined or unc onfined concrete bu t rather assigns the same properties throughout the section. Therefor e when used to produce the Mcurve of the tube beam confined concrete properties were used for the entire section. Ho wever, the top cover layer was removed and the secti on was analyzed as a section w ith a depth of 17 in. rather than the actual 18 in. This solution is a lower bound solution for the strength evaluation of the CFRP grid tube beam. From here on the results from the moment curvature program will be referred to as theoretical results. The Mcurves for both beams were also calculated based on the fiber model described in a previous s ection in this chapter. The experimental, theoretical and fiber model Mdiagrams were calculated for both beams. The theoretical and fiber model Mdiagrams for the control beam (see Fig. 4-23) were the same. However, the theoretical peak load is approximately 5% lower that the peak load calculated using the fiber mode l. This difference was attributed to the different models used to repr esent the stress-strain behavior of concrete between the two models. The stiffness of the mid-span locati on was lower that the theoretical fiber model stiffness. The stiffness of the south load lo cation was comparable to the stiffness of the diagrams calculated theoretically and using the fiber model.

PAGE 85

67 0 100 200 300 400 500 00.00020.00040.00060.00080.001 Curvature (rads/in)Moment (k-ft) Exp. Mid-Span Theoretical Exp. South Load Fiber Model Figure 4-23. Experimental and theoretical Mcurves for control beam The experimental Mbehavior of the tube beam wa s comparable to the behavior calculated by fiber model (see Fig. 4-24). The th eoretical 1 behavior is different than the experimental in that it does not capture the loss in capacity due to cover concrete crushing but this was expected because the pr ogram used only one st ress-strain curve to characterize the propert ies of the concrete section. The non-linear second part of the curve was the behavior of the beam with th e whole section confined with the top cover layer removed. Curve theoretical 1 was a cl ose match with the mid-span experimental curve up to the peak load. Although the capac ity loss was not captured by the theoretical analysis the plateau noted on the experimental curve was also noted on the theoretical 1 curve. Curve theoretical 1 was a lower bound so lution of the tube beam. Curve theoretical 2 had the same shape as curve theoretical 1. Curve theoretical 2 was obtained by assuming confined concrete properties for th e whole section and including the top cover layer. Curve theoretical 2 was an upper bound solution of the tube beam. The improvement in the ductility of the t ube beam compared to the control beam was evident when the experimental Mcurves for both beams were compared (See Fig. 4-25). The area under the load-displacement cu rves represents the amount of energy a

PAGE 86

68 structure can absorb before failure. The am ount of energy is also a good indicator of ductility. Ductile structures usually can abso rb higher amounts of energy compared to non-ductile (brittle) structures. 0 100 200 300 400 500 00.00020.00040.00060.00080.001 Curvature (rads/in)Moment (k-ft) Exp. Mid-Span Theoretica 1 Exp. South Load Fiber Model Theoretical 2 Figure 4-24. Experimental and theoretical Mcurves for tube beam The areas under the experimental moment-c urvature curves, of both beams, were calculated and compared. The area under the load-displacement curve of the tube beam was approximately 37% more than that of the control beam. The energy up to peak load was elastic energy while the energy post peak was inelastic. Therefore, the 37% extra energy was primarily inelastic energy which i ndicated the ability of the tube beam to undergo inelastic deformation contrary to the control beam. Ductility Factors The displacement ductility factor ( ) and the curvature ductility factor ( ) were used to determine the ductility of the grid beams. Details on the definition of the ductility factors (Equations 2-2 and 2-3) as well as definitions for of ultimate and yield displacements or curvatures are found in chapter 2. The ductility factors calcul ated based on the energy and deformability methods, described in detail in chapter 2, can not be directly compared to the ductility factors for

PAGE 87

69 steel reinforced concrete. The reason is b ecause they are based on different approaches. For the case of the CFRP grid reinforced concrete a met hod that can produce ductility factors in the spirit of the ductility factors fo r steel reinforced concrete is needed. Such a method will be a measure of the plastic deforma tions of the FRP reinforced structure that take place due to concrete confinement. 0 100 200 300 400 500 00.00020.00040.00060.00080.001 Curvature (rads/in)Moment (k-ft) Control Tube Figure 4-25. Experimental Mcurves for both beams The following method, to determine ductility factors for CFRP grid reinforced concrete is recommended. Because the mode of failure for the grid reinforced structures is concrete crushing and not yi elding of steel there is a need for a new parameter that will replace yield displacement or curvature in the ductility factors. This need is especially evident in the case of concrete structures with FRP flexural reinforcement. The new parameter to replace yield di splacement or curvature is na med displacement or curvature at crushing (c or c). This follows the same logic as the yield displacement or curvature. For the yield displacement or curvature first yield is used to define the displacement or ductility while for the CFRP grid reinforced structures first crushing is used. First crushing is defined as the point at which the load causes the cover concrete to spall which is assumed to happen at a concrete compre ssive strain equal to 0.003 (ACI Committee

PAGE 88

70 318, 2002). Any further activity beyond the 0.003 strain is considered contribution of the concrete confinement to the ductility of the structure. The capacity of the structure at a compressive concrete strain of 0.003 is the id eal capacity that is used to determine the displacement or curvature at crushing (spa lling) using the same procedure used for determining the yield displacement or curvatur e. The ultimate ductility was determined in the same way as discussed in chapter 2 base d on Park and Pauley (1975(b)) (see Fig. 22). The curvature ductility () was approximately 1.52 and 2.02 for the control and tube beam respectively. The schematic for determining u and c for the control beam is shown in Fig. 4-29. Ideal moment (Mi) is the moment at a concre te compressive strain of 0.003. The same approach was used in determ ining the ductility factor for the tube beam. The curvature ductility of the tube beam was approximately 33% higher than the curvature ductility of the control beam. 0 100 200 300 400 500 00.00020.00040.00060.00080.001 Curvature (rads/in)Moment (k-ft) Figure 4-26. Curvature ductility factor for control beam Using the same approach used to calculate the curvature ductility factor the displacement ductility factors of the tw o beams were calculated. They were approximately 1.33 and 1.55 for the cont rol and tube beam respectively. The M i 0.75 M i 0.8 M u M u c u

PAGE 89

71 displacement ductility of the tube beam was approximately 17% higher than the displacement ductility of the control beam. Both ductility factors identify the ductility improvement that was evident from the load-displacement curves and at the same ti me quantify it as been 17% or 33% depending on the ductility factor used. The curvature ductility factor using the fiber model moment-curvature diagram of the control beam was approximately 1.58 wh ich was approximately 4% higher than the experimental. On the other hand, the curvature ductility factor of the tube beam was approximately 2.56 which was an overestimate of approximately 27%. The fiber model curvature ductility factor for the tube beam was an overestimated compared to experimental curvature ductility factor. Than can be due to failure of the CFRP grid at lower strain than the one assume d in the fiber model that used a stress-stain curve for grid confined concrete based on gr id cylinder tests. However, only one beam was tested and therefore it is unknown whether the fiber mode l consistently overestimates the curvature ductility of CF RP grid confined beams. Conclusions In this chapter the testing of two co mpression controlled concrete beams was described and results from the tests were pr esented. The results from the experimental results were compared to results obtained using two models. Based on the results presented in this chapter the following conclusions can be drawn: The results from the two beams indicate that the CFRP grid provided confinement to the concrete. Confinement was achieved using a series of small diameter CFRP grid tubes rather than wrapping th e entire cross-section.

PAGE 90

72 There was a nominal increase in the peak load of the tube beam of approximately 3% compare to the control beam. The load increase was considered minor. The displacement ductility of the beam utilizing the CFRP grid tubes was improved by 17% compared to the control beam with no grid tubes. This was due to concrete confinement provided by the CFRP grid. The curvature ductility of the beam util izing the CFRP grid tubes was improved by 27% compared to the control beam with no grid tubes. The average improvement in the ductility of the tube beam was significant, approximately 25% increase, considering the small amount of CFRP that was used to confine the compression zone. The energy dissipation of the tube beam wa s 37% higher compared to the controlled beam due to the effect of concrete co nfinement. This increase in the energy dissipation of the element also represents an improvement in the ductility due to concrete confinement from the CFRP grid tubes. The beam model used predicted the cap acity and behavior of the beams. The difference between the experimental and predicted peak loads was 2%. The beam model was also accurate in predicting strain s in both the concrete and the steel. The difference between the experimental and th eoretical strains was less than 20% with the exception of the lower load s (22 and 46 kips) of the tube beam that the difference tended to be approximately 36%. Based on the test observations and data pr esented in this chapter the following recommendations are offered: This technique could potentially be used in cases were dimensional restrictions prevent the design of concrete structural elements according to the relevant codes. The CFRP grid tubes can potentially impr ove the ductility to the extent that the structural element meets the requirements a nd specifications of the relevant structural code. Cover concrete to the CFRP grid tubes s hould be kept to a minimum to minimize the loss of capacity to the beams when the unconfined cover concrete crushes. If the option to assign different concrete prope rties to different sections of a concrete structural element is added to the theoretical Mprogram it could became a very helpful tool in design and prediction of structural be havior of carbon reinforced concrete elements that use CFRP grid confinement.

PAGE 91

73 CHAPTER 5 CAST IN PLACE CONCRETE SECTI ONS WITH FRP BARS AND GRID Introduction To investigate the behavior of concrete piles reinforced with FRP bars and carbon grids four 20-ft pile specimens were constructe d. The piles were constructed and tested in flexure to demonstrate the f easibility of ductility improve ment of a non-ductile pile through concrete confinement using a CFRP grid. The pile specimens were cast in place a nd were produced in two shapes (round and square). The specimens were divided into two groups. Group 1 (specimens 1 and 2) included one square and one round specimen rein forced with GFRP bars and CFRP grid. Group 2 (specimen 3 and 4) included 2 round specimens reinforced with CFRP bars. Only one specimen (specimen 4) was reinforced with the CFRP grid. Group 1 specimens were tested in four poi nt bending configuration. For group 2, specimen 3 was tested in four point bending configuration wh ile specimen 4 was tested in three point bending configuration. The higher ductility factors of specimens 1 and 2 and 4 (grid reinforced) compared to specimen 3 (no grid reinforcement) i ndicated a ductility improvement due to the confining effect of the CFRP grid. The expe rimental displacement ductility factor of specimen 4 was approximately 1.73 times the ductility factor of specimen 3. Approximately the same improvement was obs erved when comparing the experimental curvature ductility factors of specimens 3 and 4. The curvature ductility factor of specimen 4 was 1.67 times the ductility factor of specimen 3.

PAGE 92

74 Experimental Program Pile Specimen Construction Table 5-1 contains details of all four p ile specimens constructed. The specimen variables included shape, type and size of reinforcement and use of CFRP grid. Table 5-1. Specimen details for cast in place pile specimens Specimen Shape/Size Flexural reinforcement FRP bar size (in.) No of CFRP grid layers 1 Square/16 in. 8 GFRP bars 0.75 2 2 Round/16 in. 8 GFRP bars 0.75 2 3 Round/16 in. 12 CFRP bars 0.375 0 4 Round/16 in. 12 CFRP bars 0.375 2 The total length for both specimens 1 and 2 was 20 ft (see Fig. 5-1). Specimen 1 had a square shape but a tubular reinforcem ent arrangement (see Fig. 5-2(a)) because it was easier to form the grid in that shape. Specimen 2 had a tubular shape and a similar reinforcement arrangement as specimen 1 (see Fig. 5-2(b)). The longitudinal reinforcement for both piles was eight 0.75-in. diameter GFRP reinforcing bars. 20' 2 Grid Layers 6' 1 Grid Layer 7' 1 Grid Layer 7' Centerline 16" Figure 5-1. Longitudinal view of specimen 2 Specimens 3 and 4 also had a length of 20 ft. Both specimens had identical reinforcing bar arrangements. Twelve 0.375-in diameter CFRP reinforcing bars were used as longitudinal reinforcement in specime ns 3 and 4 (see Fig 5-3). Most CFRP bars were placed in bundles of two (see Fig. 53) at the bottom of the piles to force a

PAGE 93

75 compression failure. Specimen 3 had no grid in the 6-foot center section of the length (see Fig 5-4) while specimen 4 had identical CFRP grid arrangement as specimen 2 (see Fig. 5-4). 16" 16" Grid 0.5" clear 2" Bending axis 2" 8" 8" 8" 8" CFRP gri d 7-1/8" Bending axis 7.5" 45oTyp. 8"(a) (b) Figure 5-2. Cross-sectional view: (a) specimen 1 and (b) specimen 2 8" 3.5" 12.5" Bending axis 8" 3.5" 12.5" Bending axis 7.5" CFRP grid (a) (b) Figure 5-3. Cross-sectional view at mid-span: (a) specimens 3 and (b) specimen 4 Specimens 3 and 4 also had a length of 20 ft. Both specimens had identical reinforcing bar arrangements. Twelve 0.375-in diameter CFRP reinforcing bars were used as longitudinal reinforcement in specime ns 3 and 4 (see Fig 5-3). Most CFRP bars were placed in bundles of two (see Fig. 53) at the bottom of the piles to force a

PAGE 94

76 compression failure. Specimen 3 had no grid in the 6-foot center section of the length (see Fig 5-4) while specimen 4 had identical CFRP grid arrangement as specimen 2 (see Fig. 5-3). No Grid 6' 1 Grid Layer 7' 1 Grid Layer 7' Centerline 16" 20' Figure 5-4. Longitudinal view of specimen 3 All specimens were cast using a standard concrete pump mixture with a maximum aggregate size of 0.375 in. The specified 28-da y compressive strength of the mixture was 5000 psi. Round Sonotubes, 16-in. diameter, were used as formwork for specimen 2, 3 and 4 (see Fig. 5-5). Wood formwork was us ed for specimen 1 (see Fig. 5-6). Figure 5-5. Placement of concrete (specimens 2, 3 and 4)

PAGE 95

77 Test Set-Up and Procedure Specimens 1 and 2 were tested in a simply supported four-point bending configuration. The span length was 18 ft and the loads were applied 6 ft from each support (see Fig. 5-7 and 5-8). Specimen 3 was also tested in a simply supported fourpoint bending configuration with loads applied at third poin ts (see Fig. 5-9). However, the instrumentation for specimen 3 was different than the instrumentation of specimens 1 and 2 (see Fig. 5-9). Figure 5-6. Placement of concrete (specimen 1) Actuator 1 Actuator 2 LVDT 6' 6'6' 3 @ 2' 3 @ 2' North Support South Support 4 @ 18"D1 D2 D3 D4 D5 D6 D7 D8 D9 D10 D11 Figure 5-7. Schematic of test set up for specimen 1

PAGE 96

78 Compression failure was the target failure mode for all specimens. Specimen 3, however, failed in flexure-shear. Conseque ntly, a simply supporte d three-point bending configuration was adopted for specimen 4 to fo rce a flexure failure mode (see Fig 5-10). Actuator 1 Actuator 2 LVDT 6'6'6' North Support South Support 3 @ 2' 3 @ 2' 4 @ 18"D1 D2 D3 D4 D5 D6 D7 D8 D9 D10 D11 Figure 5-8. Schematic of test set up for specimen 2 Actuator 1 Actuator 2 LVDT 6'6'6'D1 D2 D3 D4 D5 D6 6 @ 12"D16 D17 D18 D19 D20 D21 D7 D8 D9 D10 D11 D12 D13 D14 D156 @ 12" 8 @ 9" North Support South Support Figure 5-9. Schematic of test set up for specimen 3 For the four-point bending configuration two hydraulic actuators were used to apply the displacements to the piles at approxi mately the same rate. Load cells were used to measure the applied force. The loading c onfiguration created a 6-ft constant moment

PAGE 97

79 region in the center of the span, which allowe d evaluation of the pile behavior in pure flexure. Displacement for the three-point bendin g configuration was applied to the pile in a similar manner as for the four-point bendi ng case using a single hydraulic actuator. The displacement rate was approximately 0.034 in /sec for specimen 1 and 0.0154 in/sec for specimen 2. For specimens 3 and 4 the displacement rate was 0.008 in/sec. D16 D17 D18 D19 D20 D21 D1 D2 D3 D4 D5 D6 D7 D8 D9 D10 D11 D12 D13 D14 D15 9' 9' 6 @ 12" 6 @ 12" 8 @ 9" LVDT North Support South Support Figure 5-10. Schematic of test set up for specimen 4 Steel saddles were used for all round sh aped piles at both the support and load locations. The saddles followed the shape of the pile and evenly distributed the load while at the same time providing stability for the specimens. Instrumentation Eleven displacement transducers (LVDTs) were used to measure the displacement of the piles at different locations for specime ns 1 and 2. The LVDTs were spaced at 2 ft intervals outside the constant moment region and 1.5 ft intervals inside the constant moment region. The LVDTs were labeled from north to south as D1 through D11 (see Fig. 5-7 and 5-8).

PAGE 98

80 For specimens 3 and 4, a total of 21 LVDTs were used to measure the displacements. The LVDTs were spaced at 1 ft intervals outside the constant moment region and 9 in. intervals inside the consta nt moment region. The LVDTs were labeled from north to south as D1 through D21 (see Fig. 5-9 and 5-10). Data from all instrumentation devices were recorded using a data acquisition system at a rate of 1 Hz. Material Properties To obtain the strength of th e concrete used in piles tested, 6 x 12 in. concrete cylinders were cast and tested in compression. The cylinders were tested on the same day that the respective piles were tested. A total of 8 cylinders were te sted using a cylinder test machine. All cylinders were capped us ing sulfur as capping material. Table 5-2 contains the results from the cylinder tests. Table 5-2. Results from cylinders tests Pile Specimen Cylinder Peak stress (ksi) Aver. stress (ksi) 1 6.78 1 & 2 2 6.46 6.62 1 5.54 2 5.63 3 3 5.64 5.60 1 6.08 2 6.10 4 3 6.28 6.15 The physical and mechanical material prope rties for the flexural FRP reinforcement were obtained from the manufacturer (Hughe s 2002(a); Sika 2003) while the properties for the CFRP grid were obtained through te sting as described in Chapter 3. The properties (diameter, cross-se ctional area, tensile streng th and modulus) of the FRP materials are presented in Table 5-3.

PAGE 99

81 Table 5-3. FRP reinforcement material properties Type Dia. (in.) Area (in2) Tensile Strength (ksi) Modulus (ksi) Elongation at rupture (%) Glass Rod 0.750 0.4580 90 5900 2.00 Carbon Rod 0.375 0.1100 405 22500 1.80 Carbon Grid N/A 0.0097 100 9200 1.05 Results, Observations and Discussion The load displacement curves (Fig. 5-11) for specimens 1 and 2 have 3 distinct areas. The initial portion of the curves is line ar up to first cracking, which occurred at approximately 7.5 kips for specimen 1 and 5. 5 kips for specimen 2. After cracking the slopes are reduced due the reduction in cross-s ection stiffness from flexural cracking yet remain linear up to the plateau. The plateau seen in the load-displacement curves (see Fig. 5-11), was attributed to a combination of the following three factors: (1) concrete confinement, (2) the post peak curve that GF RP bars exhibit prior to rupture and (3) the shape of the cross-sect ion of the piles. The shape of th e cross sections was tubular for both cases once concrete spalling took place. Th e square pile had a tubular reinforcement arrangement and therefore once the cover conc rete spalled it had the same compression zone shape as the round pile. That was the reas on the square pile had a plateau associated with its load-displacement curve. For speci men 1 a noticeable loss in capacity was observed before the plateau which was attribut ed to spalling of th e top cover concrete. The information available by the manuf acturing company of the GFRP bars indicated a post peak curve for the bars (Hughes 2002(a)). Chaallal and Benmokrane (1996) reported that the GFRP bars they used in concrete beams also exhibited some post peak behavior rather than rupturing at peak load.

PAGE 100

82 0 10 20 30 40 50 60 024681012 Displacement (in)Total Load (kips) Specimen 1 Specimen 2 Figure 5-11. Load-displacement curves for specimens 1 and 2 (mid-span) The top cover concrete, outside the grid en casement, crushed (spa lled) (see Figs 512 and 5-13) but the concrete core enclosed by the CFRP grid maintained its shape and did not spalled. This was an indication of some confinement had been provided by the CFRP grid. Figure 5-12. Crushed cover concrete (specimen 2) Figure 5-13. Specimen 2 afte r the end of the test

PAGE 101

83 Both specimens had a significant loss of th eir load bearing capacity due to rupture of the CFRP grid and subsequently loss of confinement and ruptured GFRP reinforcing bars (see Fig. 5-14). It is also important to note that the specimens did not collapse but continued to carry their own we ight plus an additional load of approximately 18.8 kips for specimen 1 and 15.7 kips for specimen 2. Specimen capacity was diminished when more GFRP bars ruptured. Figure 5-14. Ruptured CFRP grid and GFRP reinforcing bar (specimen 2) From the tests results for specimens 1 and 2 it can be concluded that ductile behavior of a pile reinforced with GFRP bars can be achieved by providing confinement to the concrete. The results further support th e conclusion that the CFRP grid can provide confinement to concrete and therefore improve the ductility of the pile. The plateaus in Fig. 5-11 were a result of the combine eff ect of concrete confinement provided by the CFRP grid as well as the back curve of the GFRP reinforcing bars. However, without the added concrete ductility due to the CFRP gr id confinement the plateaus would not have been present in the load-displacement cu rves and failure would have taken place by crushing of the compression zone at approximately the location where the plateaus begin.

PAGE 102

84 Specimen 3 failed outside the constant mo ment region and in shear-flexure mode, probably due to the lack of shear reinforcement in the ar ea under the load point. This mode was brittle and resulted in the complete collapse of the specimen (see Figs 5-15). Concrete spalling was not observed prior to the failure of specimen 3 which was sudden and abrupt. Specimen 4 was tested in a three point bending configuration and in that configuration no constant moment region exis ts. The specimen experi enced, in addition to the bending moment, shear forces across its length. Specimen 4 failed close to midspan primarily in flexure. Some minor conc rete spalling of the cover concrete did occur prior to failure which supports the previous statement of a flexure failure. Concrete spalling also indicates concrete confin ement by the CFRP grid. Specimen 4 although severely damaged did not collapse (see Figs 5-16). This was partially due to the confinement provided by the CFRP grid. Figure 5-15. Specimen 3 after testing The behavior of specimens 3 and 4, wh ich had CFRP flexural reinforcement instead of GFRP, had two stages rather than the three stages of the previous specimens.

PAGE 103

85 The first stage was linear up to approximately 18 k-ft moment at which a slight reduction of slope is noted (see Fig. 5-17) due to cracking. Beyond cracking, both curves were linear up to 117 kip-ft for specimen 3 and 150 kip-ft for specimen 4. Beyond those points, however, the stiffness begins to deteriorate due to further cracking. This small reduction in stiffness was seen in specimen 4 but not in specimen 3 due to specimen failure. It should be noted that another reduction in the slope of the curve for specimen 4 was observed at approximate ly 190 k-ft moment. Figure 5-16. Specimen 4 after testing The moment capacity of specimen 4 compared to specimen 3 was improved by 58% and the improvement was attributed to the effect of the CFRP grid in both strengthening the section with its longitudinal strands but more significantly by providing confinement to concrete. It can be argued that the ductility of the section has been improved due to the fact that the area under the curv e for the grid reinforced specimen (specimen 4) is approximately 2.9 times larger than the area of the specimen with no CFRP grid (specimen 3).

PAGE 104

86 0 50 100 150 200 250 0246810 Displacement (in)Moment (k-ft) Specimen 3 Specimen 4 Figure 5-17. Moment-displacement curves for specimens 3 and 4 Experimental and Theoretical Peak Loads The theoretical Mprogram described in chapter 4 was used to calculate theoretical moment capacities fo r the piles. For the piles with CFRP grid the entire crosssection was assumed to be confined by the grid. The moment due to the self weight of the pile was determined by assuming a uniform distribution (see Fig. 5-18) of th e weight of the specimen. The weight of specimen 1 was approximately 4900 lbfs and the weight of specimens 2, 3 and 4 approximately 3900 lbfs. The uniform load (w) due to the weight of the specimen is equal to the weight divided by the length. The mo ment at mid-span due the self weight (Mself) is the moment of a simply supported beam with a uniform load of w: 82L w Mself (5-1) The experimental and theoretical moment capacities are presented in Tables 5-4. For specimens 1, 2 and 3 the theoretical moment capacities are higher than the experimental capacities. That is an overestimate by the Mprogram. However, it should be noted that the assumption that the entire cross-section was confined by the CFRP grid,

PAGE 105

87 including the cover concrete, resulted in higher theoretical moment capacities. The moment capacity of specimen 3 was more overe stimated than the capacity of specimen 2. That was due to the fact that specimen 2 failed in shear flexure and the theoretical program calculates the capacity based on a fl exure failure. The capacity of specimens 1 and 4 was slightly underestimated. 18' w Figure 5-18. Self weight dist ribution for cast in place piles Table 5-4. Experimental and theoretical moment capacities Based on the results presented the theoretical Mprogram predicted the capacity of the pile specimens. The differences be tween the experimental and theoretical capacities were small and could be attributed to differences in the material properties and minor dislocations of the reinforcement in the specimens as well as the effect of the longitudinal CFRP grid strands. Specimen Mexp (k-ft) Mtheor (k-ft) Mself (k-ft) Total Mexp (k-ft) Total Mtheor (k-ft) Mexp / Mtheor 1 146.4 157.8 9.9 156.3 167.7 0.93 2 122.9 130.9 7.9 130.8 138.8 0.94 3 128.1 143.1 7.9 136.0 151.0 0.90 4 202.6 199.2 7.9 210.5 207.1 1.02

PAGE 106

88 Moment-Curvature Analysis The experimental curvature for all four specimens was determined using the displacement profile equations. As described in detail in chapter 4, 6th order polynomial line was fitted through the displacement points. The second derivative of the displacement profile equation is the curvatur e equation and was used to calculate the curvature at increasing loads. The curves calculated using this method were called displacement in this chapter. The experimental curvature was also determined based on a numerical differential method. With the numerical differential me thod the curvature is calculated based on displacement values for adjacent points in contrast to the curvature based on the displacement profile which the curvature is calculated based on a fitted line through all displacement points that can neut ralized localized effects. The average rotation between two points is calculated based on the change in displacement (D) between the two points and the lengt h that the change is taking place (Fig. 5-19). For an n number of displacem ent points the average rotations can be calculated as follows: i i i i iX X D D 1 1 (5-2) The average rotation that is calculated is the rotation at the point located half way between the two points used to calculate the rotation. The average curvature is then calculated based on the change in the average rotation between two adjacent rotation points (c alculated in the previous step) and the distance between the two average rotation points:

PAGE 107

89 2 22 1 1 1 i i i i i i iX X X X (5-3) D1 D2 D3 D4 D5 Dn X2 X3 X4 Xn X5 ...... Dn-1 n-1 1 1 n-2 n Figure 5-19. Illustration of th e numerical differential method The average curvature calculated is the curvature of a point located at equal distances from the two rotation points. This is repeated for increasing loads up to failure. The moment-curvature diagram is the curvature values of a point at increasing loads. The curves calculated using this method were called differential. The theoretical moment-curvature curves were calculated by the theoretical Mprogram described in chapter 4. The experimentally calculated Mcurves were compared with the theoretical Mcurves for specimen 1 (Fig. 5-20) and for specimen 2 (Fig. 5-21). The theoretical moment curvature curve of specimen 1 was significantly different than the displacement moment curvature cu rve. The most obvious difference was the slope of the curve. The theoretical curve ha d a slope approximately 32% lower than the displacement moment curvature curve. It is unknown why the theoretical program underestimated the slope of the curve. On the other hand the diffe rential curve was in good agreement with the displacement curve bu t had a higher slope approximately 18%.

PAGE 108

90 0 30 60 90 120 150 180 0.00000.00100.00200.0030Curvature (rads/in)Moment (k-ft) Displacement Differential Theoretical Figure 5-20. Moment-curvature curves for specimen 1 0 30 60 90 120 150 180 0.00000.00200.00400.00600.00800.01000.0120Curvature (rads/in)Moment (k-ft) Displacement Differential Theoretical Figure 5-21. Moment-curvature curves for specimen 2 The theoretical Mcurve for specimen 2 agreed well with the displacement curve. The slope of the theoretical curve was approximately 25% higher compared to the slope of the displacement curve. The differential cu rve did not agree well w ith the displacement curve. The differential curve had a slope appr oximately 68% lower than the slope of the displacement curve. The experimental and theoretical Mcurves of specimens 3 and 4 (see Figs 5-22 and 5-23) were also calculated and plotted in the same manner as for specimens 1 and 2.

PAGE 109

91 The theoretical moment-curvature curves for specimens 3 and 4 had higher slopes than the displacement curves approximately 25% and 8% respectively. The differential curves were irregular and ther efore their slopes could not be determined. It should be noted that the slopes of the displacement curves for both specimens 3 and 4 were changing at a higher rate than the slopes of the theoreti cal curves and therefore the differences increased at loads close to peak. It was also evident that the theoretical curves calculated significant post peak behavior for specimens 3 and 4 which was different than the displacement curves that did not i ndicate any significant po st peak behavior. 0 50 100 150 200 250 0.00000.00050.00100.00150.00200.00250.0030 Curvature (rad/in)Moment (k-ft) Displacement Theoretical Differential Figure 5-22. Moment-curvature curves for specimen 3 0 50 100 150 200 250 0.00000.00050.00100.00150.00200.00250.0030 Curvature (rad/in)Moment (k-ft) Displacement Theoretical Differential Figure 5-23. Moment-curvature curves for specimen 4

PAGE 110

92 From the results presented it can be concluded that the Mprogram can calculate the capacity of the specimens. The differe ntial curves were typically not in good agreement with the displacement curves with the exception of specimen 1. On the other hand the theoretical curves were typically in better agreement with the displacement curves for specimens 2, 3 and 4 than with sp ecimen 1. Because the displacement curves were in better agreement with the theoretica l curves it was assumed that they portray the behavior of the piles better than the differential curves. Ductility Factors The ductility was defined as the ratio between the ultimate displacement or curvature and the displacement or curvature at first concrete crushing (spalling). More details about this definition can be found in chapter 4. The process of calculating the ductility factors for specimen 1 is illustrated in Figs. 5-24 (displacement ductility factor) and 5-25 (curvature ductility factor). Pi is the load at which the concrete strain is equal to 0.003 and Pu is the peak load. The same process wa s followed for specimens 2, 3 and 4. It should be noted that the experimental curvatur e ductility factors were calculated based on the displacement moment-curvature diagrams. The displacement and curvature ductility factors for the four specimens are presen ted in Tables 5-5 and 5-6 respectively. The experimental displacement factors for specimens 1 and 2 were 2.2 and 2.1 respectively. The displacement ductility f actor of specimen 1 was approximately 5% higher than the displacement ductility factor of specimen 2. Based on the small difference it can be stated that both specimens have the same displacement ductility. Specimens 3 and 4 had experimental displacement ductility factors of approximately 1.1 and 1.9 respectively. The displacement ductility f actor of specimen 4 was approximately 82% higher than the ductili ty factor of specimen one. The significant

PAGE 111

93 improvement in the ductility of specimen 4 was attributed primarily to the effect of the CFRP grid and specifically the c onfining effect on the concrete. 0 10 20 30 40 50 60 024681012 Displacement (in)Total Load (kips) Figure 5-24. Calculation of displacement ductility factors for specimens 1 0 20 40 60 80 100 120 140 160 0.00000.00050.00100.00150.0020Curvature (rads/in)Moment (k-ft) Figure 5-25. Calculation of curvatur e ductility factors for specimens 1 Table 5-5. Experimental disp lacement ductility factors Specimen Pi (kips) Pu (kips) c (in.) u (in.) 1 44.0 48.6 4.2 9.2 2.2 2 34.7 40.8 4.6 9.5 2.1 3 43.1 42.7 4.2 4.7 1.1 4 32.2 45.0 4.1 7.7 1.9 Typically, the curvature ductility factors were close to the displacement ductility factors. The curvature ductility factor of specimen 1 was 2.6. That was significantly 4.2 9.2 Pu 0.8Pu 0.75Pi Pi Mu 0.8Mu 0.75Mi Mi 0.00053 0.00138

PAGE 112

94 higher than its displacement ductility f actor by approximately 18%. The curvature ductility factors for specimens 2, 3 and 4 were approximately the same as the displacement ductility factors. The differen ce between the displacement and curvatures ductility factors for specimens 2 and 4 was approximately 5% and the difference for specimen 3 was approximately 9%. Table 5-6. Experimental curvature ductility factors Specimen Mi (k-ft) Mu (k-ft) c (rad/in.) u (rad/in.) 1 132.0 146.4 0.000530.001382.6 2 104.0 122.4 0.000940.001842.0 3 129.0 128.0 0.000830.000971.2 4 145.0 202.4 0.000990.002002.0 The theoretical curvature ducti lity factors were calculat ed based on the theoretical moment-curvature diagrams using the same procedure used for the experimental curvature ductility factors. The experimental curvature ductility factors are presented in Table 5-7. Table 5-7. Theoretical curv ature ductility factors Specimen Mi (k-ft) Mu (k-ft) c (rad/in.) u (rad/in.) 1 132.0 134.4 0.001330.001761.5 2 104.0 130.9 0.000990.001681.7 3 129.0 143.1 0.000680.001121.6 4 145.0 199.2 0.000720.001762.4 The experimental curvature ductility fact or for specimen 1 was approximately 1.7 times higher than the theoretical ductility factor. That was attributed to the large difference between the theoretical and expe rimental slope of the moment curvature diagrams. The difference between the theoretical and experimental ductility factors for specimens 2, 3 and 4 were smaller than the difference for specimen 1. The theoretical ductility factor of specimen 2 was approximately 15% lower than the experimental

PAGE 113

95 ductility factor. The theoretical ductility fact ors for specimens 3 and 4 were higher that the experimental ductility factors by approximately 33% and 20% respectively. The theoretical curvature ductility factor for sp ecimen 3 was higher than the experimental ductility factor because the theoretical curv ature ductility factor was based on a flexure failure while the experimental factor was based on a shear fl exure failure that was less ductile than the a flexure failure. The theoretic al curvature ductility factor of specimen 4 was higher due to the post peak behavior associated with the theoretical curve while no such behavior was recorded by the experimental results. Conclusions The construction and testing details of four pile sect ions reinforced with FRP materials were presented in this chapter. The experimental data obtained from the tests as well as some theoretical predictions were also presented. Based on the results presented in this chapter the following conclusions can be drawn: The results from the CFRP grid piles indicate that the CFRP grid provided confinement to the concrete. Specimens 1 and 2 and 4 had a flexure failu re. Specimen 3 failed in shear flexure and had lower ductility factors than specimens 1, 2 and 4. Therefore specimens 1, 2 and 4 that were reinforced with the CFRP gr id had improved ductility compared to specimen 3 that was not reinforced with the grid. The presence of CFRP grid and its confini ng effect resulted in a 58% increase in the capacity of specimen 4 compared to specimen 3. For specimens 1 and 2 the effect of confinement on the capacity can not be determined because no control specimens exist for comparison. The theoretical Mprogram predicted the capacity of the piles. The difference between the experimental and predicted p eak loads was less than 11%. The difference for piles with a flexure failure mode was smaller, less than 8%.

PAGE 114

96 Based on the test observations and data pres ented in this chapter the addition of the option to assign different concrete properties to different sections of a concrete structural element to the theoretical Mprogram is recommended. This will make the program an even better tool in design and determinati on of structural behavi or of FRP reinforced concrete elements that use CFRP grid confinement.

PAGE 115

97 CHAPTER 6 SPUN CAST CONCRETE PILES WITH CFRP GRID AND BARS Introduction The spun cast method is commonly used to produce prestressed concrete poles for power lines or stadium lighting. They are produced by placing the concrete in a mold, sealing the mold and then spinning it at hi gh speed for a specific amount of time. The centrifugal force evenly distribut es the concrete across the lengt h of the pole while at the same time the concrete is well compacted. The spinning process also forces some of the water out of the concrete and as a result the poles produced have a higher concrete strength and less permeability than regular cast co ncrete poles. Spun casting is a technology th at is readily available a nd could potentially provide a viable manufacturing option for construc ting round piles for use in highway bridge construction. CFRP reinforcement could be used in place of the usual prestressing steel in piles that are destined for hi ghly corrosive environments such as coastal bridges. Spun cast piles are usually produced in a tapered and hollow configur ation, but if the method is proven then prismatic shapes can be produced as well. In this chapter the manufacturing details of the CFRP reinforced spun-cast piles are presented as well as testing details for the fou r-point flexural tests. The results from the flexural tests are presented and discussed. The availabl e data indicate no significant improvement in the ductility of the sections and an improvement in the capacity of approximately 8%.

PAGE 116

98 Specimen Design and Construction Design The manufacturing of circular shape p iles using traditional precast methods is difficult. In order to produce a circular shap e a closed form mold is necessary. Casting concrete inside a circular cl osed form mold presents a significant challenge since it is necessary to pump the concrete though openi ngs and then compact it though vibration or other means. These challenges make manuf acturing difficult and time consuming which results in higher costs that make these pol es/piles economically unfeasible. That is probably why such a method to produced ci rcular shape poles/piles has not been employed by the concrete pole/pile industry. On the other hand, the spun-cast method used to produce prestressed concrete poles/piles provides a viable option to produce a circular cross-section. This method has been used successfully for more than two decades. Some of the advantages associated with the spun-cast method are: Spun-cast piles can be produced in a number of sizes and lengths. The piles are produced in a circular shap e which is the most effective shape for confinement. Vibration of the concre te is not necessary. The concrete is highly compacted due to the spinning process. That produces high density concrete piles with low permeab ility which for the same cover provides improved environmental protection. The equipment and expertise are already av ailable and can be used to produce FRP reinforced spun-cast piles. The drawbacks of the spun cas t method are the following: The circular shapes produced by the spuncast method are tapered which results in piles with different sectional properties along their length.

PAGE 117

99 The produced sections are hollow which redu ces the overall stiffness of the pole/pile compared to a solid pole/pile. This al so produces problems with shear resistance when the sections are used in a pile configuration. The thickness of the pole/pile walls are not easily contro lled and can vary across the length of the pole/pile. The manufacturing of circular piles in the laboratory was very difficult and the techniques used could not be used effici ently in mass production. Therefore, it was decided to investigate available manufactur ing methods to manuf acture additional FRP reinforced specimens and also to determine if they can be used to mass produce them. The spun cast piles were designed to behave as compression controlled piles, that is, they failed by crushing concrete. This m ode of failure was necessary to evaluate the confining effect of CFRP grid reinforcement on the concrete and subsequently the effect in the overall behavior of the pile. Piles with out the CFRP grid reinforcement were manufactured and served as the reference poi nt for determining the effect of the CFRP grid on the pile behavior. The design was limited by the availabl e mold sizes and reinforcement arrangements. More details on the designed spun cast p iles can be found in the construction drawings provi ded in the next section Manufacturing Six 38-foot long piles were built. The six piles included three w ith no grid in the center portion of the pile (spun cast control (SCC) piles) and three with carbon grid over their entire length (spun cast grid (SCG) pile s). Table 6-1 contains details for the six specimens. The reinforcement for specimens SCC3 and SCG3 was primarily #2 carbon reinforcing bars because the 40 ft long #3 re inforcing bars used in the other specimens were not available at the time specimens SCC3 and SCG3 were constructed.

PAGE 118

100 Table 6-1. Spun cast specimen details Specimen Grid in center section Pile length (ft) Tip dia. (in) Tip wall thick. (in) Butt dia. (in) Butt wall thick. (in) No. of carbon rebars SCC1 No 38 11 1.81 19.2 3.38 12 #3 SCG1 Yes 38 11 2.42 19.2 3.13 12 #3 SCC2 No 38 11 1.25 19.2 3.50 12 #3 SCG2 Yes 38 11 1.78 19.2 3.19 12 #3 SCC3 No 38 11 2.31 19.2 3.88 12 #2 4 #3 SCG3 Yes 38 11 1.81 19.2 3.25 12 #2 4 #3 The tip diameter of the piles was 11 in. a nd they were tapered at 0.215 in. per foot of length. The three piles with grid over the entire length had two layers of the grid in the 6-ft center section of the pile (see Fig. 6-1) and one layer over the rest their length. The rest of the piles did not have any grid in the 3-ft center s ection (see Fig. 6-2) but had one grid layer throughout the rest of their length. Twelve car bon reinforcing bars with a diameter of 0.375 in. were used as flexural reinforcement for pile specimens SCC1 and SCC2 (see Fig. 6-3(a)) and SCG1 and SCG2 (see Fig. 6-3(b)). Piles SCC3 and SCG3 used twelve reinforcing bars w ith a diameter of 0.25 in. and four reinforcing bars with a diameter of 0.375 in. as fl exural reinforcement (see Fi gs 6-4(c) and (d)). 2 Grid Layers 6' Centerline A A Figure 6-1. Elevation of mi dspan section of SCG piles

PAGE 119

101 3' Centerline A A Figure 6-2. Elevation of mi dspan section of SCC piles Bending axis 4.45" to 5.65" 7.45" #3 CFRP bar Typical 22.5oTypical 6.32" Bending axis 4.45" to 5.65" 7.45" 6.7" #3 CFRP bar Typical 6.32" CFRP grid 22.5oTypical (a) (b) Bending axis 22.5oTypical 4.45" to 5.65" 7.45" #3 CFRP bar Typical #2 CFRP bar Typical 6.32" Bending axis 22.5oTypical 4.45" to 5.65" 7.45" 6.7" CFRP grid #3 CFRP bar Typical #2 CFRP bar Typical 6.32" (c) (d) Figure 6-3. Cross sectional view A-A: (a ) SCC1 and SCC2, (b) SCG1 and SCG2, (c) SCC3 and (d) SCG3

PAGE 120

102 Two methods were used to construct the reinforcement cage for the first two piles to simplify contraction and minimize time. Th e more practical of the two was used to manufacture the remaining pile specimens. For the first method the CFRP grid was placed in the mold first and then the carbon reinforcing bars were tied into the required arrangement. The prestress force applied to steel strands in spun cast poles keeps the rein forcement at the right position, however, the carbon reinforcing bars were not prestressed which required the use of steel rings to attached to the reinforcing bars to hold them in place (see Fig. 6-4). The steel rings were spaced at approximately 3 ft intervals. When all steel rings were in place the CFRP grid was attached to the rebar cage and the mo ld was moved and prepared for concrete casting. Figure 6-4. Attachment of carbon re inforcing bars to steel rings For the second method the carbon reinforci ng bar cage was build first using the steel rings and the CFRP grid was placed ar ound the reinforcing bar cage (see Fig. 6-5). The second approach was found to be easier and more efficient than the first. Therefore, the second approach was used to manufactur e the rest of the pile specimens.

PAGE 121

103 Figure 6-5. Placement of CFRP grid Once the reinforcement cage was ready the mold was prepared for concrete casting (see Fig. 6-6). Concrete was slowly placed in the mold and was vibrated (see Fig. 6-7). Figure 6-6. Reinforcement cage inside the mold

PAGE 122

104 Because the concrete had the tendency to move towards the larger end of the mold when spanned, more concrete was placed from the center to the tip of the mold to counteract that tendency. The section of the mold from the center to the tip was filled with concrete whereas the rest of the mold wa s approximately half full (see Fig. 6-8). Figure 6-7. Concrete casting Figure 6-8. Concrete at the tip of the pile

PAGE 123

105 Once enough concrete for the desired wall thic kness was placed in the mold the top half of the mold was put in place and sealed using steel bolts (see Fig. 6-9). When all the bolts were secured in place the mold was m oved to the spinning platform. The mold was then lifted and placed onto the platform (see Fig. 6-10) and was spun (see Fig. 6-11) for approximately 15 minutes. After spinning was complete the mold was removed from the spinning platform and was left undisturbed until the next morning when the pile was removed from the mold. The pile was removed from the mold by firs t removing the top half of the mold and then slowly rotating the bo ttom half of the mold 180o using a crane (see Fig. 6-12(a)). Once the rotation was complete the pile was usually free due to the action of its weight (see Fig. 6-12(b)). Figure 6-9. Sealing the mold The newly removed pile was supported on se veral points along its length (see Fig. 6-12) to avoid over stressing the freshly cast pile. The pile was left in that position for

PAGE 124

106 another 1 or 2 days and was then moved and st ored until it was delivered for testing. The same procedure was followed for all pile specimens. Figure 6-10. Placement of mold onto the spinning platform Figure 6-11. Mold spinning on the spinning platform (a) (b) Figure 6-12. Pile release (a) mold rotation and (b) released pile

PAGE 125

107 Shear Reinforcement The spun cast pile specimens were tapered wh ich meant that the tip side of the piles had a significantly lower cross-sectional area and thinner walls. Due to concerns regarding shear capacity of the smaller diameter sections of the spun cast piles a length of approximately 11 ft from the tip towards the centerline of the pile was reinforced in shear using carbon fabric wraps (stirrups). The carbon stirrups had an average width of 5.5 in. and were spaced approximately 8.5 in. on center (see Fig 6-13). This reinforcement scheme was applied to specimens SCC1 and SCG1. When the tests of the first two specimens (SCC1 and SCG1) were completed it was evident that specimen SCG1 failed in shear flexur e at the south load point (tip side of the pile) just outside the constant moment region. This type of failure was caused because concrete crushing caused a reduction in the area of the pile cross-section. The reduction in the concrete area due to crushing reduced the shear capacity of the section and caused the failure of specimen SCG1. Therefore, to prevent the shear flexure failure mode it was necessary to provide shear reinforcement to en sure a flexure failure mode. In addition to the shear reinforcement scheme applied to specimens SCC1 and SCG1the shear reinforcement (carbon wrap) was extended to co ver the pile length from the tip to the south load. Due to concerns that the shear fl exure failure could migrate to the north load side just outside the constant moment region an 8 ft length section of the pile from the north load towards the butt was wrapped (see Fig. 6-14). The new shear reinforcement scheme was applied to specimens SCC2 and SCG2. Specimens SCC3 and SCG3 had the same shear reinforcement scheme as the specimens SCC2 and SCG2 with the difference that the tip side from the support to the load point was wrapped c ontinuously (see Fig. 6-15).

PAGE 126

108 CFRP Wrap Centerline 1' 2' 7" 4" 3" 10' 8" Figure 6-13. Shear reinforcement for specimens SCC1 and SCG1 CFRP Wrap 7' 9" 2' 6" 7' 1" 1' 10' Centerline 10' 8" Figure 6-14. Shear reinforcement for specimens SCC2 and SCG2 CFRP Wrap 8' 2' 17' 1' 10' Centerline Figure 6-15. Shear reinforcement for specimens SCC3 and SCG3 Test Set-Up All piles were tested in a simply suppor ted four-point bending configuration in displacement control mode, that is, a c onstant displacement rate was applied independently of the amount of load. The sp an length between the two supports was 35 ft, whereas the total length of the piles was 38 ft. The constant moment region for specimens SCC1, SCG1, SCC2 and SCG2 was 3ft long (see Fig. 6-16). Specimens SCC3

PAGE 127

109 and SCG3 had a similar test set-up (see Fig. 6-17), but a shorter c onstant moment region (2.5 ft). LVDT 1' 3' 3' 4' 5' 1.5' 16' 16' 3' Actuator Spreader Beam North Support South SupportD13 D12 D11 D10 D9 D8 D7 D4 D6 D5 D3 D2 D1 Figure 6-16. Test set-up for specime ns SCC1, SCG1, SCC2 and SCG2 Because the spun cast pile specimens were ci rcular in cross-section, steel saddles were placed at the end supports to accommodate the shape of the piles and avoid lateral movements (see Fig. 6-18). Two more steel sadd les were used at the load points for load transfer from the spreader beam to the piles without slippage. 15" 3' 3' 4' 5' 15" 16' 3" 16' 3" Actuator Spreader Beam L1 L2 L3 L4 L5 L6 L7 L10 L8 L11 L12 L13 L92' 6" South Support North Support LVDT 60 mm Gauge Figure 6-17. Test set-up for specimens SCC3 and SCG3.

PAGE 128

110 Figure 6-18. Steel saddle at north support Test Procedure A hydraulic actuator was used to apply the displacement to the piles. The applied displacement was distributed to the two load points using a steel spreader beam. From the spreader beam the displacement was transferre d to the piles using two roller devices. The rollers allowed the loading mechanism to rota te and follow the movement of the pile as the load increased and steel plates distribute d the load across the width of the piles. A load cell was used to measure the applied fo rce. The load points were located 16 ft from each support which created a 3-ft region in the center of the span with pure flexure. The pile specimens were tested in 3 sets. Each set contained one control pile and one grid pile. Set 1 included pile specimens SCC1 and SCG1, set 2 pile specimens SCC2 and SCG2 and set 3 pile specimens SCC3 and SCG3. The piles were loaded at a rate of

PAGE 129

111 0.01-in. per second. The displacement was a pplied monotonically until the pile could no longer sustain any load. Instrumentation For specimens SCC1, SCG1, SCC2 and SCG2, thirteen linear variable differential transducers (LVDT) were placed at varying lo cations of the pile spans to measure the displacement (see Fig. 6-16). The LVDTs were la beled from north to south as D1 through D13. For specimens SCC1 and SCG1 foil strain gages were attached on the sides of the piles at mid-span and on top of the pile. The strain gages at the side of the piles were labeled from the top down as SE2 and SE3 for the east side and SW2 trough SW3 for the west side of the pile. The longitudinal stra in gage on top was labeled as S1. Specimens SCC2 and SCG2 in addition to the longitudi nal strain gages of specimens SCC1 and SCG1 also had two longitudinal strain gages at tached at the south lo ad point (see Figs 619 through 6-21) inside the cont estant moment region. The two strain gages were labeled as SSE1 and SSW1. Beam CenterlineS1 SW2 SW3 SS2 SN1 8" 8" 11" 2" SSW1 0.3" Figure 6-19. Strain gage arrangement for speci mens SCC2 and SCG2 (side view of center portion of the pile)

PAGE 130

112 Beam CenterlineS1 SE2 SW2 SS2 SN1 SSE1 SSW1 8" 8" 5" 5" 11.75" 2" 2" A B A B Figure 6-20. Strain gage arrangement for sp ecimens SCC2 and SCG2 (top view of center portion of the pile) S1 SE2 SE3 SW2 SW3 7.55" 45o Typical SES1 SWS1 7.45" 15.4o Typical (a) (b) Figure 6-21. Strain gage arrangement for specimens SCC2 and SCG2: (a) section A-A and (b) section B-B Transverse strain gages were attached on the top of the specimens. The transverse strain gages were labeled from north to south as SN1 through SS2 (see Figs 6-19 and 620). For specimens SCC3 and SCG3 laser displacement gages were used to record the displacement. Thirteen laser displacement gage s were placed at varying locations of the pile span to measure the displacements (see Fig. 6-17). The laser gages were labeled from north to south as L1 through L13.

PAGE 131

113 For specimens SCC3 and SCG3 foil strain gages were attached on the sides of the piles adjacent to the south load point and on t op of the pile (see Figs 6-22 through 6-24). The strain gages at the side of the piles were labeled from the top down as SSE2 and SSE3 for the east side and SSW2 trough SSW3 for the west side of the pile. The longitudinal strain gage on top adjacent to the south load was labeled as S1. Specimens SCC3 and SCG3 also had two strain gages at tached at the mid-span location (see Figs 622 through 6-24) and they were labeled as SE 2 and SW2. The transverse strain gages were labeled from north to south as SN1 through SS2. Beam CenterlineS1 SW2 SS2 SN1 9.25" 0.25" 7"SSW2 SSW3 1" 2.73" Figure 6-22. Strain gage arrangement for speci mens SCC3 and SCG3 (side view of center portion of the pile) Beam CenterlineS1 NE2 NW2 SN1 SS2 SSE2 SSW2 7" 7" 2" 9.25" 2.73" 3.73" SSW3 SSE3 A B A B Figure 6-23. Strain gage arrangement for sp ecimens SCC3 and SCG3 (top view of center portion of the pile)

PAGE 132

114 15.2o Typical 7.55" NE2 NW2 30o Typical 7.45" SSE3 SSE2 S1 SSW2 SSW3 (a) (b) Figure 6-24. Strain gage arrangement for specimens SCC3 and SCG3: (a) section A-A and (b) section B-B The strain gages on the side of the pile s were used to measure the longitudinal strain distribution across the cr oss-section of the piles wherea s the transverse strain gages on top to measure any transverse expansion of the compression zone due to the Poisson effect. Data from all instrumentation devices were recorded using a data acquisition system at a rate of 4 Hz. Material Properties A concrete mixture with a specified 28day compressive strength of 5000 psi and the maximum aggregate size was 0.375 in. wa s used to manufacture the spun cast piles. To obtain the unconfined concrete st rength for the spun cast piles axial compressive tests were conducted on c oncrete cylinders obtained during the manufacturing process. For each of the pile specimens two sta ndard (6 x 12 in.) cylinders were cast. A total of twelve cylinders were cast for the six specimens constructed. The cylinders were cast at the spun cast casting yard at the same ti me the piles were cast. The cylinders were air cured in the laboratory prior to testing.

PAGE 133

115 The sulfur capped cylinders were tested on the same day as the piles using a cylinder tester. Table 6-2 contains the results from the cylinder tests. Table 6-3 contains the physical and mechanical properties of the CFRP reinforcement of the spun cast piles. The phys ical and mechanical properties of the CFRP flexural reinforcement were obtained fr om the manufacturer (Hughes 2002(b); Hughes 2004; Hughes 2005) while the properties of th e CFRP grid were determined through tensile tests on the grid strands. More detail s on the grid strand tests can be found in chapter 3. Table 6-2. Cylinders test results Specimen Cylinder Peak stress (ksi) Average peak stress (ksi) 1 6.49 SCC1 2 6.50 6.50 1 6.67 SCG1 2 6.47 6.57 1 6.99 SCC2 2 6.91 6.95 1 5.57 SCG2 2 5.56 5.57 1 6.26 SCC3 2 5.94 6.10 1 6.98 SCG3 2 7.03 7.01 Table 6-3. FRP reinforcement material properties Type Dia. (in.) Area (in2) Tensile strength (ksi) Modulus (ksi) Elongation at rupture (%) Carbon Rod 0.254 0.0464 400 22000 1.80 Carbon Rod 0.362 0.1010 300 19700 1.45 Carbon Grid N/A 0.0097 100 9200 1.05 Results and Observations Specimens SCC1, SCC2 and SCC3 were crac ked before testing due to self weight such that they do not show the high linear in itial slope (see Fig 6-25). Their calculated

PAGE 134

116 cracking moment was approxima tely 1.7 k-ft which was much lower than the moment due to their self weight which was appr oximately 15 k-ft. The load-displacement of specimen SCC1 was linear to failure with no signs of an initial higher stiffness because the pile was already cracked. However, the lo ad-displacement curves of specimens SCC2 and SCC3 had two stages. The first stage was between 0 and 1 kip in which the initial stiffness degraded in a nonlinear way (F ig 6-25). The second stage was linear up to failure. The initial non linear portion of the curve was due to the carbon wrap effect that was applied to the specimens. The carbon wrap for specimens SCC2 and SCC3 extended to the load points which was not the case for specimen SCC1. That was the reason the initial nonlinear portion was not observed for specimen SCC1. 0 3 6 9 12 15 0369121518 Displacement (in)Total Load (kips) SCC1 SCC2 SCC3 Figure 6-25. Load-displacement curves for piles SCC1, SCC2 and SCC3 Specimens SCG1 and SCG3 were cracked due their weight. The cracking and self weight moment of specimens SCG1 and SCG2 was approximately the same as for the control specimens (SCC1, SCC2 and SCC3). The load-displacement curve of specimen SCG1 was linear up to peak load. At peak load a small reduction in the capacity was noted. Specimen SCG1 maintained load for a ve ry short period after peak then lost all load carrying capacity (see Fig 6-26). The lo ad-displacement curve of specimens SCG3

PAGE 135

117 had two stages. The first stage was between 0 and 0.9 kips load and the initial stiffness degraded in a nonlinear way (s ee Fig 6-26). The second stage wa s linear up to peak load. The initial non linear portion of the curve wa s due to the carbon wrap effect. The carbon wrap for specimen SCG3 extended to the load points but not for specimen SCG1. That was the reason the initial nonlinear porti on was not observed for specimen SCG1. The carbon wrap also increased the stiffness of specimen SCG3. The data from pile SCG2 were lost due to a problem with the data acquisition system and that is the reason the load-displacement curve for specimen SCG2 is not shown in Fig. 6-26. 0 3 6 9 12 15 0369121518 Displacement (in)Total Load (kips) SCG1 SCG3 Figure 6-26. Load-displacement curves for piles SCG1 and SCG3 Pile SCG1 had higher stiffness and capacity than pile SCC1 (see Fig. 6-27). After examining pile SCC1 it was found that the two bottom carbon reinforcing bars had been displaced during the spinning process, reducing the effective depth by 2 in. This explains the reduction in both stiffne ss and capacity shown by SCC1. Pile SCC1 failed in flexural compression in the constant moment region. When the load reached the flexural capacity of the s ection, the compression zone exploded and the specimen collapsed under its own weight (see Fi g. 6-28(a)). Pile SCG1 also failed rather suddenly in flexural compression, but was not explosive like SCC1 and collapsed under

PAGE 136

118 its own weight (see Fig. 6-28(b)). In additi on, crushing in the compression zone occurred outside the constant moment region where shear stresses were also present. Inspection of the failure mode of SCG1 i ndicates that the failure initiated with crushing in the compression zone followed by diagonal cracking as a result of the loss of cross-section due to crushing. To ensure that the failure mode was purely flexur al compression, shear reinforcement outside the constant moment re gion was added to subsequent specimens. 0 3 6 9 12 15 0369121518 Displacement (in)Total Load (kips) SCC1 SCG1 Figure 6-27. Load-displacement curves for piles SCC1 and SCG1 (a) (b) Figure 6-28. Pile specimens after testing: (a) SCC1 and (b) SCG1 The failure of pile SCC2 took place inside the constant moment region and the pile exploded into pieces (see Fig. 6-29(a)). Ho wever, the pieces for specimen SCC2 were larger than the concrete pieces of specimen SCC1.

PAGE 137

119 Although the data from pile SCG2 were lo st a number of si gnificant observations were made. The pile failed in flexure inside the constant moment region adjacent to the south load point. Failure was not abrupt but gradual. Concrete in the compression zone crushed gradually. Pile SCG2 did not collap se at the end but was capable of supporting its own weight and an additional load of approximately 2 kips (see Fig. 6-29(b)). (a) (b) Figure 6-29. Pile specimens after testing: (a) SCC2 and (b) SCG2 Failure of specimen SCC3 took place insi de the constant moment region and was explosive. The pile crushed to the floor and exploded into pieces (see Fig. 6-30(a)). Failure of pile SCG3 occurred inside the c onstant moment region at the south load. The pile crushed to the floor but it did not expl oded in the manner that specimen SCC3 did (see Fig. 6-30(b)). That was attributed to CFRP grid. After the completion of the test of specimen SCG3 it was observed that the cover concrete had split at the location of the ruptur ed CFRP grid strands (see Fig. 6-31). This occurred because the hoop CFRP strands ha d been ruptured during the manufacturing process. Some of the longitudinal strands rotated and created a plane of weakness perpendicular to the face of th e pile that caused the split.

PAGE 138

120 In general all control specimen (SCC1, SCC2 and SCC3) failures were explosive. The failures of the grid specimens (SCG 1, SCG2 and SCG3) were less explosive probably due to the presen ce of the CFRP grid. (a) (b) Figure 6-30. Pile specimens after testing: (a) SCC3 and (b) SCG3 Figure 6-31. Top cover concrete (pile SCG3) Based on the observations from specime n SCG2 it was concluded that the extension of the shear reinfor cement from the support location to the load point resulted in a flexure failure inside the constant mome nt region of the grid reinforced pile. The visual observations indicated concrete conf inement provided by the CFRP grid and an

PAGE 139

121 improvement in the behavior for pile SCG2 regarding ductility. However, no data were available to quantify and support the visual observations. The results available for the grid reinforced specimens (SCG1 and SCG3) represent a lower bound of the problem since no confin ement to the concrete was provided and therefore no ductility improvement was observed. Strain Data Analysis Compressive and tensile strain data were collected in the constant moment region during testing. Typical load-s train relationships at the t op of the piles for specimens SCC1, SCC2 and SCC3 are presented in Fig. 632. Typical load-strain relationships at the top of the piles for specimens SCG1 and SCG3 are presented in Fig. 6-33. The strains for specimens SCC1, SCC2 and SCG1 were linear up to peak load. Some nonlinearity of the strain was observed for specimens SCC3 and SCG3 at loads higher th an 8 kips. It should be noted that the strain gages for specimen s SCC1, SCC2 and SCG1were located at midspan while the strain gages for specimens S CC3 and SCG3 at the south load inside the constant moment region. 0 3 6 9 12 15 0500100015002000250030003500 Strain (microstrains)Load (kips) S1 (SCC1) S1 (SCC2) S1 (SCC3) Figure 6-32. Load-strain relationship for specimens SCC1, SCC2 and SCC3 S1 SE2 SE3 SW2 SW3

PAGE 140

122 Where data from stain gages on opposing sides of the specimen was available the strain was taken as the aver age of the two recorded valu es. Typically the strains at opposing sides were consistent (see Fig. 6-34) This was typical for all locations were gages on opposing sides of the piles were used. 0 3 6 9 12 15 0500100015002000250030003500 Strain (microstrains)Load (kips) S1(SCG1) S1 (SCG3) Figure 6-33. Load-strain relationshi p for specimens SCG1 and SCG3 0 3 6 9 12 150500100015002000250030003500Strain (microstrains)Load (kips) NE2 (SCC3) NW2 (SCC3) Figure 6-34. Strains at oppos ing sides for specimen SCC3 The compressive strain recorded at peak load for specimen SCC1 was 2470 (see Fig. 6-35). This was lower than the 3000 to 4000 crushing strains reported in the literature (Nawy 2005; Hasoun and Al-M anaseer 2005; Hassoun 2002; MacGregor S1 SE2 SE3 SW2 SW3 SSE3 SSE2 S1 SSW2 SSW3 NE2 NW2

PAGE 141

123 1997). The lower value of the strain was due to the fact that the gages were located at mid-span and concrete crushing took place at the south load location. For pile SCC2 the top compressive strain at peak load at mid span was approximately 2360 (see Fig. 6-36). However the strain recorded at the south load location was higher, approximately 2665 The strain gages at the south load were not located on the top of the specimen. Therefore it was logical to assume that the strain on the top of the specimen at the south load location was higher and probably close to 3000 The higher strain at the south load locat ion indicated that concrete crushing was taking place there which verified the observations made during testing. 0 3 6 9 12 15 0500100015002000250030003500 Top Concrete Strain (microstrains)Total Load (kips) S1 (SCC1) S2 (SCC1) S1(SCG1) S2 (SCG1) Figure 6-35. Compression zone load-strain curves for specimens SCC1 and SCG1 The maximum compressive strain recorded for specimen SCC3 at peak load was 2810 while for specimen SCG3 was 2600 (see Fig. 6-37). The maximum strain recorded for specimen SCC3 was higher than the maximum strain recorded for specimen SCG3 but that was attributed to the effect of the CFRP grid that restrained concrete movement and to the higher concrete streng th of specimen SCG3 compared to specimen SCC3. Higher strength concrete tends to have lower crushing strains (Nawy 2005; Hasoun and Al-Manaseer 2005; Hassoun 2002; MacGregor 1997). S1 SE2 SE3 SW2 SW3

PAGE 142

124 0 3 6 9 12 15 0500100015002000250030003500 Top Compressive Strain (microstrains)Total Load (kips) S1 (SCC2) S2 (SCC2) SS1(SCC2) Figure 6-36. Compression zone load-s train curves for specimen SCC2 0 3 6 9 12 150500100015002000250030003500Strain (microstrains)Load (kips) S1 (SCC3) S2 (SCC3) S1 (SCG3) S2 (SCG3) Figure 6-37. Compression zone load-strain curves for specimens SCC3 and SCG3 Strain data from three different longit udinal locations (S1, S2 and S3) were recorded for specimens SCC3 and SCG3. The data was used to estimate the compression zone strain profiles for the two specimens. The strain profiles at increasing loads for specimens SCC3 and SCG3 are presented in Figs 6-38 and 6-39 respectively. It was noted that the strain did not va ry linearly through the section. This was typical for both specimens. The nonlinearity of the strains grew as th e load increased for both specimens SCC3 and SCG3. It was noted that the neutral axis for both specimens was located approximately at an equal dist ance from the top of the specimens as the SSE3 SSE2 S1 SSW2 SSW3 S1 SE2 SE3 SW2 SW3 SES1 SWS1

PAGE 143

125 distance of strain gages SSE3 and SSW3. It also noted that for specimen SCC3 at peak load the depth of the neutral axis increased. The strain profile with respect to the cross section of the specimens is depicted in Fi g. 6-40. This profile was typical for both specimens. The results presented indicate that for the round spun cast hollow specimens, plane sections did not remain plane. That was probably due the very large deformations that the specimens had to sustain prior to failure. -4 -3 -2 -1 0050010001500200025003000Strain (microstrains)Location from the Top (in) P = 3 kips P = 6 kips P = 9 kips P = 10.4 kips Figure 6-38. Strain profile of compression zone for pile SCC3 -4 -3 -2 -1 0 050010001500200025003000 Strain (microstrains)Location from Top (in) P = 3 kips P = 6 kips P = 9 kips P = 10.5 kips P = 11.8 kips Figure 6-39. Strain profile of compression zone for pile SCG3 The transverse strain data for pile SC C1 and SCG2 are shown in Fig.6-41. The recorded strains remained below 500 for a load less than 7.5 kips and 12 kips for

PAGE 144

126 specimens SCC1 and SCG2 respectively. For loads higher than the above values up to peak the strain gages recorded large increases in the strain. Typical ly the strain located close to the south load location recorded larger strains than the gage located close to the north load location. The difference in the recorded strains was due to the different sectional properties between the locations wher e the gages were attached. The south side of the specimen had a smaller diameter cros s-section than the north side. Therefore, failure occurred at the south side of the constant moment region which was confirmed by the data. This trend was typical for all ot her specimens even though the strain values recorded were different in each specimen. The peak strain recorded at the south side of the constant moment region for specimen SCC1 was higher than the strain recorded for specimen SCG1. This was also typical for all specimens. The lower strains recorded for the specimens reinforced with the CFRP grid were due to the restrain that the grid provided to the lateral expansion of the concrete. The reduction in the lateral displacement of the grid specimens resulted in lower strains. S1 S2 S3 Figure 6-40. Typical compressi on zone strain profile for specimens SCC3 and SCG3

PAGE 145

127 The data from the other specimens are not presented because the trends were typically the same as for specimens SCC1 and SCG1. The rapid increase in strain recorded at location SS2, indicated that the concrete was rapidly expanding and that concrete in th e south side of the c onstant moment region was about to fail. This confirmed earlier obser vations from the longitudinal strain data that also showed the south side of the c onstant moment region as the location where concrete failure occurred. 0 3 6 9 12 15 0500100015002000250030003500 Top Transverse Strain (microstrains)Total Load (kips) SN1 (SCC1) SS2 (SCC1) SN1 (SCG1) SS2 (SCG1) Figure 6-41. Transverse expansive st rains for specimens SCC1 and SCG1 Experimental and Fiber Model Moment Capacity The peak loads for all the piles were calcu lated using a fiber model analysis of the pile cross-section. For piles with CFRP grid the entire cross-section was assumed to be confined by the grid. The compression zone of the piles (see Fig. 6-42) was divided into eight rectangular fiber layers. Some of the assumptions employed in this fiber model in clude perfect bond between concrete and the reinforcing bars (s train compatibility), plain sections remain plain (linear strain distributi on), the area below the neutral axis was considered cracked

PAGE 146

128 and was ignored in the force and mome nt calculation and monotonic loading and deformation of the section. The compressive force in each fiber layer was calculated as the product of the area of the fiber layer and the average stress. Th e average stress was determined based on the strain in the fiber layer and the stress-strain curves of c oncrete. The Hognestad parabola was used to calculate the stress-strain cu rve of unconfined concrete. The modified Hognestad was used to calcula te the stress-strain curve of confined concrete. The parameters of the modified Hognestad were determined based on the available data from confined concrete cylinder tests. Neutral Axis c Void Figure 6-42. Spun cast cross-sectional fiber model The tensile force was calculated as the product of the area of carbon reinforcement and the stress in the carbon reinforcement wh ich was determined based on the strain. The stress in the carbon reinforcement was calcu lated based on an assumed elastic stressstrain curve for the carbon reinforcem ent as reported by the manufacturer.

PAGE 147

129 The moment in the cross-section for the applied curvature distribution was determined by summing moments about the neutral axis. The moment due to the self weight of the pile was determined by assuming a trapezoidal distribution (see Fig. 6-43) of the weight due to the fact that the pile was tapered and the wall thickness variable through the length. Based on the uniform distribution of weight assumed th e total weight of the pile ( W ) was equal to: 1 2 15 0 w w L w L W (6-1) The magnitude of the uniform weight w2 was related to the magnitude of weight w1 in terms of the cross-sectional areas of the tip and butt sections. The magnitude of w2 was equal to the following: 1 2w A A wt b (6-2) where Ab was the area of the butt and At was the area of the tip of the pile. 35' w2w1L = 38' Figure 6-43. Self weight di stribution of spun cast piles The expression in Eq. 6-2 was substitute d into Eq. 6-1 and the magnitude of w1 was calculated. Then w2 was calculated by substituting the magnitude of w1 into Eq. 6-2. Once both w1 and w2 were known the moment due to self weight at the south load point was calculated using static analysis. The self weight moment was calculated at the south load point because the specimens failed at that point.

PAGE 148

130 The total experimental and fiber model mo ment capacities are presented in Table 64. The fiber model overestimat ed the capacities of specimens SCC1 and SCC2. However, the differences between the experimental a nd fiber model capacities for specimens SCC1 and SCC2 were small (less than 7%). For specimens SCG1, SCC3 and SCG3 the experimental capacity was higher than the fi ber model capacity. The differences were 1% for specimen SCC3 and 8% for specimens SCG1 and SCG3. Table 6-4. Experimental and theoretical moment capacities A comparison between the experimental ca pacities of specimens SCC1 and SCG1 can not be made due to the fact that the diffe rence can be attributed to other factors than just confinement (different location of the bottom two carbon reinforc ing bars). However, a valid comparison was made between piles SCG1 and SCC2 where the difference was primarily due to concrete confinement. The increase in the capacity of specimen SCG1 compared to pile SCC2 was approximately 6%. The increase in the capacity of specimen SCG3 compared to specimen SCC3 was 8%. Moment-Curvature Analysis The experimental curvature for all four specimens was determined using the displacement profile equations. As described in detail in chapter 4, 6th order polynomial line was fitted through the displacement points. The second derivative of the displacement profile equation is the curvatur e equation and was used to calculate the Pile Mexp (k-ft) Mfiber (k-ft) Mself (k-ft) Total Mexp. (k-ft) Total Mfiber (k-ft) Mexp/ Mfiber SCC1 74.4 80.8 15.4 89.8 96.2 0.93 SCG1 105.6 96.8 15.5 121.1 112.3 1.08 SCC2 99.2 101.6 15.3 114.5 116.9 0.98 SCG2 N/A 91.2 15.4 N/A 106.6 N/A SCC3 84.5 83.1 19.8 104.3 102.9 1.01 SCG3 98.3 89.4 17.8 116.1 107.2 1.08

PAGE 149

131 curvature at increasing loads. The curves calculated using this method were called displacement in this chapter. The experimental curvature was also determined based on a numerical differential method. With the numerical differential me thod the curvature is calculated based on displacement values for adjacent points in contrast to the curvature based on the displacement profile which the curvature is calculated based on a fitted line through all displacement points that can neut ralized localized effects. More details on the numerical differential method can be found in chapter 5. The experimentally calculated Mcurves from both methods (displacement profile and numerical differential) for specime n SCC3 and SCG3 are presented in Figs 644 and 6-45. 0 20 40 60 80 100 120 140 00.00050.0010.00150.0020.0025 Curvature (rads/in)Moment (k-ft) Disp. (SCC3) Diff. (SCC3) Figure 6-44. Experimental Mcurves for piles SCC3 Typically the differential moment curvat ure curves were different than the displacement moment curvature curves as is noted from Figs 6-44 and 6-45. The obvious difference was the slope of the curve. The di fferential curves had larger slopes than the displacement curves. For a given load the cu rvature calculated based on the differential

PAGE 150

132 method was always higher than the curv ature based on the displacement profile equations. This was a typical trend that was observed for all specimens. 0 20 40 60 80 100 120 140 00.00050.0010.00150.0020.0025 Curvature (rads/in)Moment (k-ft) Disp. (SCG3) Diff. (SCG3) Figure 6-45. Experimental Mcurves for piles SCG3 Ductility Factors The ductility was defined as the ratio between the ultimate displacement or curvature and the displacement or curvature at first concrete crushing (spalling). More details about this definition can be found in chapter 4. The process of calculating the ductility factors for specimen SCC3 is illustra ted in Figs. 6-46 (displacement ductility factor) and 6-47 (curvature ductility factor). Pi is the load at which the concrete strain is equal to 0.003 (nominal load) and Pu is the peak load. The same process was followed for specimens SCC1, SCG1, SCC2 and SCG3. It should be noted that the experimental curvature ductility factors were calculated based on the displacement moment-curvature diagrams. The displacement and curvature ductility factors for the five specimens are presented in Tables 65 and 6-6 respectively. The displacement ductility factor of specimen SCG1 was 15% higher than the ductility factor of specimen SCC1. The displacement ductility factor of specimen SCG3 was 12% higher than the ductili ty factor of specimen SCC3 Therefore an improvement

PAGE 151

133 in the displacement ductility factor was obser ved for the specimens reinforced with the CFRP grid. 0 3 6 9 12 15 0369121518 Displacement (in)Total Load (kips) Figure 6-46. Calculation of displacement ductility factors for specimen SCC3 0 20 40 60 80 100 120 140 00.00050.0010.00150.0020.0025 Curvature (rads/in)Moment (k-ft) Figure 6-47. Calculation of curvature ductility factors for specimen SCC3 Table 6-5. Experimental disp lacement ductility factors Specimen Pi (kips) Pu (kips) c (in.) u (in.) SCC1 9.3 9.3 11.5 11.9 1.03 SCC2 12.4 12.4 11.4 12.4 1.09 SCC3 10.2 10.4 11.2 11.6 1.04 SCG1 12.1 13.2 12.7 15.0 1.18 SCG3 11.0 12.1 9.9 11.5 1.16 11.2 11.65 Pu 0.8Pu 0.75Pi Pi Mu 0.8Mu 0.75Mi Mi 0.000683 0.00778

PAGE 152

134 The curvature ductility factors were typical ly larger than the displacement ductility factors. The curvature ductility factor of specimen SCG1 was 15% higher than the ductility factor of specimen SCC1. The curvat ure ductility factor of specimen SCG3 was 22% higher than the ductility factor of specimen SCC3. Ther efore an improvement in the curvature ductility factor was observed for the specimens reinforced with the CFRP grid. Table 6-6. Experimental curvature ductility factors Specimen Mi (k-ft) Mu (k-ft) c (rad/in.) u (rad/in.) SCC1 89.8 89.8 0.0007080.0007891.10 SCC2 114.5 114.5 0.0007140.0008101.13 SCC3 102.7 104.3 0.0006830.0007781.10 SCG1 112.3 121.1 0.0007210.0009121.26 SCG3 107.2 116.1 0.0005660.0007591.34 Conclusions Based on the results presented in this chapter the following conclusions can be drawn: The results from the piles indicate that th e ductility of the grid piles was improved by and amount of approximately 12 to 22% de pending on the type of ductility factor used. The visual observations during the te sting of specimen SCG2 point towards an even greater improvement for that specime n. Experimental data to support these visual observations do not exist becaus e they were lost during the test. The fiber model calculated the capacity of the piles. The difference between the experimental and predicted p eak loads was less than 8%. The tests revealed problems with the manuf acturing practice that proved to be very significant in influencing the behavior of the pile specimens. The results presented in this chapter repr esent a lower bound soluti on to the ductility problem of spun-cast manufactured CFRP reinforced piles. Based on the test observations and data pr esented in this chapter the following comments and recommenda tions are offered: Concrete confinement can be further improve d with the use of a heavier grid with more fibers in the hoop direction or more layers of this par ticular grid. It is therefore recommended to use a higher number of grid layers of a heavier grid.

PAGE 153

135 This technique could potentially produce dur able concrete piles for coastal regions that will address the problem of corrosion because carbon unlike steel does not corrode. Cover concrete to the CFRP grid tubes s hould be kept to a minimum to minimize the loss of capacity to the piles when th e unconfined cover concrete crushes. Prestessing of the carbon re inforcing bars is recomme nded. Prestressing can reduce displacements and also help keep the bars at the correct locations during the spinning process. The use of internal carbon stirrups as sh ear reinforcement is recommended. Because the concrete cross-section is reduced due to crushing the carbon shear reinforcement should be designed to resist all of the exp ected shear forces. This is a conservative approach. Alternatively, onl y a portion of the concrete cross-section (for example 50%) can be considered for shear resistance.

PAGE 154

136 CHAPTER 7 SYSTEM BEHAVIOR OF PILES CONSTRUCTED WITH CFRP COMPOSITES Introduction The previous chapters have addressed the use of confinement to improve the ductility of concrete in compression. Concrete cylinders were tested in compression to compare the behavior of unconfined concrete wi th that of concrete confined with CFRP grid. The grid was further used to confin e the compression zone of several flexural members with varying cross-se ctional geometries. Confinement at the member level improves the member ductility either as measured at the section as in curvature ductility or as measured at the load point as in member ductility. The resistance that piles provide to lateral loads such as earthquake or ship impact is characterized on a system level. One typica l system used in bridge substructures is the pile bent (see Fig. 7-1). The pile bent is an economical form of s ubstructure construction in which the piles are used for both the founda tion and the bent colu mns. The piles are driven into the soil and extend up to the cap beam. To determine if the system ductility of piles bents constructed with CFRP reinforcement are comparable to those of p iles constructed using steel reinforcement, static non-linear analyses were conducted. Th e moment curvature data needed to generate hinges in the CFRP models were taken from th e experimental work presented in chapters 5 and 6. Several square prestressed concre te piles were pulled out from the old St. George island causeway in Florida and were te sted in flexure to determine strength and

PAGE 155

137 behavior as part of a separate research program. The data from this project were used to generate the moment curvature data needed for the prestressed piles. Figure 7-1. Typical pile bent system Static Non-Linear (Push Over) Analysis Several bent types were selected for the push-over analysis: (1 ) prestressed piles, (2) corroded prestressed piles, (3) cast-in-pl ace piles with GFRP bars (3) cast in place piles with CFRP bars, and (4) s pun cast piles with CFRP bars. The model pile bent system selected was composed of four piles. The dimensions and type of pile bent were identical in each case with the only difference the piles. Two different load locations were considered. In the first case the load was applied on the pile cap (see Fig. 7-2(a)) while in the second case the load was applied on one of the exterior piles (See Fig. 7-2 (b)). The piles in each pile bent had the same dimensions and properties as the piles te sted in the laboratory. The pile bents using the prestressed conc rete piles were used as the basis for comparison between pile bents. The goal was to determine the ducti lity of each system compared to the ductility of an undamaged prestressed system. Two more pile bent

PAGE 156

138 systems with corrosion damaged prestressed piles were analyzed. The first one had a moderate damage and the second one had severe damage to its prestress steel reinforcement due to corrosion. The data for these piles came from the St. George Island research. The pile bent systems using the damaged prestressed piles were used to demonstrate any changes in the structural prope rties and behavior of the pile bent systems due to corrosion damage and were also comp ared to the pile bent systems using the CFRP reinforced piles. 3 @ 6' Water Ground Load 10' 7' 10' 3.5' 3 @ 6' Water Ground Load 10' 7' 10' 3.5' 4' (a) (b) Figure 7-2. Typical model pi le bent system: (a) load case 1 and (b) load case 2 Pile Bent Model Description The prototype bent was modeled assuming th at the piles are fixed in the cap beam and at ten feet below grade as shown in Fig. 7-2. The fixity depth was assumed to be ten feet below grade based on recommendations in the unified facilities criteria (UFC) of the US military and the geotechnical manual of the Texas Department of Transportation for medium cohesive soils (US Army Corps of Engineers et al. 2001; Texas DOT 2000). The water does not offer any significant resistance to lateral loads and it was ignored. The soil

PAGE 157

139 resists lateral loads applied to the pile bent but in order to model it the soil properties have to be known and several springs need to be used in the analysis. For simplicity the soil effect was ignored. Ignori ng the soil effect is a conservative approach. Load case 1 has a single lateral load at the cap beam le vel, which results in maximum moments in the piles just under the cap beam and at the fixe d base. If the cap beam stiffness is assumed large relative to the piles, then the moments at the ends of the piles are all equal, which results in the simultaneous formation of plastic hinges at each of t hose locations. At each plastic hinge location rotational springs were us ed to control the stiffness of the joints (see Figs 7-3 and 7-4) after moments b ecame sufficiently high to cause nonlinear behavior. Once all plastic hinge rotations reac hed failure rotations the pile bent system formed a collapse mechanism and it was considered to have failed. Determining plastic hinge length is a co mplicated matter and no universal equation exists. Many empirical equations that estimate the plastic hinge length ( lp) have been proposed. For the purpose of this study an empirical equation proposed by Caltrans (2004) was used because it relates to bridge dril led-shaft reinforced concrete piles that are closer to this case compared to equations de rived based on reinforced concrete beam and column tests. The empirical equation used to estimate the plastic hinge length ( lp) was the following: H D lp 08 0 (7-1) where D is pile/column diameter or section depth and H is the distance from the location of maximum moment to the poi nt of contraflexure. The plastic hinge lengths for the various types of piles investigated can be s een in Table 7-1. Table 7-1. Plastic hinge length of various types of piles Pile type Shape D (in) H (ft) ld (in)

PAGE 158

140 Steel prestressed Square 20 17 33 Cast in place GFRP bar / CFRP grid Square 14 17 27 Cast in place GFRP bar / CFRP grid Round 16 17 29 Cast in place CFRP bar and grid Round 16 17 29 Spun cast CFRP bar and grid Round 15 17 28 3 @ 6' 27' 3 @ 6' 27'(a) (b) Figure 7-3. Visual analysis st ructural model: (a) with spri ngs, and (b) without springs The Visual Analysis pile bent model for lo ad case 2 (see Fig. 7-4) was similar to the model as in load case 1 with one differen ce been an extra plastic hinge location at the load point of the external pile. As in load case 1 the rotational stiffness of possible plastic hinge locations was controlled by the stiffness of the rotational springs. The amount of rotation at specific load levels was determined based on the experimental Mcurves. The rotational stiffness of the plastic hinge locations was neither constant nor linear but follo wed the same relationship as the Mcurves. The rotation at each load increment used to dete rmine the load-displacement curve of the pile bent system was determined by multiplying the curvature by the length of the plastic

PAGE 159

141 hinge. The spring stiffness was determined by dividing the section moment by the calculated rotation at each load increment. 3 @ 6' 27' 4' Figure 7-4. Visual analysis model pile bent system (load case 2) Once the rotations at specific loads were determined, a static lateral load was applied to the pile bent system that produ ced the target moment at the plastic hinge locations. The rotational stiffness of the plas tic hinge locations was then modified to much the rotations for the specific load. The required stiffness of the rotational springs was calculated by dividing the moment by the ta rget rotation at each load increment. The lateral displacement for each static load increment was recorded and the loaddisplacement curves of the pile bent sy stem plotted for each type of pile. Results for Load Case 1 Both the cast in place glass square (CPGS) and round (CPGR) piles were used. One pile bent for each of the two shapes was an alyzed as well as three pile bents using prestressed concrete piles. In the first of th e prestressed pile bent s, piles from the St.

PAGE 160

142 George Island causeway with minor corrosion dama ge were used while in the second pile bent piles with moderate corrosion damage a nd in the third piles with severe corrosion damage. Hence forth the prestressed piles from the St. George Island Causeway are referred to as low (minor corrosion damage), medium (moderate corrosion damage) and high (severe corrosion damage). All five curv es were plotted toge ther to distinguish differences in the behavior between them (see Fig. 7-5). Its evident that the pile bents using th e cast in place piles reinforced with GFRP bars and CFRP grid behaved in a ductile manner. The ductility of these pile bents compared well to the ductility of the intact (minor corrosion damage) pile. The moderately corrosion damaged pile bent lost a significant portion of its original strength (32%) and a portion of its ductility. The stre ngth loss for the severely corrosion damaged pile bent was more extreme (59%). However its ductility was higher compared to the intact pile bent. 0 10 20 30 40 50 60 70 80 0510152025 Pile Bent Displacement (in)Load (kips) Low Medium High CPGS CPGR Figure 7-5. Load-displacement curves of pres tressed pile bents and pile bents using cast in place piles reinforced with GFRP bars and CFRP grid Piles bents using both the cast in place carbon control (CPCC) and grid (CPCG) piles were analyzed. The same three prestressed pile bents were plot with the cast in place

PAGE 161

143 piles for comparison purposes (see Fig. 7-6) For the cast in place CFRP bar and grid reinforced piles the Mcurves from the theoretical program were used. The experimental curves were not used because the failure mode was shear-flexure. The Mcurves presented in Chapter 5 were in good agre ement with the experimental curves up to the failure point of the specimens and theref ore it was reasonable to assume that the portion of the theoretical Mcurves after that point were reasonable estimations of the actual curves for a flexure failure. The ductility of the pile bent using the cast in place CFRP bar reinforced piles was lower than the ductility of the pile bent using GFRP bar and CFRP grid reinforced piles. The ductility of the pile bent using GFRP bar and CFRP grid reinforced piles was comparable to the ductility of the moderately corroded prestressed pile bent although lower. 0 10 20 30 40 50 60 70 80 0510152025 Pile Bent Displacement (in)Load (kips) Low Medium Severe CPCC CPCG Figure 7-6. Load-displacement curves of pres tressed pile bents and pile bents using cast in place piles reinforced with CFRP bars and grid Pile bents using both the sp an-cast control piles (SCC) and grid (SCG) piles were analyzed. Again the three prestressed pile be nts were plot together with the span-cast piles bents for comparison purposes (see Fig. 7-7). Although the spun cast piles reinforced with the CFRP grid failed in shear the theoretical Mcurves were similar to

PAGE 162

144 the experimental. The theoretical curves pr edicted rupture of the CFRP longitudinal reinforcement at the peak load. The predic ted peak load was in agreement with the experimental peak load. Since the theoretical curves were similar to the experimental the experimental curves were used in the static nonlinear analysis. Both pile bents using the spun cast piles with and without the CFRP grid showed no significant ductility. Both load-displacement curves were linear except very closed to peak load were a small nonlinearity in the curv es can be observed. 0 10 20 30 40 50 60 70 80 0510152025 Pile Bent Displacement (in)Load (kips) Low Medium High SCG SCC Figure 7-7. Load-displacement curves of pres tressed pile bents and pile bents using spun cast piles reinforced with CFRP bars and grid Figures 7-5 through 7-7 show a comparison of the behavior of corrosion damaged piles from the St. George Island causeway br idge. Piles reinforced or prestressed with steel will eventually deteriorate due to corrosion, which changes their behavior significantly over the life of the structure. This is illustrated in each figure by the curves denoted as low, medium, and high (previously described). The results of the tests on steel reinforced piles indicate that the capacity deteriorates significantly over time. Yet the ductility of highly corroded piles appears to be higher than that of uncorroded piles. Even though highly corroded piles appear to have improved ductility, they also have a

PAGE 163

145 significantly reduced capacity. This loss in capacity can render the pile non-functional. Piles in a state of moderate to severe corro sion require constant m onitoring, maintenance and repair to extend their service life, which is rarely successful. CFRP reinforcement, however, theoretically does not deterior ate over the typical life of the structure in the harsh saltwater envi ronment. Therefore, it is expected that the behavior of FRP reinforced pile s will be the same throughout th e life of the structure. The results from the push over analysis using the piles tested in the laboratory indicate that they lack the capacity of the intact prestr essed piles but in some cases (CPGP) they actually outperform the prestressed piles wi th medium or high corrosion damage. Since corrosion damage accumulates quickly, the FRP reinforced piles will perform better than the prestressed piles when the life cycle is the basis of the comparison. Ductility of Pile Bent Systems The displacement ductility factors for all pile bents were determined using the procedure described in chapter 2 for steel rein forced concrete piles and in chapter 4 for the FRP reinforced piles with CFRP grid conf inement. For more details on the procedures used see chapters 2 and 4. The capacities of the St. George causewa y prestress piles were reduced due to corrosion. The nominal capacity of the piles wa s higher than the experimental peak load and therefore calculating the yield displacem ent for the ductility factors based on the nominal capacity was very conservative. That is why for the prestressed pile bents the experimental peak load was assumed to be the nominal capacity of the pile bent. The same was assumed for the rest of the pile bents to maintain consistency for comparison purposes.

PAGE 164

146 The ductility factors are listed in Table 7-2. The ductility factors for the steel reinforced pile bents were calculated based on the procedure described in chapter 2. The ductility factors for the FRP reinforced p ile bents were calculated using the same procedure and the definition of splalling displacement as defined in chapter 4. The prestressed pile bent with piles with minor corrosion had a ductility factor of three. The prestressed pile bent with the moderately co rroded piles had a ductili ty factor of two and a capacity that was 68% of the capacity of the pile bent with minor corrosion. The last prestressed pile bent with the severely corr oded piles had the highest ductility factor from all pile bents analyzed but its load capacity was also severely reduced to approximately 41% of the capacity of the p ile bent with minor corrosion. Table 7-2. Ductility factors for pile bents (load case 1) Pile type Pideal (kips) y or c (in) u (in) Prestressed concrete (minor corrosion) 76.4 3.3 9.9 3.0 Prestressed concrete (moderate corrosion) 51.9 2.8 5.7 2.0 Prestressed concrete (sever e corrosion) 31.4 2.6 11.7 4.5 Cast in place GFRP bar / CFRP grid (CPGS) 45.7 8.9 15 1.7 Cast in place GFRP bar / CFRP grid (CPGR) 40.3 14.1 19.5 1.4 Cast in place CFRP bar and grid (CPCC) 44.7 10.4 13.6 1.3 Cast in place CFRP bar and grid (CPCG) 61.3 14.6 20.8 1.4 Spun cast CFRP bar and grid (SCC) 30.8 17.7 20.5 1.2 Spun cast CFRP bar and grid (SCG) 34.4 19.5 21.6 1.1 None of the pile bents using the FRP reinforced piles had a comparable ductility factor as the pile bent with minor corrosi on damage. The highest duc tility factor for the pile bents using FRP reinforced piles wa s approximately 1.7 which was 57% of the ductility factor needed to compare favorably to the pile bent with minor corrosion. The ductility factor of the pile bent using the cas t in place square piles reinforced with GFRP bars and CFRP grid was approximately 85% of the ductility factor of the pile bent with the moderately corroded piles. The capacity of the pile bents using the FRP reinforced

PAGE 165

147 piles was lower than the capaci ty of the non corroded pile bent, ranging from 45 to 80%. Further improvement of the ductility and load capacity of the pile bents using the FRP reinforced piles was needed. The ductility of the sections might be fu rther improved by incr easing the amount of confinement reinforcement which could increas e the ductility of th e enclosed concrete. The capacity of the sections could be im proved by providing additional longitudinal reinforcement or by increasing the size of th e section or both. Any pile section design must ensure that the section is heavily reinforced which will result in compression controlled failure which can use concrete c onfinement to improve section ductility prior to rupture of the FRP longitudinal reinforcement. Results for Load Case 2 The static non-linear analysis of the pile bents for load case 2 was very similar for all different pile bends analy zed. It was discovered that failure of the external pile to which the load was applied prevented the fo rmation of plastic hinges on the remaining piles in the pile bent system. The lack of plastic hinge formation on the internal piles resulted in a non-ductile response of the pile bent system. Because th e pile bent system behavior was non-ductile the ductility factors of the systems were not calculated for load case 2. As an example the load-displacement of the prestressed pile bent with minor corrosion was plotted for load case 2 (Fig. 78). The load-displacement of the same pile bent for load case 1 was plotted for compar ison. Similar behavior was exhibited by all pile bents using FRP reinforced piles. The failure load of the pile bent system in load case 2 was lower than the failure load for load case 1. Only a portion of the total load applied to the external pile was

PAGE 166

148 distributed to the remaining piles in the pile be nt. For this particular case 70% of the total load was transferred to the other three piles. This also meant that the top portion (portion above the load) of the external pile had a high shear fo rce (70% of total load) which should be accounted for in design and ade quate shear reinforcement provided if the concrete section does not have the capacity to fully resist such shear force. The bending moments in the internal piles were smaller compared to load case 1 for the same total load which resulted in a stiffer response of th e pile bent system compared to load case 1. This was more evident at the higher loads where the rotational stiffness of the internal piles had a more dominant influence on the system behavior. 0 10 20 30 40 50 60 70 80 0510152025 Bent Displacement (in)Load (kips) Low (Case 1) Low (Case 2) Figure 7-8. Load-displacement curves of the prestressed pile bent with minor corrosion In load location two the load was applied f our feet from the bottom of the pile bent cap. If the load is applied at a lower location the response of the pile bent system will be even less ductile than the respons e of the system at load loca tion two. If the load location moves closer to load location one then the pile bent system behavior will became more ductile and will move closer to the behavior of the pile bent for load location one. The closer the load to load locati on one the more similar the pile bent system response will be to the response of the syst em at load location one.

PAGE 167

149 Static Non Linear Analysis of Prototype Pile Bents To better compare the prestressed pile bents with the FRP reinforced pile bents comparable capacities were required. Using the theoretical Mprogram that has yielded reasonable sectional Mcurves for tested specimens the sectional Mcurves for a number of prototype piles were derived. Thes e curves were used to determine the loaddisplacement curves of pile bent systems us ing these pile sections. The basis for the comparison was the theoretical behavior of a 20 in. square concrete steel prestressed pile (CSPP) with 20 0.5-in. prestressing strands si milar to the St. George Island Causeway bridge. The analysis was perf ormed using Visual Analysis as in the case of the experimental curves and only load case 1 was considered. The section details of the pr ototype pile sections used in the prototyp e pile bents are presented in Table 7-3. All pile sections explored ha d tubular shapes with similar diameter ( D ) and the longitudinal FRP bars were uniformly spaced around a reinforcement diameter Dr (Fig. 7-9). Some of the pile sections were prestressed and some were not prestressed. For the prestressed secti ons a prestressing force of approximately 50% of the FRP bar strength was assumed with 20% prestress losses. Based on these assumptions the effective prestress was approximately 40% of the FRP bar strength (36 ksi for glass bars and 120 ksi for carbon bars). The reinforcement details of the prototype pi le sections used in the prototype pile bents are listed in Table 7-4. Both glass a nd carbon FRP bars were used. The diameter of the glass FRP bars used in the prototype piles was 0.875 in. and the diameter of the carbon FRP bars was 0.5 in. The schematic of the prototype cross-section in Fig. 7-9 applies to both the solid and hollow cross-sectio ns that were investigated in this study.

PAGE 168

150 D Shear ties Dr FRP bar Notes: The type, size and number of FRP bars varies between prototypes. The wall thickness applies only to spun cast prototypes. Wall thickness Figure 7-9. Typical pile secti on schematic for prototype piles Table 7-3. Section details fo r prototype FRP reinforced piles Pile type D (in.) Dr (in.) Wall thick. (in) fc (ksi) Prestress Cast in place CFRP bar and grid (CPCP1) 18 16 N/A 5 No Cast in place GFRP bar / CFRP grid (CPGP1) 19 17 N/A 5 No Spun cast CFRP bar and grid (SCCP1) 18 16 3 5 No Spun cast GFRP bar and grid (SCGP1) 19 17 3.5 5 No Precast prestressed CFRP bar and grid (PCPCP1) 19 17 N/A 5.5 Yes Precast prestressed GFRP bar / CFRP grid (PCPGP1) 19 17 N/A 5 Yes Precast prestressed CFRP bar and grid (PCPCP2) 19 17 N/A 5 Yes Precast prestressed CFRP bar and grid (PCPCP3) 20 18 N/A 4.5 Yes Spun cast prestressed CFRP bar and grid (SCPCP1) 19 18 4 6 Yes Spun cast prestressed GFRP bar and grid (SCPGP1) 19 18 5.5 6 Yes Spun cast prestressed CFRP bar and grid (SCPCP2) 21 19 4.5 5 Yes Spun cast prestressed CFRP bar and grid (SCPCP3) 21 19 4.5 5 Yes

PAGE 169

151 Table 7-4. Reinforcement details fo r prototype FRP reinforced piles Pile type FRP reinf. type FRP reinf. size (in.) No. of FRP bars Prestr. (ksi) grid layers Cast in place CFRP bar and grid (CPCP1) Carbon 0.5 24 N/A 2 Cast in place GFRP bar / CFRP grid (CPGP1) Glass 0.875 18 N/A 2 Spun cast CFRP bar and grid (SCCP1) Carbon 0.5 24 N/A 2 Spun cast GFRP bar and grid (SCGP1) Glass 0.875 18 N/A 2 Precast prestressed CFRP bar and grid (PCPCP1) Carbon 0.5 24 120 2 Precast prestressed GFRP bar / CFRP grid (PCPGP1) Glass 0.875 22 36 2 Precast prestressed CFRP bar and grid (PCPCP2) Carbon 0.5 24 120 2 Precast prestressed CFRP bar and grid (PCPCP3) Carbon 0.5 24 120 2 Spun cast prestressed CFRP bar and grid (SCPCP1) Carbon 0.5 26 120 2 Spun cast prestressed GFRP bar and grid (SCPGP1) Glass 0.875 24 36 2 Spun cast prestressed CFRP bar and grid (SCPCP2) Carbon 0.5 22 120 2 Spun cast prestressed CFRP bar and grid (SCPCP3) Carbon 0.5 20 120 2 All the prototype pile bents analyzed we re plotted with the steel reinforced prestressed pile bent for comparison (Fig s. 7-10 through 7-15). The following notation was used when referred to the prototype pile bents analyzed: Cast in place carbon prototype (CPCP) Cast in place glass prototype (CPGP) Spun cast carbon prototype (SCCP) Spun cast glass prototype (SCGP) Pre-cast prestressed ca rbon prototype (PCPCP) Pre-cast prestressed gl ass prototype (PCPGP)

PAGE 170

152 Spun cast prestressed carbon prototype (SCPCP) Spun cast prestressed gl ass prototype (SCPGP) 0 20 40 60 80 100 120 0510152025 Bent Displacement (in)Load (kips) CSPP CPCP1 CPGP1 Figure 7-10. Pile bent load-displacement curves for CSPP, CPCP1 and CPGP1 piles The combination of FRP reinforcement with two layers of the CFRP grid used as confining reinforcement was not enough to pr oduce ductility factors that compared well to the steel reinforced prestressed piles used on the St. George Causeway bridge. However, some of the prototypes had ductility factors that were higher than the ductility factor of the prestressed pile with me dium corrosion damage and ductility factors comparable to the ductility factor of the pr estressed pile with low corrosion damage. 0 20 40 60 80 100 120 0510152025 Bent Displacement (in)Load (kips) CSPP SCCP1 SCGP1 Figure 7-11. Pile bent load-displacement curves for CSPP, SCCP1 and SCGP1 piles

PAGE 171

153 0 20 40 60 80 100 120 0510152025 Bent Displacement (in)Load (kips) CSPP PCPCP1 PCPGP1 Figure 7-12. Pile bent load-displacement cu rves for CSPP, PCPCP1 and PCPGP1 piles 0 20 40 60 80 100 120 0510152025 Bent Displacement (in)Load (kips) CSPP PCPCP2 PCPCP3 Figure 7-13. Pile bent load-displacement cu rves for CSPP, PCPCP2 and PCPCP3 piles 0 20 40 60 80 100 120 0510152025 Bent Displacement (in)Load (kips) CSPP SCPCP1 SCPGP1 Figure 7-14. Pile bent load-displacement cu rves for CSPP, SCPCP1 and SCPGP1 piles

PAGE 172

154 The non-prestressed prototype pile bent s (CPCP1, CPGP1, SCCP1 and SCGP1) had a much lower stiffness than the steel rein forced prestressed pile which led to a very low ductility factor. In all cases an improve ment in ductility of the pile bents was observed. The pile bents using cast in place so lid prototypes behaved better than the pile bents using spun cast hollow pile prototypes. Confinement, whic h is the source of ductility for FRP reinforced prototypes, is more effective for solid section and less effective for hollow sections and is the reason solid sections outperform hollow sections. The prestressed prototype pile bents (CPPCP, CPPGP, SCPCP and SCPGP) had improved stiffness and ductility compared to the non prestressed FRP reinforced pile bents. 0 20 40 60 80 100 120 0510152025 Bent Displacement (in)Load (kips) CSPP SCPCP2 SCPCP3 Figure 7-15. Pile bent load-displacement cu rves for CSPP, SCPCP2 and SCPGP3 piles The ductility factors for all the prototype pile bents analyzed are listed in Table 7-5. The non-prestressed cast in place prototype FR P reinforced pile bents had a ductility factor that was approximately 49% lower than the ductility factor of the steel prestressed pile bent. The non-prestressed spun cast protot ype pile bents had an even lower ductility factor which was approximately 59% lower.

PAGE 173

155 When prestressing was applied to the prisma tic FRP reinforced pile bent prototypes their ductility factors increased up to approximately 67% of the ductility factor of the steel prestressed pile bent. Prestress also improved the duc tility factor of the spun cast hollow prestressed pile bents but to a lower extent. The ductility factor of the spun cast hollow prestressed pile bents was as high as approximately 62% of ductility factor of the steel prestressed pile bent. Th e best performance for the FRP reinforced pile bents was exhibited by the pre-cast solid CFRP prestr essed pile bents. These pile bents had a ductility factor of approximately 2.6 while the steel prestressed pile bent had a ductility factor of 3.9. The ductility factor of the pr e-cast prestressed CFRP reinforced pile bents was approximately 33% lower than the ductility factor of the steel pr estressed pile bents. None of the FRP reinforced prototype pile bents reached the ductility level of the steel prestressed pile bent. However, these result s should be viewed in conjunction with the data available from the extracted piles of the old St. George Island Causeway bridge. Many of the old St. George piles had a signi ficant reduction in both their strength and ductility. Table 7-5. Ductility factors for prototype pile bents Pile type Pideal (kips) y or c (in) u (in) SCCP1 76 12.9 20.7 1.6 SCGP1 74 11.6 19.1 1.6 SCPCP1 77 6.3 11.1 1.8 SCPGP1 75 6.1 10.9 1.8 CPCP1 72 11.3 22.0 1.9 CPGP1 71 11.6 24.7 2.1 PCPCP1 84 8.0 17.4 2.2 PCPGP1 75 7.2 16.0 2.2 SCPCP2 83 4.8 10.5 2.2 SCPCP3 79 4.7 10.6 2.3 PCPCP2 70 5.3 13.2 2.5 PCPCP3 77 5.9 15.6 2.6 CSPP 80 2.7 10.6 3.9

PAGE 174

156 The pile bents using the prestressed p iles with minor corrosion had a ductility factor of approximately three. That repres ented a reduction of approximately 23% of its original ductility factor. In addition a significant strength re duction of approximately 15% was associated with the same pile bent. Knowing that the process of steel corrosion begins immediately after installation it is l ogical to assume that during the first 10 years of the life of the piles at least minor corrosion damage will take place. With in approximately 20 years moderate corrosion dama ge is also possible. In such a case the steel reinforced prestressed piles will be in service having less ducti lity than the pre-cast prestressed CFRP reinforced piles. The corro sion damage will also reduce the capacity of the steel reinforced piles as the results of the St. George Island Causeway piles suggest. For moderate corrosion damage a strength redu ction of up to 35% is possible which is very significant. The pre-cast prestressed CF RP pile bents initia lly have a ductility disadvantage compared to the steel prestresse d pile bents but with in the first 20 years they actually became more advantageous than the steel prestressed pile bents. In time their advantage becomes greater because further reduction of both the ductility and strength is a strong possibility based on the results availabl e from St. George piles. It is reasonable to assume that for at l east the second half of their lifespan the steel prestressed pile bents are less safe than pr e-cast prestressed CFRP pile bents both in terms of strength and ductility. That is true if the life span of the pile bents is approximately 35 to 40 years. If the expected life is longer then the steel prestressed pile bents will be less safe than the pre-cast pres tressed CFRP pile bents for the larger portion of their lives.

PAGE 175

157 Prestressing of the longitudinal FRP reinfor cement of the prototype piles to be used in pile bents was deemed necessary based on th e results of the static non-linear analysis of the pile bents. Prestressing improved the stiffness of the FRP reinforced pile bents as well as their ductility. Due to the lower modulus of elasticity of the FRP reinforcement compared to prestressing steel the stiffness of the FRP reinforced pile bents did not match the stiffness of the steel reinfo rced prestressed pile bent. However, part of reason for the stiffness mismatch was the larger cross sect ion of the steel prestressed pile bent. Conclusions The static non-linear analysis of pile bent system that us ed pile sections tested in the laboratory was performed to evaluated the ductility at the system level. The experimental results were compared using the ductility factor as the basis of the comparison. In addition to the experimental results analysis was performed on pile bents using the theoretical Mcurves for FRP reinforced pile sections with comparable capacity to the steel rein forced pile sections used in bridges today. Based on the results of the st atic non-linear analysis of the pile bents the following conclusion can be drawn: The results from the experimental and theore tical static non-linear analysis indicate that member ductility did translate to syst em ductility when plastic hinge formation took place in all the system members. When the load was applied to the pile bent head (load case one) the system behavior was ductile while when the load was applied on the one of the external piles (load case two) failure of the external pile took place prior to plastic hinge formation in the other piles. However, the pile itself can provide a ductile response when impacted by a marine vessel. A ductile system behavior was feasible with pile bents using piles reinforced with FRP when using concrete confinement to pr oduce ductility at the member level that eventually translated to system ductility.

PAGE 176

158 Prestressing of the FRP reinforcement was required because the theoretical results indicated that it improved both the stiffn ess and the ductility of the members and therefore the stiffness and ductility of the system. Using piles with two CFRP grid layers provi ded pre-cast prestressed CFRP reinforced pile bents with approximately 67% of the ductility of the new intact steel prestressed pile bent. The pre-cast prestressed CFRP reinforced pile bents had the highest ductility factor of all the FRP reinforced piles bents. Although lower than the ductility factor of a new intact steel prestressed pile bent these pile bents did compare favorably with the steel prestressed pile bents with minor, modera te or severe corrosion damage. Actually they exhibited superior prope rties to the moderately corroded steel prestressed pile bent in both ductility (30% higher) and stre ngth because the moderately corroded pile bent had a strength reduction of approximate ly 35%. The steel prestressed pile bent with minor corrosion damage had higher duc tility but its strength was reduced by approximately 15%. The severely corroded pile bent did have a higher ductility but its strength degradation was severe amounting only to approximately 35% of its theoretical capacity. Because corrosion damage will take place in th e early stages of th e life of the bridge the steel prestressed pile bents will have an advantage over the pre-cast prestressed CFRP reinforced pile bents only during the fi rst years of the life of the bridge. Once corrosion causes damage the advantage of the steel prestressed pile bents will no longer exist. With more corrosion damage accumulating the advantage will be with the pre-cast prestressed CFRP pile bents that are not expe cted to lose strength or ductility during their lifespan. Providing more confinement to the concrete core has the potential to further improve the ductility of the FRP reinforced pile s ections which could translate into further improvement in the ductility of the pile bents. This has the potential to produce ductility similar to the ductility of the new intact steel prestressed pile bents for the pre-cast prestressed CFRP reinforced p ile bents which will make the pre-cast prestressed CFRP reinforced pile bents more advantageous than the steel prestressed pile bents throughout the lifespan of the bridge.

PAGE 177

159 CHAPTER 8 PROPOSED CONCRETE MODEL Introduction A number of available concrete confinemen t models were explored to determine if they could model the stress-strain curve of confined concrete. The models were calculating the peak stress of the confined conc rete but calculated a different stress-strain curve than what was obtained from the experi mental testing. Therefore it was necessary to develop a new model that predicted the be havior of CFRP grid confined concrete. A new theory for explaining concrete behavi or and its failure mechanics is offered. The theory suggests that local buckling of concrete micro columns that form in concrete due to cracking is the failure mechanism and th at for the case of the confined concrete the columns are braced by the confining material A concrete model based on the local buckling of concrete micro columns was deve loped for both the unconfined and confined concrete. The preliminary results indicated th at the theory of concrete micro column buckling has the potential to successfully model the behavior of both unconfined and confined concrete. The proposed model was tune d to a specific set of experimental data (chapter 3) and there was good agreement be tween the experimental and model results. Further investigation, validati on and refinement are needed before the model can be used in analysis or design of CFRP grid conf ined concrete elements or structures. Unconfined Concrete Model Although concrete has been around for a long time its failure mechanisms are still not understood. It is well accepted that comp ression tests failure occurs due to cracking

PAGE 178

160 of the concrete that is caused by tensile stra ins that develop due to the Poisson effect. A new theory that attempts to explain concre te failure based on buckling is offered. The theory is that as the concrete cracks unde r axial compressive load, due to the Poisson effect, micro columns are formed (see Fig. 8-1). These micro columns are not braced (unconfined concrete) and when the cracks reach a critical length local buckling occurs which leads to failure of the concrete. Radial cracks Longitudinal cracks Figure 8-1. Cracked concrete cylinder The cracks are not uniformly distributed but are longer and more severe on the exterior layers than the inte rior layers (Shah et al.1995; Landis and Shah 1993). However, for the purpose of this study it was assumed that on average the cracks were uniformly spaced for each concrete layer considered. To develop the stress-strain relationship of concrete based on the assumption that concrete behavior and failure was due to lo cal buckling of micro columns that form due

PAGE 179

161 to cracking, a concrete cylinder was analyzed It was assumed that micro columns formed due to longitudinal and radial cracking. The crack spacing in both the longitudinal and radial directions controlled the size of th e micro columns. As the longitudinal cracks grow deeper it was assumed that they eventua lly met at the center of the cylinder. This created slices around the circumference of the cy linder such as the one seen in Fig. 8-2. Figure 8-2. Concrete cylinder slice The ends of the cylinder are usually not da maged because the conc rete is confined by the friction between the platens that are used to load the concrete cylinder which often results in the formation of conical regions at the ends of the cyli nders (Mindess et al. 2003; Kotsovos and Pavlovic 1999). Kotsovos an d Pavlovic (1999) suggested that if the friction between the load platens and the c oncrete cylinder was re duced then the post peak behavior became more brittle and essent ially zero when no friction force existed.

PAGE 180

162 However, it was noted that complete elimin ation of friction duri ng cylinder testing had not been achieved. They also suggested that th e behavior of concrete prior to peak stress was not affected by the amount of friction betw een the load platens and the cylinder. The effect of friction on the cylinder behavior wa s also recognized by Mindess et al. (2003) who indicated that the confini ng effect of the platens extends as far as a distance from each end of approximately (30.5/2) d which meant that for a concrete cylinder with a diameter of 6 in. the unconfined section of the cylinder was very small, approximately 2 in. Therefore, the damage and failure zone was located towards the mid-height of the cylinder. Mindess et al. (2003) al so indicated that as the c onfining effect of the load platens was reduced the failure patterns of the concrete cylinders changed from cone failure to columnar failure for the cylinders with minor confining effects. This type of failure was also described in the ASTM C 39/C39M standard test method for concrete cylinders as one of the possible fracture type s for concrete cylinders tested in uniaxial compression (ASTM 2001). Landis and Shah (1993) tested small si ze mortar beams in bending and used acoustic emissions to map the cracks across the section of the beams. They found that the cracks were denser and longer on the external layers of the beams and became shorter closer to the center of the cross-section. The beam cross section had two regions with regard to the rate of change of the crac k length. Region one extended from the outside face of the beam to a distance approximately one eighth to one quarter the width of the beam. In region one the crack profile followed an angle of 50 to 64 degrees while in region two the angle was 7 to 11 degrees (see Fig. 8-3). Similar results were obtained by Kan and Swartz when they mapped the crack profiles of small beams using a dye

PAGE 181

163 penetration method (Mindess et al.). The crack profile of the air cured specimens was similar to the crack profil e of Landis and Shah (1993). Based on these observations it was reasonable to assume that the critical length of the micro columns was not constant but varied through the cylinder becoming smaller towards the center of the cylinder. The length ch ange was more severe in the outer layers and close to the exterior surface. The lengt h change was significantly smaller for the interior concrete laye rs (see Fig. 8-4). Estimated crack profile 50o64o 11o7o Region 2 Region 1 Load A ACross-section A-ALoad test set-up Figure 8-3. Distributi on of acoustic emissions for mortar beams Therefore, it was assumed that the combin ation of radial and longitudinal cracks generated a series of micro columns with s horter lengths and smaller cross sections as they approached the center of the cylinder (see Fig. 8-5). For this study it was assumed that the micro column length variation was b ilinear from the outside face of the cylinder to its center. The lengths of the micro columns varied by an angle 1 from the exterior concrete layers and by an angle 2 thereafter to the center of the cylinder (see Fig. 8-4).

PAGE 182

164 It was also assumed that on average both the radial and longitudinal cracks had a constant spacing between them. The spacing of the l ongitudinal cracks was not necessarily the same as the spacing of the radial cracks. The radial cracks were assumed to have a spacing t and the longitudina l cracks a spacing of degrees from the center of the cylinder. e A A A A Section A-AConcrete cylinder Figure 8-4. Crack profile of concrete cylinder (longitudinal cross-section) For a given size micro column to buckle the critical buckling stress had to be reached. This occurred when the longitudinal cracks reached a critical length at which case local buckling of the micro column cause d failure. The Euler critical buckling stress for the micro columns was determined using the Euler buckling equation: 2 2 i i iL Ao I E nc cr (8-1)

PAGE 183

165 where nc is the number of micro columns in each radial layer which was determined by dividing the 360 degrees of the circle by the angle E was the initial modulus of elasticity of concrete, I was the moment of inertia of the micro column, Ao was the area of the cylinder, and L was the length of the micro column The modulus of elasticity of concrete was assumed to be constant to simplify the model. Both the length and the moment of inertia varied between the micr o columns. The micro columns located on the exterior layers of the concrete cylinder ha d longer lengths and hi gher moments of inertia than the micro columns located towards the center of the cylinder. e n @ t Figure 8-5. Concrete cylinder micro columns The cross section of the micro columns was idealized and assumed to have a trapezoidal shape (dotted lines in Fig. 8-6) even though their shap e was like a circular segment (solid lines in Fig. 8-6). The height of the trapezoid was equal to the radial crack spacing (t). The lengths of the sides of the tr apezoid were calculated based on the longitudinal crack spacing angle () and their distance from th e center of the cylinder.

PAGE 184

166 The lengths of the sides of the trapezoid we re determined based on simple trigonometric relationships (see Fig 8-7). X0X1X2 t t Figure 8-6. Micro column a ssumed cross sectional shape From Fig. 8-7 the length Xi in terms of its distance from the center of the cylinder (ri) and the longitudinal crack spacing () was expressed as follows: ) 2 sin( 2 i ir X (8-2) Xi/ 2 ri Figure 8-7. Determining the length of the side of the trapezoid using trigonometry

PAGE 185

167 The angle was constant which meant that the length of the trapezoid sides was dependent only on the distance from the center of the cylinder. The distance from the center of the cylinder was smaller closer to the center which meant that the trapezoids were also smaller in size close to the center of the cylinder. For the exterior micro column the lengths of the trapezoid sides were equal to X0 and X1 (see Fig. 8-6). The lengths for the micro column adjacent to that were equal to X1 and X2 (see Fig. 8-6). Therefore, the moment of inertia of the idealized micro column cross section was generally expressed as follows: 1 2 1 1 2 336 4 i i i i i i iX X X X X X t I(8-3) The angle 1 by which the length varies for the ex terior layers was assumed to be equal to approximately 60 degrees For a given t value the angle 2 was varied until the resulting curve matched the experimental results but was kept close to 10 degrees. The length of the exterior micro column s (region 1 in Fig. 8-3) was calculated based on the first exterior micro column length (e), the distance of the micro column from the exterior surface of th e cylinder and the angle 1: 1 tan ) 2 ( 2 i ir d e L (8-4) The length of the interior micro columns (re gion 2 in Fig. 8-3) was calculated based on the last micro column length ( LB) of the first region disc ussed in the previous paragraph, the number of micro columns in the first region ( B ), the distance of the micro column from the center of the cylinder ( ri) and the angle 2 : 2 tan ) 2 ( 21 r t B d L LB i(8-5)

PAGE 186

168 With the critical stress calculated based on the Euler buckling e quation the load can be determined by simply multiplying th e stress by the area of the cylinder: Ao cr Pi i (8-6) where Pi was the total load on the cylinder, cri was the Euler buckling stress of the micro columns, and Ao was the area of the cylinder. The total axial compressive strain ( i) in the cylinder was determined based on the areas for each section of the cylinder and the micro column lengths relative to the length of the cylinder. The lengths for the micro co lumns were expressed as fractions of the length of the cylinder to simplify th e strain equation (see Fig. 3-20). Ao Ao Aci(Ao + Aci)/2 (Ao + Aci)/2 Lo (1-)Lo/2 (1-)Lo/2i Lo-i) Lo-i) Lo Figure 8-8. Cylinder set up for total strain determination The fraction for each micro column length was denoted as i and was determined as follows:

PAGE 187

169 Lo Li i (8-7) The total strain was equal to the total displacement of the cylinder over the length of the cylinder ( Lo ). The total strain of the cylinder was expressed in terms of the cross sectional areas and the length fractions as follows: 2 10 0 i i i i i iAc Ao Ac Ao E P (8-8) where 0 was the length fraction for th e exterior micro column, i was the length fraction for the micro column unde r the buckli ng stress and Aci was the area of the cylinder that remained unbuckled. The unbuckled area of the cylinder was the circular area enclosed by the micro columns under stress. The radius of the area was the di stance of the micro columns from the center of the cylinder ( ri). Therefore, the unbuckled area was: 2 i ir Ac (8-9) Eq. 8-8 was applicable for micro columns in the region 1. When buckling preceded into the second re gion the strain equation became: 2 2 10 0 i B i B B B i i i iAc Ac Ac Ao Ac Ao E P (8-10) To evaluate the sensitivity of the model to the variation of the number of micro columns in each buckling layer the angle was varied while the other parameters were kept constant. The effect of the number of micro columns on the peak strength is shown in Fig. 8-9. It was found that the model wa s sensitive to the numb er of micro columns only if the number was less than 18. For 18 or more micro columns the calculated peak stress did not change and was the same as th e experimental peak stress. Based on this the

PAGE 188

170 stress-strain curves were calculated usi ng 18 micro columns in each buckling layer ( = 20 degrees). 4 5 6 7 8 020406080 No of Micro ColumnsStress (ksi) Exper. Peak Stress Calculated Peak Stress Figure 8-9. Sensitivity of model to the number of micro columns The stress-strain curve of the concrete cylinder was constructed by plotting the critical stress against the strain. The parame ters of the model such as the crack spacing and the lengths of the micro columns are unknown and no experimental data were found in the literature to indicate their value. Therefore, an a ssumption about the value of the parameters was made. The parameters of the model were tuned to the specific experimental data set of the grid confined cy linders from chapter 3. The parameters were chosen to yield a curve that matched the e xperimental data from chapter 3. The set of parameters that best matched the experimental data are presented in table 8-1. It was assumed that the modulus of elasticity of concrete was equal to 4700 ksi (experimental concrete strength 6.8 ksi), longitudinal cracks were oriented at an angle of 20 degrees (approximate spacing 1.2 in. on the exterior face) and radial cracks at 0.15 in. The critical buckling length of the exterior micro column s was assumed to be approximately 3.6 in. Using these values the stress-strain curve of the concrete cylinder was constructed (see Fig. 8-10).

PAGE 189

171 Table 8-1. Parameters used to model beha vior of unconfined concrete cylinder in compression Parameter Value Ec (ksi) 4700 (degrees) 20 t (in.) 0.15 e (in) 3.6 0 2 4 6 8 10 00.0010.0020.0030.0040.005 Strain (in/in)Stress (ksi) Exper. (Aver. of 3) Model Figure 8-10. Experimental and calculated st ress-strain curves fo r unconfined control cylinders The fact that the stress-strain curve of c oncrete were calculated from the model was a strong indication that failure mechanisms of concrete can be explained using micro column buckling theory provided that crack spacing and critical length variation are known. Confined Concrete Model For the case of confined c oncrete the buckling theory suggests that although micro columns still formed they were braced by the CFRP grid or any other confining material. The mechanisms of failure ar e similar in that the micro columns fail by buckling. It was assumed that the CFRP grid di d not brace the columns immediately but rather after the micro columns buckled. Once buckled the micro columns pushed against the CFRP grid which generated a reaction R on the buckled micro columns (see Fig. 8-

PAGE 190

172 11). This generated extra load which was manifested into higher stresses and higher strains (higher ductility) for the cylinder. 0 1 2 3 i ... i R Figure 8-11. Restraint of micro columns by CFRP grid strand Because it was assumed that the micro co lumns buckle prior to being braced by the CFRP grid the model in Fig. 8-11 treated the micro columns as axially rigid columns with real hinges and rigid body motions. It was assu med that only the micro columns adjacent to the CFRP grid strand were restrained and the entire extra load from confinement was carried by those micro columns. The lateral displacement ( ) was determined using geometry (Fig. 8-12) in terms of the length of the micro column ( L ) and the axial compressive strain ( ). The strain used to determine the lateral displacement was the st rain calculated using Equations 8-8 and 810. Using the Pythagorean Theorem and rearranging the equation the lateral displacement at a given strain was equal to: 22 2i i iL (8-11) The load (PR) contributed by the restrained micro column was calculated by summing moments about point B (Fig. 8-12). After rearranging the equation the load PR was:

PAGE 191

173 4L R PR (8-12) i R L/2 L/2 ( ) L/2 ( ) L/2 PRA B C PR R/2 R/2 Figure 8-12. Geometry of micro colu mn restrained by the CFRP grid The reaction R from the CFRP grid was equal to the lateral stiffness of the grid ring (K) times the lateral displacement. It was assumed that only one grid ring was contributing to the stiffness of the spring used to model the grid restraint. This reduced Equation 8-12 into: 4L K PR (8-13) The stiffness of the grid ring (K) and the length of the micro column were constant quantities which made load PR also constant and inde pendent of the lateral displacement The stiffness of the grid ring was equal to:

PAGE 192

174 2 sin 2T K (8-14) where T was the force for a unit lateral displacement of the CFRP grid ring (see Fig. 813). /2 /2 /2 1" T T T sin ( /2) T sin ( /2) Figure 8-13. Lateral stiffness of CFRP grid ring The critical stress for the confined concrete was determined as the critical stress to buckle the unconfined micro column plus the stress produced by the additional load PR. Therefore, the concrete stress for the confined concrete ( cci) was the following: Ao P nc P ccR i i (8-15) The concrete outside the CFRP encasement was treated as unconfined and the extra load PR was set equal to zero. The total load used to calculate the st rain in the cylinder was equal to the contribution of the concrete micro columns and the extra load from each micro column

PAGE 193

175 that was restrained by the grid. A total of 18 micro columns were restrained by the grid. Therefore the total load used to calculate strain was determined based on the following: R i iP nc P Pt (8-16) Using the total load from Eq. 8-16 and s ubstituting into Eqs 3-8 or 3-10 the new strain was calculated. The lateral displacem ent of the micro columns controlled the failure of the CFRP grid ring. It was discovere d that based on the leng th and the strain of the micro column adjacent to the CFRP grid, the CFRP grid was reaching failure strains as soon as the micro column buckled. This was not observed during the tests and two possibilities exist: (1) the CFRP grid layers were not bonded together and it is possible that once the outside concrete was damaged th ere was some slippage developed since the bond between the grid and the c oncrete weakened, and (b) as it is often the case with actual structures it usually ta kes some initial movement before all components stiffen and start working together. Therefore, an initia l spacing between the micro column and the CFRP grid of approximately 0.019 in. was a ssumed. This initial spacing was selected based on the experimental data from grid c onfined cylinders presented in chapter 3. Therefore, the selection of th e initial spacing is tuned to th at specific group of data. The initial spacing prevented the CFRP grid from engaging the buckled micro columns immediately. The lateral displacement of the CFRP grid was then equal to the total lateral displacement reduced by th e assumed initial spacing. The lateral displacement was compared to th e failure lateral displacement (fail) of the CFRP grid ring that was determined as follows: f f f faild L 1 2 1 (8-17)

PAGE 194

176 where f is the failure strain of the CRFP grid When the lateral displacement exceeded the failure lateral displacement the cylinder was considered to have failed due to loss of confinement caused by CFRP grid rupture. The stress-strain curves of the cylinders with two CFRP grid layers, for the two grid diameters tested, were calculated a nd plotted against the average experimental curves obtained from cylinder tests (see Figs 8-14 and 8-15) The experimental stressstrain curves in Figs 8-14 and 8-15 were the average curves from three tests for each CFRP grid diameter. The stress-strain curves for both grid diam eters matched well with the experimental curves. The CFRP grid rupture was represented by the last point on the curves. The calculated peak stress was lower that the experimental peak stress by approximately 3% for the cylinders with a grid diameter of 5.25 in. The calculated peak stress for the cylinders with a grid diameter of 5.5 in. wa s the same as the experimental peak stress. However, the assumed parameters of the model were selected to match the experimental data from grid confined cylinde rs presented in chapter 3. Therefore, the model was tuned to the specific data. 0 2 4 6 8 10 00.0020.0040.0060.0080.01 Strain (in/in)Stress (ksi) Exper. (Aver. of 3) Model Figure 8-14. Stress-strain curves for grid diameter of 5.25 in.

PAGE 195

177 0 2 4 6 8 10 00.0020.0040.0060.0080.01 Strain (in/in)Stress (ksi) Exper. (Aver. of 3) Model Figure 8-15. Stress-strain curves for grid diameter of 5.5 in. The effect of additional layers of grid on the strength and ductility of the cylinder was determined by simply increasing the numbe r of CFRP grid layers. This was done for 2, 4, 5 and 6 layers for cylinders with a grid diameter of 5.5 in. (see Fig. 8-16). 0 2 4 6 8 10 00.0030.0060.0090.0120.015 Strain (in/in)Stress (ksi) M, H & A (2 layers) M, H & A (4 layers) M, H & A (5 layers) M, H & A (6 layers) Figure 8-16. Stress-strain curves fo r different amounts of CFRP grid The addition of the extra CFRP layers had a significant effect on their ductility with the cylinders with the higher number of grid layers having higher ultimate strains. The effect of the CFRP grid on the strength of the cylinder was small (10% increase for the 2 layers and 16% increase for the 6 layers compared to the unconfined strength). The increase in the ultimate strain was very significant and was increas ing as the amount of

PAGE 196

178 CFRP grid was increased. The cylinder with two grid layers had approximately 2 times higher ultimate strain than the unconfined cylinder. The cylinder with six layers of the CFRP grid had approximately 3.8 times highe r ultimate strain. An important observation from Fig. 3-28 was that there seems to be an apparent softening as soon as the cover concrete was assumed to have been lost due to buckling of th e exterior layers. Discussion This model is an alternative to the concrete confinement models available. The difference with other confinement models is th at it is based on simple failure mechanisms such as column buckling. A number of models use hydr ostatic pressure mechanics to calculate the confining pressure that they then multiply by an effectiveness factor which is empirically estimated to determine the peak stress. Other models a ssume a variable confining pressure based on the Poisson ratio that is calculated based on empirical formulas. The variable confining pressure is still used in empirical equati ons and is multiplied by empirical factors. Although all these models may predict the behavior of confined concrete they are complicated and their mechanics bac kground very difficult to comprehend. The model presented here attempts to pr ovide a simple approach and to explain failure mechanics of concrete based on si mple concepts that are easily understood. Column buckling is simple and has been used for a long time which makes this approach easy to follow. The model presented is based on a number of assumptions that need to be verified through experimental testing. Some of the pa rameters used in the model could possibly be measured through experimental testing a nd expressions to calcu late them can be developed. For example the crack spacing that controls the size of the micro column

PAGE 197

179 needs to be determined. In the model it was assumed that the radial crack spacing was constant but it has been implied in the literatu re that the cracks at the outer layers of the concrete are more severe. This could mean that the cracks are also closer together in the outer layers. The length of the micro column was assu med to vary linearly across the two identified regions (regions 1 and 2) of th e cylinder becoming smaller towards the center for simplification. A different relationship for the variation of the micro column length can be explored such as a para bolic relationship. It should be noted that constant values of the micro column length across the cross s ection were investigated but did not yield any reasonable results. Another issue that needs to be addressed is the modulus of elasticity of concrete. In this study the modulus was assumed constant but it is known that the initial modulus varies for different concrete strengths. Empirical relationships that estimate the initial concrete modulus depended on the design st rength are available and could provide estimations for the different concrete strengths. Another aspect of the model that might ha ve an impact on the different parameters used in this model is the amount of CFRP grid reinforcement. Only a few tests have been conducted using a specific amount of the CFRP grid. More tests with increasing amount of CFRP grid reinforcement are needed to validate the confinement model. The CFRP grid has not been used for this purpose before and its overall effect on the behavior of concrete is somewhat differe nt than the effect of other types of FRP reinforcement. Therefore the findings from ot her studies do not necessarily apply to the case of CFRP grid confined concrete.

PAGE 198

180 Conclusions Based on the information presented the following conclusions can be drawn: This new approach is based on the theory that concrete cracking results in the formation of micro columns in concrete th at under the right c onditions fail due to buckling. The structural mechanics behind this new idea are easy to understand which is different than other approach es that are typically used. The stress-strain curves constructed using th e concrete model, were fitted to the data obtained from grid confined cylinders. The model was tuned to that specific group of data presented in detail in chapter 3. It was also evident that the model needs to be improved and its parameter need to be further investigated. The amount of experime ntal data was limited and therefore more tests for calibration of the parameters are needed. The effect of increasing the number of CF RP grid layers to the cylinders had a positive effect on both the strength of the confined concrete as well as its ultimate strain. The effect on the strength was sma ll (less than 5% increase from two to six layers). A very significant effect on the ulti mate strain of the confined concrete was calculated by the model. The concrete w ith the six layers of CFRP grid had approximately 89% more ductility than th e cylinder with two CFRP grid layers.

PAGE 199

181 CHAPTER 9 CONCLUDING REMARKS AND FUTURE REASERCH Dissertation Summary Corrosion of prestressing steel in precas t concrete is a significant problem for coastal bridges in Florida wh ich results in higher maintena nce costs due to the adoption of protective measures for the prestressing st eel. Even if repair and protective measures are employed to extend the life of the struct ure, they are costly, time consuming and rarely add significantly to the service life. It was suggested that carbon fiber reinfo rced polymer (CFRP) reinforcement can provide a viable replacement option if the focus of improving member ductility was concentrated on the concrete, rather than the CFRP, through confinement that delays degradation of the compression zone at capac ity, resulting in a more ductile response. The objective of this disser tation was to develop methods by which CFRP grid can be used to confine concrete and to develop a model that will predict the behavior of concrete confined by this grid. These obj ectives were accomplished through a series of tasks. First, concrete cylinders with embedded grid were constructed and tested in compression to experimentally obtain the beha vior of concrete confined by the grid. A new approach in explaining concrete failure using buckling was offered. A new confinement model was developed based on co ncrete buckling failure mechanics that predicts the behavior of CFRP grid confined concrete. The experimental data from the cylinders was used to validate th e developed confinement model.

PAGE 200

182 Secondly, the grid was used in different configurations to provide confinement for concrete elements such as beams, cast in place piles and spun cast piles. The construction, experimental testing and experi mental results from th e different confining configurations were discussed and presented. This included the c onstruction and testing of two rectangular reinforced concrete b eams that used CFRP grid tubes in the compression zone to confine concrete. The tw o beams were designed to fail by concrete crushing. Another configuration tested was the use of the CFRP grid to wrap FRP reinforced concrete piles. Four piles were constructed and tested in flexure. The construction and testing details were presented. Experimental results from the four tests were discussed and presented. The last configuration tested was the CFRP grid embedment in hollow spun-cast concrete p iles reinforced with CFRP flexural reinforcement. A total of 6 spun-cast p iles were manufactured and tested. The manufacturing and testing deta ils as well as the experime ntal results of the CFRP reinforced spun-cast piles tested in flexur e were discussed and presented in this dissertation. Finally, a static non-linear analysis of pile be nts using both pr estressing steel and FRP reinforcement was presented to determ ine whether the ductil ity of the elements translates into ductility for the structural system and to determine whether the FRP reinforced piles have comparable ductility to the steel reinforced prestress piles. The results from the analyses were presented and discussed. The ductility factors of the different systems were determined and presented. Summary of Conclusions Based on the findings presented in this dissertation the following summary of conclusions is offered:

PAGE 201

183 No evidence of CFRP grid used as c onfinement reinforcement was found but the available research suggests that it is po ssible to improve concre te ductility by using FRP materials as confinement reinforcement. The available research suggest s that non-linear static analys is can be used to analyze structural systems under dynamic loads and can produce good results. The CFRP grid does not produce a highly c onfined concrete. This was expected since the amount of CFRP material provide d by the grid is low due to its large openings. Significant improvement was observed in the du ctility of the concrete cylinders with embedded CFRP grid. The ultimate strain for the grid cylinders was 2 times the ultimate strain of the control cylinders. Grid confinement also resulted in an increase in the concrete strength of approximately 10.7%. The modified Hognestad provides an accurate empirical prediction of the behavior of concrete confined with the CFRP grid. The results from the CFRP grid tube b eam indicate that the CFRP grid provided confinement to the concrete when compar ed to the control beam. Confinement was achieved using a series of small diameter CFRP grid tubes rather than wrapping the entire cross-section. The displacement ductility of the beam utilizing the CFRP grid tubes was improved by 17% compared to the control beam with no grid tubes. The curvature ductility of the beam utilizing the CFRP grid tubes was improved by 27% compared to the control beam with no grid tubes. This wa s due to concrete confinement provided by the CFRP grid. The improvement in the duc tility of the tube beam was significant considering the small amount of CFRP th at was used to confine the compression zone. The energy dissipation of the grid tube beam was 37% higher compared to the controlled beam due to the eff ect of concrete confinement. This increase in the energy dissipation of the element also represents an improvement in the ductility due to concrete confinement from the CFRP grid tubes. The results from all four cast in place p iles indicate that the CFRP grid provided confinement to the concrete. Cast in place piles reinforced with gla ss FRP bars and carbon FRP grid failed in flexure and their failure was ductile. Cast in place pile reinforced with carbon FRP bars and without the carbon grid failed in sh ear-flexure. Cast in place pile reinforced with carbon FRP bars and grid failed in fl exure and its ductility was improved by as much as 20%.

PAGE 202

184 The presence of CFRP grid and its confini ng effect resulted in a significant increase in the capacity of cast in place pile reinforced with carbon FRP bars and grid of approximately 52% compared to cast in pl ace pile reinforced with carbon FRP bars and without the carbon grid. For cast in pl ace piles reinforced with glass FRP bars and carbon FRP grid the effect of confinemen t on the capacity can not be determined because no control specimens exist for comparison. The results from the spun-cast piles indicate th at the ductility of th e grid piles was not significantly altered. These c ould be attributed to two ma jor reasons: (1) The mode of failure was not always flexure and (2) Lack of concrete confinement due to damage accumulated during construction. The only sp an-cast pile that had both a flexure failure and concrete conferment was pile SCG2 and visual observations during the test indicated a change in the behavior using the CFRP grid as confinement reinforcement. Experimental data to suppor t these visual observa tions do not exist. The spun-cast tests revealed problems with the manufacturing practice that proved to be very significant in influencing th e behavior of the pile specimens. The experimental results from the spuncast pile tests represent a lower bound solution to the ductility problem of spuncast manufactured CFRP reinforced piles. The results from the experimental and theore tical static non-linear analysis indicate that member ductility did translate to syst em ductility when plastic hinge formation took place in all the system members. When the load was applied to the pile bent head (load case one) the system behavior was ductile while when the load was applied on the one of the external piles (load case two) failure of the external pile took place prior to plastic hinge formation in the other piles. However, the pile itself can provide a ductile response when impacted by a marine vessel. A ductile system behavior was feasible with pile bents using piles reinforced with FRP when using concrete confinement to pr oduce ductility at the member level that eventually translated to system ductility. Prestressing of the FRP reinforcement was required because the theoretical results indicated that it improved both the stiffn ess and the ductility of the members and therefore the stiffness and ductility of the system. Using piles with two CFRP grid layers provi ded pre-cast prestressed CFRP reinforced pile bents with approximately 67% of the ductility of the new intact steel prestressed pile bent. The pre-cast prestressed CFRP reinforced pile bents had the highest ductility factor of all FRP reinforced piles bents. Although lower than the ductil ity factor of a new intact steel prestressed pile bent these pile bents did compar e favorably with the steel prestressed pile bents with minor, modera te or severe corrosion damage. Actually

PAGE 203

185 they exhibited superior prope rties to the moderately corroded steel prestressed pile bent in both ductility (30% higher) and stre ngth because the moderately corroded pile bent had a strength reduction of approximate ly 35%. The steel prestressed pile bent with minor corrosion damage had higher duc tility but its strength was reduced by approximately 15%. The severely corroded pile bent did have a higher ductility but its strength degradation was severe amounting only to approximately 35% of its theoretical capacity. A new confinement model is proposed. This ne w approach is based on the theory that concrete cracking results in the formation of micro columns in concrete that under the right conditions fail due to buckling. The structural m echanics behind this new idea are easy to understand which is different than other approaches that are typically used. The stress-strain curves constructed using th e concrete model, were fitted to the data obtained from grid confined cylinders. The model was tuned to that specific group of data presented in detail in chapter 3. It was also evident that the model needs to be improved and its parameter need to be further investigated. The amount of experime ntal data was limited and therefore more tests for calibration of the parameters are needed. Future Research It is impossible to test every applicat ion of the CFRP grid in the different configurations that can be used to provide confinement due to time and money constrains. However, more research relating to the resear ch included in this di ssertation can be done in the future to build on the lessons learned a nd also test the grid in other configurations in concrete structures. The following sugge stions on future research are offered: The improvement, refinement and further validation of the c onfinement model are necessary. This can be done by providing mo re experimental data from CFRP grid confined concrete cylinder tests. These tests can explore different unconfined concrete strengths, different amounts of re inforcement and different sizes of the CFRP grid encasement. The later can only be achieved by testing larger than standard size cylinders because the grid is very diffi cult to form in round shapes less than 6 in. Since different CFRP grid configurations exist it would be a dvantageous to test cylinders with the different CFRP grids to find out if any other CFRP grid can provide enough ductility to be used in FRP reinforced piles or columns. Apart from providing experimental data to validated and help improve the concrete confinement model more work is needed on th e analytical side of the model. Some of the parameters involved in the model such as the initial modul us of elasticity of

PAGE 204

186 concrete as well as the longitudinal crack sp acing were assumed to be constant but it is quite possible that they are variable. Thei r effect on the model when they are varied needs to be investigated and taken into account. Another confinement configuration of the CF RP grid that can be investigated is related to the CFRP grid tube beams. In this configuration a series of CFRP grid tubes that serve both as confinement reinforcement as well as longitudinal reinforcement can be used in columns. This means that th e longitudinal strands of the grid will have to be more heavily reinforced to provide enough flexural strength and force a flexural failure mode that will promote concrete cr ushing and not rapture of the longitudinal CFRP reinforcement. In this dissertation the CFRP grid tube s or rings were manufactured by loosely wrapping layers of the available grid to bu ild the desired thickness, size and shape. The manufacture of solid CFRP grid pieces with the desired thickness, shape and size can improve constructability of the concrete elements. This pre-manufactured CFRP grid tubes can serve both as the confinement reinforcement as well as flexural reinforcement much like the suggestion described in the previous suggestion with the difference that one large tube wi ll be used in this case rather than a series of smaller tubes.

PAGE 205

187 LIST OF REFERENCES Abdel-Fattah, H., and Ahmad, S. H., 1989, Behavior of Hoop-Confined High-Strength Concrete under Axial and Shear Loads, AC I Structural Journal, Vol. 86, pp. 652659. Abdelrahman, A. A., and Rizkalla, S. H., 1999, Deflection Control of Concrete Beams Pretensioned by CFRP Reinforcement, J ournal of Composites for Construction, Vol. 3, No 2, pp. 55-62. ACI Committee 318, 2002, Building Code Requirements for Structural Concrete, American Concrete Institute, Farmington Hills, MI. Alsayed, S. H., and Alhozaimy, A. M., 1999, Ductility of Concrete Beams Reinforced with FRP bars and Steel Fibers, Journal of Composite Materials, Vol. 33, No 19, pp. 1792-1806. ASTM, 2001, ASTM C39 / C39 M 01 Standa rd Test Method for Compressive Strength of Cylindrical Concrete Specimens, Ameri can Society for Testing and Materials, West Conshohocken, PA. ASTM, 2003, ASTM C31 / C31 M 03a St andard Practice for Making and Curing Concrete Test Specimens in the Field, Am erican Society for Testing and Materials, West Conshohocken, PA. ASTM, 2004, ASTM C172 04 Standard Practi ce for Sampling Freshly Mixed Concrete, American Society for Testing and Materials, West Conshohocken, PA. Baker, A. L. L., 1956, Ultimate Load Theory Applied to the Design of Reinforced and Prestressed Concrete Frames, Concre te Publications Ltd, London, p. 91. Baker, A. L. L., and Amarakone, A. M. N., 1964, Inelastic Hyperstatic Frames Analysis, Proceedings of the Internati onal Symposium on the Flexural Mechanics of Reinforced Concrete, ASCE-ACI, Miami, pp. 85-142. Barbero, E. J., 1998, Chapter 7: Fail ure and Strength Design, Introduction to Composite Materials Design, Taylor and Francis, Philadelphia, PA, pp. 181-230. Budek, A. M., Priestley, M. J. N. and Benz oni, G., 2000, Inelastic Seismic Response of Bridge Drilled-Shaft RC Pile/Columns, J ournal of Structural Engineering, Vol. 126, No 4, pp. 510-517.

PAGE 206

188 Caltrans, 2004(a), Section 5: Analysis, Seismic Design Criteria 1.3, Caltrans, Sacramento, California, p. 7. Caltrans, 2004(b), Section 7: Design, Seismic Design Criteria 1.3, Caltrans, Sacramento, California, p. 32. Campione, G., and Miraglia, N., 2003, Str ength and Strain Capacities of Concrete Compression Members Reinforced with FR P, Cement and Concrete Composites, Vol. 25, No 1, pp. 31-41. Chaallal, O., and Benmokrane, B., 1996, Fiber -Reinforced Plastic Rebars for Concrete Applications, Composites: Part B, Vol. 27, No 3-4, pp. 245-252. Cho, C. G., Kwon, M., and Spacone, E., 2005, Analytical Model of Concrete-Filled Fiber-Reinforced Polymer Tubes based on Mu ltiaxial Constitutive Laws, Journal of Structural Engineering, Vol. 131, No 9, pp. 1426-1433. Consolazio, G. R., Fung, J., and Ansley, M., 2004, M-P Diagrams for Concrete Sections under Biaxial Flexure and Axia l Compression, ACI Structural Journal, Vol.101, No 1, pp. 114-123. Corley, W. G., 1966, Rotational Capacity of Reinforced Concrete Beams, Journal of Structural Division, Vol. 92, ST5, pp. 121-146. Davol, A., Burgueno, R., and Seible, F., 2001, Flexural Behavior of Circular Concrete Filled FRP Shells, Journal of Structural Engineering, Vol. 127, No. 7, pp. 810817. El-Salakawy, E., Benmokrane, B., and Desg agne, G., 2003, Fibre-Reinforced Polymer Composite Bars for the Concrete Deck Sl ab of Wotton Bridge, Canadian Journal of Civil Engineering, Vol. 30, pp. 861-870. Fam, A. Z., and Rizkalla, S. H., 2001, Conf inement Model for Axially Loaded Concrete Confined by Circular Fiber-Reinforced Po lymer Tubes, ACI Structural Journal, Vol. 98, No 4, pp. 451-461. Fenves, G. L, and Ellery, M., 1998, Behavio r and Failure Analysis of a Multiple-Frame Highway Bridge in the 1994 Northri dge Earthquake, Pacific Earthquake Engineering Research Center, College of Engineering, University of California Berkley, PEER Report 1998/08, p. 171. Gadappa, D. C., Sanjayan, J. G., and Setunge S., 2001, Complete Triaxial Stress-Strain Curves of High-Strength Concre te, Journal of Materials in Civil Engineering, Vol. 13, No 3, pp. 209-215. Grace, N. F., and Sayed, G. A., 1998, Duc tility of Prestressed Bridges Using CFRP Strands, Concrete International, Vol. 20, No 6, pp. 25-30.

PAGE 207

189 Grace, N. F., Soliman, A. K., Sayed, G. A., and Saleh, K. R., 1998, Behavior and Ductility of Simple and Continuous FRP Reinforced Beams, Journal of Composites for Construction, Vol. 2, No 4, pp. 186-194. Halabian, A. M., El Naggar, M. H., and Vickery, B. J., 2002, Nonlinear Seismic Response of Reinforced-Concrete Free-Stan ding Towers with Application to TV Towers on Flexible Foundations, The Struct ural Design of Tall Buildings, Vol. 11, Wiley InterScience (www.interscience.wiley.com ), pp. 51-72. Harries, K. A., and Gassman, S. L., 2003, L oad Tests of Reinforced Concrete Catch Basing Knockout Panels, Department of Civil and Environmental Engineering, University of South Carolina, Report No ST03-01, p. 21. Harries, K. A., and Kharel, G., 2002, Experime ntal Investigation of the Behavior of Variably Confined Concrete, Cement and Concrete Research, Vol. 33, No 6, pp. 873-880. Hasan, R., Xu, L., and Grierson, D. E., 2002, Push-Over Analysis for PerformanceBased Seismic Analysis, Computers a nd Structures, Vol. 80, No 31, pp. 24832493. Hassoun, M. N. and Al-Manaseer, A., 2005, Chapter 2: Properties of Reinforced Concrete, Structural Concrete: Theory and Design, Third Edition, John Wiley and Sons, Inc., Hoboken, NJ, pp. 15-59. Hassoun, M. N., 2002, Chapter 2: Propertie s of Reinforced Concrete, Structural Concrete: Theory and Design, Second Ed ition, Prentice Hill, Inc., Upper Saddle River, NJ, pp. 15-36. Hughes, 2002(a), Glass Fiber Reinforced Polymer (GFRP) Rebar: Aslan 100, Information Flier, Hughes Brothers, Seaward, NE. Hughes, 2002(b), Carbon Fiber Reinforced Polymer (CFRP) Rebar: Aslan 200, Information Flier, Hughes Brothers, Seaward, NE. Hughes, 2004, Tensile Testing of 40 ft L ong #3 Size Carbon Fiber Reinforced Polymer (CFRP) Rebars, Test Report, Hughes Brothers, Seaward, NE. Hughes, 2005, Tensile Testing of #2 Size Ca rbon Fiber Reinforced Polymer (CFRP) Rebars, Test Report, Hughes Brothers, Seaward, NE. Jansons, J. O., Glejbol, K., Rytter, J., Anis kevich, A. N., Arnautov, A. K., and Kulakov V. L., 2002, Effect of Water Absorption, Elevated Temperatures and Fatigue on the Mechanical Propertie s of Carbon-Fiber-Reinforced Epoxy Composites for Flexible Risers, Mechanics of Composite Materials, Vol. 38, No. 4, pp. 299-310. Jeong, S. M., 1994, Evaluation of Ductility in Prestressed Concrete Beams Using Fiber Reinforced Plastic Tendons, PhD Thesis, University of Michigan, Ann Arbor, MI.

PAGE 208

190 Kotsovos, M. D. and Pavlovic, M. N., 1999, Ultimate Limit-State Design of Concrete structures: A New Approach, Thomas Te lford, Ltd, London, England, p.164. Lam, L., and Teng, J. G., 2004, Ultimat e Condition of Fiber Reinforced PolymerConfined Concrete, Journal of Composite s for Construction, Vol. 8, No 6, pp. 539-548. Landis, E. N., and Shah, S. P., 1993, Recovery of Microcrack Parameters in Mortar Using Quantitative Acoustic Emission, Jour nal of Nondestructive Evaluation, Vol. 12, No 4, pp. 219-232. Li, J., and Hadi, M.N.S., 2003, Behaviour of Externally Confined High-Strength Concrete Columns under Eccentric Loading, Composite Structures, Vol. 62, No 2, pp. 145-153. Li, V. C., and Wang, S., 2002, Flexural Be haviors of Glass Fiber-Reinforced Polymer (GFRP) Reinforced Engineered Cementi tious Composite Beams, ACI Materials Journal, Vol. 99, No 1, pp. 11-21. Li, Y., Lin, C., and Sung, Y., 2003, Compre ssive Behavior of Concrete Confined by Various Types of FRP Composite Jackets, Mechanics of Materials, Vol. 35, No 36, pp. 603-619. MacGregor, J. G., 1997, Chapter 3: Materi als, Reinforced Conc rete: Mechanics and Design, Third Edition, Prentice Hall, Upper Saddle River, NJ, pp. 35-81. Mackie, K., and Stojadinovic, B., 2003, S eismic Demands for Performance-Based Design of Bridges, Pacific Earthquake E ngineering Research Center, College of Engineering, University of Californi a Berkley, PEER Report 2003/16, p. 156. Malvar, L. J., 1998, Durability of Composites in Reinforced Concrete, CDCC First International Conference on Durability of Composites for Construction, Sherbrooke (Qubec) Canada, August 1998. Mandal, S., Hoskin, A., and Fam, A., 2005, Influence of Concrete Strength on Confinement Effectiveness of Fiber-Rein forced Polymer Circular Jackets, ACI Structural Journal, Vol.102, No 3, pp. 383-392. Mander, J. B., Priestley, M. J. N., and Pa rk, R., 1988, Theoretical Stress-Strain Model for Confined Concrete, Journal of Struct ural Engineering, Vol. 114, No 8, pp. 1804-1826. Mei, H., Kiousis, P. D., Ehsani, M. R ., and Saadatmanesh, H., 2001, Confinement Effects on High-Strength Concre te, ACI Structural Journa l, Vol.98, No 4, pp. 548553. Micelli, F., and Nanni, A., 2004, Durability of FRP Rods for Conc rete Structures, Construction and Building Materials, Vol. 18, No 7, pp. 491-503.

PAGE 209

191 Mindess, S., Young, J. F., and Darwin, D., 2003, Chapter 14: Testing of Hardened Concrete, Concrete, Second Edition, Pren tice Hall, Upper Saddle River, NJ, pp. 363-400. Mirmiran, A., Shahawy, M., Samaan, M., El Echary, H., Mastrapa, J. C., and Pico, O., 1998, Effect of Column Parameters on FRP-Confined Concrete, Journal of Composites for Construction, Vol. 2, No 4, pp. 175-185. Myers, J., Nanni, A., and Micelli, F., 2002, Characterization of a New FRP Bar for Reinforcement of Concrete, Center for Infrastructure Engineering Studies/UTC Program University of Missouri Rolla, Report No R49, p. 127. Nawy, E. G., 2003, Chapter 3: Concrete, Reinforced Concrete: A Fundamental Approach, Fifth Edition, Prentice Hall, Upper Saddle River, NJ, pp. 20-67. Nawy, E. G., 2005, Chapter 3: Properties of Hardened Concrete, Reinforced Concrete: A Fundamental Approach, Fifth Edition, Pr entice Hall, Upper Saddle River, NJ, pp. 20-67. Newhook, J., Ghali, A., and Tadros, G., 2002, Concrete Flexural Members Reinforced with Fiber Reinforced Polymer: Design for Cracking and Deformability, Canadian Journal of Civil Engineering, Vol. 29, No 1, pp. 125-134. Pantelides, C. P., Gergely, J., Reaveley, L. D., and Volnyy, V. A., 1999, Retrofit of RC Bridge Pier with CFRP Adva nced Composites, Journal of Structural Engineering, Vol. 125, No 10, pp. 1094-1099. Park, R., and Paulay, T., 1975 (a), Chapter 6: Ultimate Deformati on and Ductility of Members with Flexure, Reinforced Concre te Structures, John Wiley & Sons, New York, NY, pp. 195-269. Park, R., and Paulay, T., 1975 (b), Chapter 11: Strength and Ductility of Frames, Reinforced Concrete Structures, John Wiley & Sons, New York, NY, pp. 496-609. Priestley, M. J. N., and Park, R., 1987, S trength and Ductility of Concrete Bridge Columns under Seismic Loading, ACI Structural Journal, Vol. 84, No 1, pp. 6176. Rahman, A. H., Kingsley, C. Y., and Kobaya shi, K., 2000, Service and Ultimate Load Behavior of Bridge Deck Reinforced with Carbon FRP Grid, Journal of Composites for Construction, Vol. 4, No 1, pp. 16-23. Rooney, J., and Taylor, S., 2004, Flexural Behaviour of Steel and GFRP Reinforced Concrete Beams, Composites: Part B, Vol. 27, No 3-4, pp. 38-40. Saatcioglou, M., and Razvi, S. R., 2002, Displacement-Based Design of Reinforced Concrete Columns for Confinement, ACI Stru ctural Journal, Vol. 99, No 1, pp. 311.

PAGE 210

192 Samaan, M., Mirmiran, A., and Shahawy, M., 1998, Model of Concrete Confined by Fiber Composites, Journal of Structural Engineering, Vol. 124, No 9, pp. 10251031. Sawyer, H. A., 1964, Design of Concrete Fr ames for Two Failure States, Proceedings of the International Symposium on the Fle xural Mechanics of Reinforced Concrete, ASCE-ACI, Miami, pp. 405-431. Sfer, D., Carol, I., Gettu, R., and Etse, G., 2002, Study of the Behavior of Concrete under Triaxial Compression, Journal of E ngineering Mechanics, Vol. 128, No 2, pp. 156-163. Shah, S. P., Swartz, S. E., and Ouyang, C ., 1995, Chapter 4: St ructure and Fracture Process of Concrete, Fracture Mechanics of Concrete: Applications of Fracture Mechanics to Concrete, Rock and Other Quasi-Brittle Materials, John Wiley and Sons, Inc., New York, NY, pp. 88-110. Shahawy, M, Mirmiran, A., and Beitelman, T., 2000, Tests and Modeling of CarbonWrapped Concrete Columns, Composites Part B: Engineering, Vol. 31, No 6-7, pp. 471-480. Shao, Y., Johnson, C., and Mirmiran, A., 2003, Control of Plastic Shrinkage Cracking of Concrete with TechFab Carbon FRP Grids, Department of Civil, Construction, and Environmental Engineering, North Caro lina State University, Report to TechFab Inc, p. 7. Sheikh, S. A., and Khoury, S. S., 1993, Conf ined Concrete Columns with Stubs, ACI Structural Journal, Vol. 90, No 4, pp. 414-431. Sika, 2003, Sika CarboDur Rods: Carbon Fi ber Rods for Structural Strengthening, Technical Data Sheet, Sika Corporation, Lyndhurst, NJ. TechFab, 2004, C-Grid Carbon Grid for Concrete Reinforcement: C-5500-AX1, Technical Data and Use Guide, TechFab LLC, Anderson, SC Teng, M., Sotelino, E. D., and Chen, W., 2002, Performance Evaluation of Reinforced Concrete Bridge Columns Wrapped with Fi ber Reinforced Polymers, Journal of Composites for Construction, Vol. 7, No 2, pp. 83-92. Texas DOT, 2000, Chapter 8: Laterally Lo aded Foundations, Geotechnical Manual, Texas Department of Transporta tion, Austin, Texas, p. 15. Thriault, M., and Benmokrane, B., 1998, Effects of FRP Reinforcement Ratio and Concrete Strength on Flexural Behavior of Concrete Beams, Journal of Composites for Construction, Vol. 2, No 1, pp. 7-16.

PAGE 211

193 Thiagarajan, G., 2003, Experimental and An alytical Behavior of Carbon Fiber-Based Rods as Flexural Reinforcement, Journal of Composites for Construction, Vol. 7, No 1, pp. 64-72. Toutanji, H., and Deng Y., 2003, Deflection and Crack Width Prediction of Concrete Beams Reinforced with Glass FRP Rods, Construction and Building Materials, Vol. 17, No 1, pp. 69-74. US Army Corps of Engineers, Naval Facil ities Engineering Command, and Air Force Civil Engineer Support Agency, 2001, Cha pter 2: Piling, Unified Facilities Criteria (UFC) General Criteria for Wa terfront Constructi on, UFC 4-151-10, Washington, DC, p.12. Vijay, P. V., and GangaRao, H. V. S., 2001, Bending Behavior and Deformability of Glass Fiber-Reinforced Polymer Reinforced Concrete Members, ACI Structural Journal, Vol. 98, No 6, pp. 834-842. Wang, H., and Belarbi, A., 2005, Flexural Behavior of Fiber-Reinforced-Concrete Beams Reinforced with FRP Rebars, 7th International Symposium of FiberReinforced Polymer (FRP) Reinforcement fo r Concrete Structur es, Editors: Carol K. Shield, John P. Busel, Stephanie L. Walkup, and Doug D. Gremel, American Concrete Institute, Kansas City, MO, Vol. 2, pp. 895-914. Watson, S., and Park, R., 1994, Simulated Se ismic Load Tests on Reinforced Concrete Columns, Journal of Structural Engi neering, Vol. 120, No 6, pp. 1825-1849. Xiao, Y., and Wu, H., 2000, Compressive Behavior of Concrete Confined by Carbon Fiber Composite Jackets, Journal of Material s in Civil Engineering, Vol. 12, No 2, pp. 139-146. Xiao, Y., and Wu, H., 2003, A Constitutiv e Model for Concrete Confinement with Carbon Fiber Reinforced Plastics, Journa l of Reinforced Plastics and Composites, Vol. 22, No 13, pp. 1187-1201. Yeh, Y. K., Mo, Y. L., and Yang, C. Y., 2002, Seismic Performance of Rectangular Hollow Bridge Columns, Journal of Struct ural Engineering, Vol. 128, No 1, pp. 60-68. Yost, J. R., Goodspeed, C. H., and Schmeckpe per, E. R., 2001, Flexural Performance of Concrete Beams Reinforced with FRP Grids, Journal of Composites for Construction, Vol. 5, No 1, pp. 18-25. Zahn, F. A., Park, R., and Priestley, M. J. N., 1990, Flexural Strength and Ductility of Circular Hollow Reinforced Concrete Columns without Confinement on Inside Face, ACI Structural Journal, Vol. 87, No 2, pp. 156-166.

PAGE 212

194 Zou, P. X. W., 2003, Flexural Behavior and Deformability of Fiber Reinforced Polymer Prestressed Concrete Beams, Journal of Composites for Construction, Vol. 7, No 4, pp. 275-284.

PAGE 213

195 BIOGRAPHICAL SKETCH Antonis Michael was born in Larnaca, Cyprus, on March 22, 1975. He was raised in Avgorou, Cyprus, and graduated from Pancyprian Lycium, Larnaca, in 1993. He attended the Higher Technical Institute, in Nicosia, a nd graduated in 1996 with the diploma of Technician Engineer in Civil E ngineering. He joined the Army of Cyprus after graduation and served in the Army Corps of Engineers. He came to the United States in th e Fall of 1997 and attended Tennessee Technological University. He graduated in 1999 with a Bachelor of Science degree in civil engineering. He moved to Maine and en tered the civil engineer ing graduate program at the University of Maine in 2000 and r eceived his Master of Science in 2002. Antonis joined the University of Florida in the Fall of 2002 and began his studies towards a Doctor of Philosophy degree in civil engineering. Antonis is a candidate for the Doctor of Philosophy degree in civil engineer ing from the University of Florida in Summer, 2006.


Permanent Link: http://ufdc.ufl.edu/UFE0015670/00001

Material Information

Title: Using carbon fiber reinforced polymer grids as confinement reinforcement for concrete
Physical Description: xviii, 195 p. ; ill.
Language: English
Creator: Michael, Antonis Petrou ( Dissertant )
Hamilton, Homer R. ( Thesis advisor )
Consolazio, Gary R. ( Reviewer )
Cook, Ronald A. ( Reviewer )
Boyd, Andrew ( Reviewer )
Sankar, Bhavani ( Reviewer )
Publisher: University of Florida
Place of Publication: Gainesville, Fla.
Publication Date: 2006
Copyright Date: 2006

Subjects

Subjects / Keywords: Civil and Coastal Engineering thesis, Ph.D
Dissertations, Academic -- UF -- Civil and Coastal Engineering

Notes

Abstract: Prestressed concrete piles are widely used in marine environments to support docks, piers, bridges and other waterfront structures. Corrosion of the reinforcement caused by the penetration of the sea salts through the concrete can cause severe deterioration. Corrosion eventually forces replacement of the pile and the structure it supports. Carbon fiber reinforced polymer (CFRP) reinforcement has been researched for a number of years as a potential replacement for steel reinforcement. The significant advantage that CFRP reinforcement holds over steel is that it is highly resistant to deterioration in a harsh marine environment. One of the primary reasons, however, that the CFRP reinforcement has not seen wider use is its lack of ductility. Rather than attempting to improve the CFRP ductility, which is very difficult to do, the primary focus of the research reported in this dissertation was to improve the member flexural ductility by confining the concrete in the compression zone. For that purpose a CFRP grid has been investigated for use as confinement reinforcement in FRP reinforced concrete members. The grid was used in different configurations to confine concrete in the compression zone and improve flexural member ductility. The grid was used to confine concrete cylinders that were tested in axial compression. The results showed a significant increase in the ultimate axial strain of the CFRP confined concrete of approximately 100%. Another application of the grid was the embedment of grid tubes in the compression zone of beams that resulted in an improvement of the ductility factors of approximately 20%. The grid was also used to fully wrap concrete piles that were cast in place or spun cast. The ductility of the piles was improved by as much as 20%. Therefore improvement of the member flexural ductility by confining the concrete in the compression zone is feasible. However the improvement in the ductility of the concrete elements was not enough to compare favorably with the ductility of steel reinforced concrete member. More improvement is required for the FRP reinforced members to be accepted and used to replace steel reinforced members.
Subject: confinement, ductility, FRP, piles
General Note: Title from title page of source document.
General Note: Document formatted into pages; contains 213 pages.
General Note: Includes vita.
Thesis: Thesis (Ph.D.)--University of Florida, 2006.
Bibliography: Includes bibliographical references.
Original Version: Text (Electronic thesis) in PDF format.

Record Information

Source Institution: University of Florida
Holding Location: University of Florida
Rights Management: All rights reserved by the source institution and holding location.
System ID: UFE0015670:00001

Permanent Link: http://ufdc.ufl.edu/UFE0015670/00001

Material Information

Title: Using carbon fiber reinforced polymer grids as confinement reinforcement for concrete
Physical Description: xviii, 195 p. ; ill.
Language: English
Creator: Michael, Antonis Petrou ( Dissertant )
Hamilton, Homer R. ( Thesis advisor )
Consolazio, Gary R. ( Reviewer )
Cook, Ronald A. ( Reviewer )
Boyd, Andrew ( Reviewer )
Sankar, Bhavani ( Reviewer )
Publisher: University of Florida
Place of Publication: Gainesville, Fla.
Publication Date: 2006
Copyright Date: 2006

Subjects

Subjects / Keywords: Civil and Coastal Engineering thesis, Ph.D
Dissertations, Academic -- UF -- Civil and Coastal Engineering

Notes

Abstract: Prestressed concrete piles are widely used in marine environments to support docks, piers, bridges and other waterfront structures. Corrosion of the reinforcement caused by the penetration of the sea salts through the concrete can cause severe deterioration. Corrosion eventually forces replacement of the pile and the structure it supports. Carbon fiber reinforced polymer (CFRP) reinforcement has been researched for a number of years as a potential replacement for steel reinforcement. The significant advantage that CFRP reinforcement holds over steel is that it is highly resistant to deterioration in a harsh marine environment. One of the primary reasons, however, that the CFRP reinforcement has not seen wider use is its lack of ductility. Rather than attempting to improve the CFRP ductility, which is very difficult to do, the primary focus of the research reported in this dissertation was to improve the member flexural ductility by confining the concrete in the compression zone. For that purpose a CFRP grid has been investigated for use as confinement reinforcement in FRP reinforced concrete members. The grid was used in different configurations to confine concrete in the compression zone and improve flexural member ductility. The grid was used to confine concrete cylinders that were tested in axial compression. The results showed a significant increase in the ultimate axial strain of the CFRP confined concrete of approximately 100%. Another application of the grid was the embedment of grid tubes in the compression zone of beams that resulted in an improvement of the ductility factors of approximately 20%. The grid was also used to fully wrap concrete piles that were cast in place or spun cast. The ductility of the piles was improved by as much as 20%. Therefore improvement of the member flexural ductility by confining the concrete in the compression zone is feasible. However the improvement in the ductility of the concrete elements was not enough to compare favorably with the ductility of steel reinforced concrete member. More improvement is required for the FRP reinforced members to be accepted and used to replace steel reinforced members.
Subject: confinement, ductility, FRP, piles
General Note: Title from title page of source document.
General Note: Document formatted into pages; contains 213 pages.
General Note: Includes vita.
Thesis: Thesis (Ph.D.)--University of Florida, 2006.
Bibliography: Includes bibliographical references.
Original Version: Text (Electronic thesis) in PDF format.

Record Information

Source Institution: University of Florida
Holding Location: University of Florida
Rights Management: All rights reserved by the source institution and holding location.
System ID: UFE0015670:00001


This item has the following downloads:


Full Text












USING CARBON FIBER REINFORCED POLYMER GRIDS AS CONFINEMENT
REINFORCEMENT FOR CONCRETE













By

ANTONIS PETROU MICHAEL


A DISSERTATION PRESENTED TO THE GRADUATE SCHOOL
OF THE UNIVERSITY OF FLORIDA IN PARTIAL FULFILLMENT
OF THE REQUIREMENTS FOR THE DEGREE OF
DOCTOR OF PHILOSOPHY

UNIVERSITY OF FLORIDA


2006

































Copyright 2006

by

Antonis Petrou Michael
































This dissertation is dedicated to my family for their love and support all these years that
kept me going and to my new born nephew Theodosis that I hope to meet soon.














ACKNOWLEDGMENTS

I would like to thank my advisor, Dr. H. R. Hamilton III, for giving me the

opportunity to come to the University of Florida. His help, support and encouragement

were invaluable to the completion of my work.

I would like also to thank Mr. Marc Ansley for giving me the opportunity to work

and conduct research with him at FDOT structures laboratory. I will always be grateful to

Marc for the opportunity he gave me. Not only have I gained valuable experience

working with him but also made a great friend.

Thanks are also due to the staff of the FDOT structures center for their help in

completing the experimental work for this dissertation. The contributions of Steve Eudy

who set up and ran the data acquisition systems for all of my tests are greatly appreciated.

Frank Cobb, Tony Johnston, Paul Tighe, and David Allen all offered great assistance in

specimen manufacturing and preparation of testing apparatus.

I Thank TechFab for donating materials (CFRP grid) for my specimens and Accord

Industries for accepting the challenge to built FRP spun cast piles.

Lastly I would like to thank Dr Gary Consolazio, Dr Ronald Cook, Dr Andrew

Boyd, and Dr Bhavani Sankar, for serving on my committee.















TABLE OF CONTENTS

page

A C K N O W L E D G M E N T S ................................................................................................. iv

LIST O F TA B LE S ...... ........................ ................ ................. ... viii

LIST OF FIGURES ................................. ...... ... ................. .x

ABSTRACT ............. .................................................................. xvii

CHAPTER

1 IN TR OD U CTION ......................................................... ... ........ ........... .... ....

2 LITER A TU R E R EV IEW ................................................................. ....................... 5

FRP Flexural Reinforcement .......................... ............... ..................... 5
Carbon FRP Grids.............................. .. ...... ... ................. .6
D urability of FR P R einforcem ent................................................................... ........ 7
FRP Concrete Confinement................................................ ..... ............. ............... 8
Concrete Confinement Failure Criteria and Modeling ................. ..................10
D u ctility F acto rs ................... ... ........................................................ .............. 13
N on-Linear Static (Push-Over) Analysis................................ ....... ............... 19
P plastic H inge L ength............. .......................................................... ..... .... ..... 20
C o n c lu sio n s..................................................... ................ 2 1

3 CARBON GRID CONFINED CYLINDERS ..................................... .................23

In tro d u ctio n ........................................................................................................... 2 3
M manufacturing .................. .................. .................. ........... ............... 24
Experim mental Program .....................................................................26
CFRP Grid Testing .......... .. ..................... .......... ...... ... .............. ... 26
Cylinder Testing D etails............................................ .............................. 29
Cylinder R results and D discussion ........................................... ......................... 30
Em pirical Confinem ent M odel .................................. ..........................................35
C o n c lu sio n s........................................................................................................... 3 9

4 RECTANGULAR CONCRETE SECTION WITH CFRP GRID TUBES...................41

In tro d u ctio n ........................................................................................................... 4 1
Experim mental Program ............. .................................................. ............... 41



v









Specim en C onstruction............................................... ............................. 41
Test Set-Up and Procedure ........... ...... ........ ................... 45
Instrum entation ................................................. ........... ... ........ 47
R results and D discussion .................................... ........................ ............... 49
C ylinder tests ................................................... ..............................49
B e am te sts ..............................................................5 0
F iber M odel A naly sis .............................. ......................... ... ...... .... ...... ...... 52
A naly sis of Strain D ata ........................................................................ .. ..... 55
M measured R stations ........................ .................... .. .. ............. ......... 61
M om ent-C urvature A analysis ........................................................... .....................63
D u utility F a cto rs ................................................................................................... 6 8
C o n c lu sio n s ........................................................................................................... 7 1

5 CAST IN PLACE CONCRETE SECTIONS WITH FRP BARS AND GRID.............73

In tro d u ctio n ............. .. ............. ........................................................................... 7 3
Experim mental Program ......... ......... .......................................... ............... 74
Pile Specim en C construction ........................................ .......................... 74
Test Set-Up and Procedure .................................... ..........77
In stru m en tatio n .............................................................................................. 7 9
M material P properties .................................................... .............................. 80
Results, Observations and Discussion.............. .................................81
Experimental and Theoretical Peak Loads ............. ............. ........................86
M om ent-C urvature A analysis ........................................................... .....................88
D u utility F a cto rs ................................................................................................... 9 2
C o n c lu sio n s........................................................................................................... 9 5

6 SPUN CAST CONCRETE PILES WITH CFRP GRID AND BARS .........................97

In tro d u ctio n ............... ..... .... .. ................. ........................................................ 9 7
Specimen Design and Construction......................... .................98
D e sig n ............. ................. .................................................................... 9 8
M manufacturing ............................................ .. .. ............. ......... 99
Shear R einforcem ent .......................................................... ............... 107
T est S et-U p ...............................................................10 8
T e st P ro c e d u re ................................................................. .................................1 1 0
Instrumentation ............... ............... ...... ...............111
Material Properties ................ .. ...... ..................114
Results and Observations ......................... ................ 115
Strain Data Analysis ................... ........................ ..... ...............121
Experimental and Fiber Model Moment Capacity ...................................... 127
Moment-Curvature Analysis ..............................................130
D u utility F actors ...............................................................132
C o n c lu sio n s......................................................................................................... 1 3 4

7 SYSTEM BEHAVIOR OF PILES CONSTRUCTED WITH CFRP
C O M P O S IT E S ................................................................................................... 13 6









Introduction ....................................................................................... .................... 136
Static N on-Linear (Push Over) Analysis ........... ............................ .................. 137
Pile Bent Model Description ................ ......... ....................138
R results for L oad C ase 1 .............................................. ............................. 14 1
Ductility of Pile Bent Systems ...... ....................................... ...................145
R results for L oad C ase 2............................................... ............................ 147
Static Non Linear Analysis of Prototype Pile Bents ........................................149
C o n c lu sio n s.......................................................................................................... 1 5 7

8 PROPOSED CONCRETE MODEL........... ............. ............................ 159

In tro d u ctio n ............. ........... .................. ..............................................1 5 9
Unconfined Concrete Model ............ .............. ............................ 159
C confined C concrete M odel......... ................. ................... ................. ............... 171
Discussion ............... ................................178
C o n c lu sio n s.......................................................................................................... 1 8 0

9 CONCLUDING REMARKS AND FUTURE REASERCH ............... ..................181

D issertation Su m m ary ..................................................................... .................... 18 1
Sum m ary of Conclusions............................................................. ................. 182
F u tu re R e se a rch ................................................................................................... 1 8 5

L IST O F R E FE R E N C E S ......................................................................... ................... 187

BIOGRAPH ICAL SKETCH .............................................................. ............... 195
















LIST OF TABLES

Table page

3-1. C cylinder test m atrix ............................................ ................... .. ......25

3-2. Results for CFRP grid specimens....... ...............................................28

3 -3 C y lin d er resu lts .................................................................. 32

3-4. Area under stress-strain curve ............................................................................. 34

4-1. T est m atrix for tube beam s .............................................................. .....................42

4-2. Experim mental results from cylinders tests........................................ ............... 50

4-3. Experimentally calculated top compressive strains............................... ...............57

4-4. Steel strains calculated using experimental data ................................................59

4-5. R stations m measured by tilt m eters ........................................ ......................... 61

4-6. Rotations calculated based on the displacement profiles .......................................62

5-1. Specimen details for cast in place pile specimens.............. ..... .................74

5-2. R results from cylinders tests...................... ................ ............... ............... 80

5-3. FRP reinforcement material properties ........................... ............. ............... 81

5-4. Experimental and theoretical moment capacities.......................... .............87

5-5. Experim ental displacem ent ductility factors ................................... .................93

5-6. Experim mental curvature ductility factors ........................................ .....................94

5-7. Theoretical curvature ductility factors.... ............................ .............94

6-1. Spun cast specimen details .............. ......... ......100

T able 6-2. C ylinders test results............................................. ................. ............... 115

6-3. FRP reinforcement material properties..................................................... .......... 115



viii









6-4. Experimental and theoretical moment capacities.......................... .....................130

6-5. Experim ental displacem ent ductility factors .................................... ............... 133

6-6. Experim mental curvature ductility factors ...................................... ............... 134

7-1. Plastic hinge length of various types of piles ..... .......... .............................139

7-2. Ductility factors for pile bents (load case 1)...................................... ............... 146

7-3. Section details for prototype FRP reinforced piles.............................. ...............150

7-4. Reinforcement details for prototype FRP reinforced piles .........................151

7-5. Ductility factors for prototype pile bents....................................... ............... 155

8-1. Parameters used to model behavior of unconfined concrete cylinder in
co m p re ssio n ............................ ....................................................... ............... 17 1
















LIST OF FIGURES

Figure page

2-1. Mohr-coulomb failure criterion ................. ......... .... ............... 11

2-2. Schematic for ductility factor component definitions .............................................15

2-3. Schematic for energy method ductility factor ......... ............. .. ............. ....16

2-4. Schematic for deformation method ductility factor ..............................................18

3-1. C F R P grid round tubes ...................................................................... ...................25

3-2. CFRP grid cylinder casting in the field ........................................... ............... 25

3-3. CFRP grid ............. ... ........................ ........ ............ .......26

3-4. CFRP strand tests................ ................................. 27

3-5. Stress-strain curves of CFRP grid strands............................. ................28

3-6. Typical load head movement rate for control cylinders ......................... ..........29

3-7. Typical load rate for control cylinders ............................................ ............... 30

3-8. CFRP grid cylinder test set-up............... .......................................... ............... 30

3-9. Cylinders after testing .......................... .......................................... ............... 31

3-10. Stress-strain curves for control cylinders ...................................... ............... 32

3-11. Stress-strain curves for grid cylinders 1, 2 and 3 ............................................. 33

3-12. Stress-strain curves for grid cylinders 4, 5 and 6 .............................................. 33

3-13. Stress-strain curves for typical control and grid cylinders ....................................34

3-14 C ylindrical pressure vessel ............................................................ .....................36

3-15. M modified Hognestad stress-strain curve ....................................... ............... 38

3-16. Experimental and empirical model stress-strain curves .......................................39









4-1. Longitudinal (top) and cross-sectional (bottom) views of control beam....................42

4-2. Longitudinal (top) and cross-sectional (bottom) views of grid tube beam................43

4-3. Formation of CFRP grid tubes ......................... ...................... 44

4-4. C control beam ................................................................... 44

4-5. C concrete placing (tube beam )............................................................ ......... ......45

4-6. C concrete cylinder casting ........................................ .............................................46

4-7. T est set-up for both beam s............................................................... .....................46

4-8. Strain gage arrangement (side view of center portion of the beam).........................48

4-9. Strain gage arrangement (top view of center portion of the beam)..........................48

4-10. Test set-up for both beam s before testing...................................... ............... 49

4-11. Load-displacement curves for control and tube beams ................. ............ .....50

4-12. Compression zones for both beams after testing ................................................ 51

4-13. Tube beam compression zone after testing........... ...........................52

4-14. Tube beam cross-sectional fiber m odel ........................................ ............... 53

4-15. Load-strain curves for strain gages at opposing locations (control beam) ..............55

4-16. Load-strain curves for control beam .................................... ......................... 56

4-17. Compressive strain profile for control beam .................................... .................57

4-18. A ssum ed strain distribution .......... ............................................................ ... ... 58

4-19. Transverse expansive strains for control beam............................................. 60

4-20. Measured rotations at increasing loads (control beam).......................... .........63

4-21. Measured rotations at increasing loads (tube beam) ................... ... .............63

4-22. Displacement curve and fitted polynomial line for control beam at 43.7 kips.........64

4-23. Experimental and theoretical M-D curves for control beam.............. .......... 67

4-24. Experimental and theoretical M-D curves for tube beam........................................68

4-25. Experimental M -D curves for both beams .................................... ............... 69









4-26. Curvature ductility factor for control beam.................. ............ ................70

5-1. Longitudinal view of specim en 2 ........................................ .......................... 74

5-2 C ro ss-section al v iew ............. .......................................................... ........ .............. 7 5

5-3. Cross-sectional view at mid-span........................................................75

5-4. Longitudinal view of specim en 3 ........................................... ......... ............... 76

5-5. Placem ent of concrete (specim ens 2, 3 and 4)................................. ............... 76

5-6. Placem ent of concrete (specim en 1)........................................ ....................... 77

5-7. Schematic of test set up for specimen 1 ......... ........... ......................... 77

5-8. Schematic of test set up for specimen 2 ......... ... ........... ....... ........... ............... 78

5-9. Schematic of test set up for specimen 3 ............................................ ................... 78

5-10. Schem atic of test set up for specimen 4 ....................................... ............... 79

5-11. Load-displacement curves for specimens 1 and 2 (mid-span) ..............................82

5-12. Crushed cover concrete (specim en 2)...................................... ...... ............... 82

5-13. Specimen 2 after the end of the test............. ............................... 82

5-14. Ruptured CFRP grid and GFRP reinforcing bar (specimen 2).................................83

5-15. Specim en 3 after testing ........................................ .............................................84

5-16 Specim en 4 after testing ........................................ .............................................85

5-17. Moment-displacement curves for specimens 3 and 4............................................86

5-18. Self weight distribution for cast in place piles .......................... ................... 87

5-19. Illustration of the numerical differential method................................. ..............89

5-20. M oment-curvature curves for specimen 1 ..................................... .................90

5-21. Moment-curvature curves for specimen 2.................................................... 90

5-22. M om ent-curvature curves for specimen 3 ..................................... .................91

5-23. Moment-curvature curves for specimen 4.................................................... 91

5-24. Calculation of displacement ductility factors for specimens 1..............................93









5-25. Calculation of curvature ductility factors for specimens 1 ....................................93

6-1. Elevation of midspan section of SCG piles................. ............................... 100

6-2. Elevation of midspan section of SCC piles ................................................. .......... 101

6-3. Cross sectional view A-A ........._...._ .......... ............. 101

6-4. Attachment of carbon reinforcing bars to steel rings ............................................102

6-5. Placem ent of CFRP grid ................ ......... ................... ................... ............... 103

6-6. Reinforcem ent cage inside the m old ............................................. ............... 103

6-7. Concrete casting ......................... ......... .. ......... ...... ........ .. 104

6-8. Concrete at the tip of the pile.......... .. .................. ................. 104

6-9. Sealing the m old ............. .......... ............................... .......... .. ............ 105

6-10. Placement of mold onto the spinning platform ........................ ..................106

6-11. Mold spinning on the spinning platform ................ ...... ...................106

6 -12 P ile rele a se ............. ......... ... ... .............. .................. ................ 10 6

6-13. Shear reinforcement for specimens SCC1 and SCG1 ........................................108

6-14. Shear reinforcement for specimens SCC2 and SCG2 .........................................108

6-15. Shear reinforcement for specimens SCC3 and SCG3 ........................................108

6-16. Test set-up for specimens SCC1, SCG1, SCC2 and SCG2 ....................................109

6-17. Test set-up for specimens SCC3 and SCG3 ..........................................................109

6-18. Steel saddle at north support ......................................................... ..................... 110

6-19. Strain gage arrangement for specimens SCC2 and SCG2 (side view of center
portion of the pile) ....... .. .. ........................... .. ............................ .. 111

6-20. Strain gage arrangement for specimens SCC2 and SCG2 (top view of center
portion of the pile) .................. ...................................... .. ........ .. 112

6-21. Strain gage arrangement for specimens SCC2 and SCG2...................................112

6-22. Strain gage arrangement for specimens SCC3 and SCG3 (side view of center
p portion of th e p ile) ........ .. .. ........ .. .. .. .. .... .. ...... .................................. .. 1 13









6-23. Strain gage arrangement for specimens SCC3 and SCG3 (top view of center
p o rtio n o f th e p ile) ............ ...... .. .. .. ...... .... .... .. .................... .. .......... .. .. 1 13

6-24. Strain gage arrangement for specimens SCC3 and SCG3 .....................................114

6-25. Load-displacement curves for piles SCC1, SCC2 and SCC3 ..............................116

6-26. Load-displacement curves for piles SCG1 and SCG3 ..........................................117

6-27. Load-displacement curves for piles SCC1 and SCG1 ........................................118

6-28. P ile specim ens after testing ......................................................... ..................... 118

6-29. Pile specim ens after testing ......................................................... ............... 119

6-30. Pile specim ens after testing .............................................................................. 120

6-31. Top cover concrete (pile SCG3).................................................... 120

6-32. Load-strain relationship for specimens SCC1, SCC2 and SCC3 .........................121

6-33. Load-strain relationship for specimens SCG1 and SCG3 ......................................122

6-34. Strains at opposing sides for specimen SCC3 ................................ ............... 122

6-35. Compression zone load-strain curves for specimens SCC1 and SCG1.................. 123

6-36. Compression zone load-strain curves for specimen SCC2...................................124

6-37. Compression zone load-strain curves for specimens SCC3 and SCG3................124

6-38. Strain profile of compression zone for pile SCC3 ....................... ..................... 125

6-39. Strain profile of compression zone for pile SCG3 ...................................... 125

6-40. Typical compression zone strain profile for specimens SCC3 and SCG3 ............126

6-41. Transverse expansive strains for specimens SCC1 and SCG1.............................127

6-42. Spun cast cross-sectional fiber m odel ........................................ .....................128

6-43. Self weight distribution of spun cast piles.....................................129

6-44. Experim ental M -0 curves for piles SCC3 ......................................... .................131

6-45. Experim ental M -D curves for piles SCG3 ........................................ ..................132

6-46. Calculation of displacement ductility factors for specimen SCC3.........................133

6-47. Calculation of curvature ductility factors for specimen SCC3.............................133









7-1. Typical pile bent system ...................................................................... 137

7-2. Typical model pile bent system .......................... ......... .. .. ............ ... 138

7-3. Visual analysis structural model....................................... ................... 140

7-4. Visual analysis model pile bent system (load case 2) ........................................... 141

7-5. Load-displacement curves of prestressed pile bents and pile bents using cast in
place piles reinforced with GFRP bars and CFRP grid..........................................142

7-6. Load-displacement curves of prestressed pile bents and pile bents using cast in
place piles reinforced with CFRP bars and grid............................................143

7-7. Load-displacement curves of prestressed pile bents and pile bents using spun cast
piles reinforced with CFRP bars and grid ............................. .. .......... ........ 144

7-8. Load-displacement curves of the prestressed pile bent with minor corrosion .........148

7-9. Typical pile section schematic for prototype piles ....... ... ................................... 150

7-10. Pile bent load-displacement curves for CSPP, CPCP1 and CPGP1 piles .............152

7-11. Pile bent load-displacement curves for CSPP, SCCP1 and SCGP1 piles............ 152

7-12. Pile bent load-displacement curves for CSPP, PCPCP1 and PCPGP1 piles..........153

7-13. Pile bent load-displacement curves for CSPP, PCPCP2 and PCPCP3 piles..........153

7-14. Pile bent load-displacement curves for CSPP, SCPCP1 and SCPGP1 piles..........153

7-15. Pile bent load-displacement curves for CSPP, SCPCP2 and SCPGP3 piles..........154

8-1. C racked concrete cylinder ......... ..... ............ ................................. ..................... 160

8-2. C concrete cylinder slice .................................................. ............................... 161

8-3. Distribution of acoustic emissions for mortar beams .....................................163

8-4. Crack profile of concrete cylinder (longitudinal cross-section) .............................164

8-5. C concrete cylinder m icro column ns ......... ................. ................... ..................... 165

8-6. Micro column assumed cross sectional shape ........ .........................................166

8-7. Determining the length of the side of the trapezoid using trigonometry................ 166

8-8. Cylinder set up for total strain determination........................ ............... 168









8-9. Sensitivity of model to the number of micro columns ................................ 170

8-10. Experimental and calculated stress-strain curves for unconfined control
cy lin d ers ................................ ............ ........................................ 17 1

8-11. Restraint of micro columns by CFRP grid strand.............................................172

8-12. Geometry of micro column restrained by the CFRP grid.............. ............... 173

8-13. Lateral stiffness of CFRP grid ring....................... .. ... ...............174

8-14. Stress-strain curves for grid diameter of 5.25 in .................................................176

8-15. Stress-strain curves for grid diameter of 5.5 in. ............. ........................ ......... 177

8-16. Stress-strain curves for different amounts of CFRP grid ......................................177














Abstract of Dissertation Presented to the Graduate School
of the University of Florida in Partial Fulfillment of the
Requirements for the Degree of Doctor of Philosophy


USING CARBON FIBER REINFORCED POLYMER GRIDS AS CONFINEMENT
REINFORCEMENT FOR CONCRETE

By

Antonis Petrou Michael

August 2006

Chair: Homer R. Hamilton III
Major Department: Civil and Coastal Engineering

Prestressed concrete piles are widely used in marine environments to support

docks, piers, bridges and other waterfront structures. Corrosion of the reinforcement

caused by the penetration of the sea salts through the concrete can cause severe

deterioration. Corrosion eventually forces replacement of the pile and the structure it

supports.

Carbon fiber reinforced polymer (CFRP) reinforcement has been researched for a

number of years as a potential replacement for steel reinforcement. The significant

advantage that CFRP reinforcement holds over steel is that it is highly resistant to

deterioration in a harsh marine environment. One of the primary reasons, however, that

the CFRP reinforcement has not seen wider use is its lack of ductility.

Rather than attempting to improve the CFRP ductility, which is very difficult to do,

the primary focus of the research reported in this dissertation was to improve the member

flexural ductility by confining the concrete in the compression zone. For that purpose a









CFRP grid has been investigated for use as confinement reinforcement in FRP reinforced

concrete members.

The grid was used in different configurations to confine concrete in the

compression zone and improve flexural member ductility. The grid was used to confine

concrete cylinders that were tested in axial compression. The results showed a significant

increase in the ultimate axial strain of the CFRP confined concrete of approximately

100%. Another application of the grid was the embedment of grid tubes in the

compression zone of beams that resulted in an improvement of the ductility factors of

approximately 20%. The grid was also used to fully wrap concrete piles that were cast in

place or spun cast. The ductility of the piles was improved by as much as 20%.

Therefore improvement of the member flexural ductility by confining the concrete

in the compression zone is feasible. However the improvement in the ductility of the

concrete elements was not enough to compare favorably with the ductility of steel

reinforced concrete member. More improvement is required for the FRP reinforced

members to be accepted and used to replace steel reinforced members.


xviii














CHAPTER 1
INTRODUCTION

Prestressed concrete piles are widely used in marine environments to support

docks, piers, bridges and other waterfront structures. Corrosion of the reinforcement

caused by the penetration of the sea salts through the concrete can cause severe

deterioration. Corrosion of the steel reinforcement reduces the structural capacity of the

concrete pile rendering it, in extreme cases, unable to perform the function for which it

was designed. Furthermore, corrective or protective measures that can slow corrosion

rates have to be adopted which results in higher maintenance costs. Corrosion will

eventually force replacement of the pile and the structure it supports. Therefore, the

service life of the whole structure is dependent upon the service life of the piles

supporting it. Even if repair and protective measures are employed to extend the life of

the structure, they are costly, time consuming and rarely add significantly to the service

life.

Carbon fiber reinforced polymer (CFRP) reinforcement has been researched for a

number of years as a potential replacement for steel reinforcement. CFRP reinforcement

is formed by bundling carbon fibers into a round shape and saturating with an appropriate

resin. These bars can be fabricated to have strength and stiffness comparable to that of

steel. The significant advantage that CFRP reinforcement holds over steel is that it is

highly resistant to deterioration in a harsh marine environment. One of the primary

reasons, however, that the CFRP reinforcement has not seen wider use is its lack of

ductility. CFRP bars when loaded in tension, exhibit linear stress-strain behavior up to









rupture. There is no yield point and associated plateau to provide a ductile response when

used as tensile reinforcement in concrete. There have been attempts to improve the

ductility of CFRP with little or no success.

Rather than attempting to improve the CFRP ductility, the primary focus of the

research reported in this dissertation was to improve the member flexural ductility by

confining the concrete in the compression zone.

One of the challenges was locating CFRP that could be used to confine concrete.

In steel reinforced concrete, smaller steel bars are usually bent to form hoops to enclose

the concrete and provide confinement. CFRP loses strength when bent sharply so a

unique approach using a prefabricated CFRP grid was used. The grid, unlike FRP wraps,

can be embedded into concrete prior to casting because it has open space through which

fresh concrete can flow. Light carbon grid mesh occupies approximately 31% of the grid

area, leaving a 69% open area through which concrete can pass relatively easily. The

grid is easily formed into a tubular shape, which avoids sharp bends and makes efficient

use of the tensile capacity of the grid.

The research objective is to develop and evaluate the use of CFRP grid to confine

concrete. To accomplish this objective, a number of cross-sectional shapes were

constructed and tested to evaluate the use of CFRP grid for confinement. One of these

was a full scale concrete tapered pile using the spun-cast construction method. These

piles were hollow and circular in cross-section and were reinforced with CFRP composite

grid and bars. Confinement models available in the literature were investigated for use in

predicting behavior observed in the structural tests. The selected model was calibrated

using concrete cylinder tests. The confinement model was also used to calculate the









member behavior. In addition, system behavior was investigated analytically using the

test results and confinement model. Finally, an entirely new approach for modeling

confinement was developed.

This dissertation is organized into nine chapters. In these chapters different

methods by which the CFRP grid can be used to confine concrete are presented. The

methods are presented along with the experimental work and results for each method. A

model based on a new approach that predicts the behavior of unconfined and confined

concrete is also presented.

Chapter 2 contains a summary of the literature review. Several topics that relate to

this dissertation were explored to find any material that could be helpful in the process of

completing the necessary research.

In chapter 3 the experimental testing and experimental results from concrete

cylinders that were confined using the CFRP grid are presented. The cylinders were

tested in axial compression.

In chapter 4 the construction and testing of two reinforced concrete beams using

CFRP grid tubes in the compression zone to confine concrete are described. The

experimental findings from the flexural tests are also presented.

In chapter 5 and 6 the construction and testing details of FRP reinforced concrete

piles that use the CFRP grid as confinement reinforcement are presented. The

experimental results from the tests are also presented.

In chapter 7 a static non-linear analysis of pile bents using both prestressing steel

and FRP reinforced piles is discussed. A description of the static non-linear analysis and

the results are presented.






4


In chapter 8 a new concrete confinement model is presented. The results from the

model are compared to the available experimental results.

Chapter 9 provides a summary of the findings presented in this dissertation.














CHAPTER 2
LITERATURE REVIEW

Several areas were investigated in the literature review. One area was that of the

ductility of carbon fiber-reinforced polymer (CFRP) reinforcement and what has been

done to measure as well as improve it. Another area was to determine the extent to which

CFRP grid has been investigated for use in confinement of concrete. Yet another was to

identify and evaluate the existing confinement models for use in analytically predicting

member and system behavior. Finally, some review was done on ductility computation

and measurement.

FRP Flexural Reinforcement

A number of researchers have indicated that the lack of ductile behavior exhibited

by FRP reinforced members is a limiting factor to their use. Rooney and Taylor (2004),

Toutanji and Deng (2003), Grace et al. (1998), Theriault and Benmokrane (1998) and

Chaallal and Benmokrane (1996) found that the post cracking beam behavior was linear

to failure in concrete beams reinforced with glass FRP rods. El-Salakawy et al. (2003)

tested concrete deck slabs reinforced with both carbon and glass FRP bars. The carbon

FRP bars were placed on the bottom in the main (transverse) direction while on top of the

main direction as well as in both top and bottom of the secondary (longitudinal) direction

glass FRP bars were used. The slab had a linear post cracking behavior until failure

occurred. Thiagarajan (2003) compared the moment curvature behavior of concrete

beams reinforced with carbon rods and mild steel. Although the steel reinforced beams

were found to be significantly more ductile, it was noted that the carbon FRP reinforced









beams exhibited some ductility, which was attributed to concrete crushing in

compression. Zou (2003) and Abdelrahman and Rizkalla (1999) tested prestressed

concrete beams reinforced with carbon FRP bars. The load deflection curves of the beams

were linear to failure. Some beams tested by Zou failed by rupture of the prestressing

CFRP bars and some by crushing concrete.

Carbon FRP Grids

Heavy carbon grids with thicknesses of half an inch or more have been produced

and have been used as primary reinforcement in concrete slabs or bridge decks in an

effort to address the problem of corrosion due to the use of deicing salts during the winter

months. Rahman et al. (2000) used these carbon grids as reinforcement in a section of

concrete deck manufactured in a laboratory. The deck was supported on Steel I beams.

They reported that the behavior of the deck was satisfactory and the carbon grid could

replace steel reinforcement in bridge decks. Yost et al. (2001) used the same type of

heavy carbon grid as reinforcement in concrete beams. The use of the grid as flexural

reinforcement resulted in brittle failure since the carbon has no yield point and is linear

elastic to failure.

Light carbon grids (thickness 3 to 4 hundredths of an inch) are also available and

are used primarily for crack control in concrete structures. Harries and Gassman (2003)

conducted tests on reinforced concrete basin knockout panels that employed a light

carbon grid to control cracking. The grid reduced cracking of the panel. Shao et al. (2003)

used the same light carbon grid to control plastic shrinkage cracking in concrete. They

concluded that the plastic shrinkage crack reduction was in the range of 50% to 65%.









Durability of FRP Reinforcement

Glass fiber reinforced polymer (GFRP) materials are sensitive to salt water. If salt

water comes to contact with the glass fibers it will attack them and can destroy them in a

short period of time. It is not unusual for a GFRP bar to lose approximately 50% of its

strength once the fibers are exposed. Even though GFRP reinforcing bars have an epoxy

coating that provides protection against such attack, cracking of the epoxy protective

layer can allow saltwater to penetrate and destroy the fibers. It is therefore dangerous to

use GFRP bars for such applications. On the other hand carbon fibers are immune to

attack by saltwater and therefore well suited for marine structures. Even in the case of

cracking in the matrix material of carbon fiber reinforced polymer (CFRP) bars their

strength will not be compromised. Micelli and Nanni (2004) tested both GFRP and CFRP

rods for durability in various environments and reported problems with GFRP rods but no

problems were unveiled for the CFRP rods. Jansons et al. (2002) exposed carbon FRP

composites to salt water at elevated temperatures with no noticeable changes to the

strength and modulus of the composites. Myers et al. (2002) tested both glass and carbon

FRP rods in tension after alkali exposure or a combined effect of Ultra Violet (UV)

radiation, high temperature cycles and high moisture (environmental cycles). Although

the environmental cycles did not have any effect on the tensile strength of neither the

glass nor the carbon rods, the alkali exposure had a significant impact on one of the glass

rod types. A reduction in the tensile strength of 41% was observed after alkali exposure

for 42 days at a temperature of 60 C. No significant loss of tensile strength was reported

for the carbon rods. Carbon fibers are not influenced by alkaline environments even when

in direct contact, while glass fibers will deteriorate once they come into contact with such

an environment (Malvar 1998).









FRP Concrete Confinement

Confinement of concrete is not a new concept but rather has been practiced for

many years. Confinement of concrete can be achieved by wrapping the concrete,

therefore providing resistance in the hoop direction of a concrete element in compression.

A concrete element loaded in compression in addition to the displacement in the direction

of the applied compression load it also displaces in the hoop direction (the direction that

is perpendicular to the applied load) due to the Poisson effect. If the concrete is

unconfined the expansion developed in the hoop direction will eventually result to the

failure of the concrete element. On the other hand, if a concrete element is confined, a

confining pressure develops which restrains the hoop direction expansion and therefore

prevents the failure of the concrete element until a different mode of failure occurs. This

has two primary effects on the behavior of the concrete element. First it increases the load

at which the concrete element fails and secondly increases the amount of displacement

required to produce failure. As a consequence of the second effect the concrete element

can dissipate higher amounts of energy, which makes it more ductile, compared with the

unconfined concrete element.

Abdel-Fattah and Ahmad (1989) tested 3 x 9 in. (the unsupported length was 6 in.)

concrete cylindrical specimens confined by steel rings spaced at 0.5 in. with the cylinders

exhibiting highly ductile behavior. Mei et al. (2001) tested 4 x 8 in. cylinders with a steel

sleeve on the outside. Axial compressive load was applied only to the concrete core. The

improvement to the concrete properties was apparent with concrete properties further

improving with an increase to the thickness of the steel sleeve.

When fiber reinforced polymer (FRP) materials became widely available in the

civil sector, they started replacing steel as external confinement reinforcement. One of the









primary applications of FRP materials is retrofit of concrete elements, primarily columns,

to improve their ductility. This is done mainly in seismic regions where concrete

structures experience large deformations. Column wrapping improves the strength and

ductility of the concrete and improves its performance under earthquake loads.

Xiao and Wu (2000 and 2003) wrapped concrete cylinders using various materials

and methods. Some were wrapped with carbon fiber fabrics, while others were wrapped

with glass fiber fabrics. They also wrapped cylinders using a machine that tightly wound

carbon fibers around the cylinders. The results showed a significant improvement both in

strength and ductility.

Lam and Teng (2004), Li et al. (2003) and Harries and Kharel (2002) wrapped

cylinders with carbon fabrics with similar results as Xiao and Wu. Harries and Kharel

(2002) had some of their cylinders wrapped with glass fabrics. Li and Hadi (2003) and

Campione and Miraglia (2003) tested round concrete columns wrapped with either glass

or carbon fiber fabric sheets in a polymer matrix. In doing so they improved the ductility

of the columns. Campione and Miraglia (2003) also wrapped, in the same manner, square

columns and square columns with round covers with the same results. It was found that

the round shape is the most effective shape for confinement while the square with sharp

corners the least effective of the three. Teng et al. (2002) wrapped bridge columns in the

field using FRP wraps. Laboratory specimens were also tested with the columns

exhibiting a ductile behavior. Shahawy et al. (2000) tested standard concrete cylinders

wrapped with carbon fiber fabrics in an epoxy matrix. The results varied depending on

the number of carbon layers applied. For an unconfined concrete strength of 41.4 MPa

the confined strength of cylinders was increased to 70 MPa for the 1-layer wrap and 110









MPa for the 4-layer wrap. The ultimate strain for the 1-layer wrap was 0.007 and for the

4-layer wrap 0.016.

Pantelides et al. (1999) wrapped a bridge pier with carbon fiber composites and

tested it in situ. An unwrapped pier was also tested. The pier wrapped with carbon was

able to accommodate movements two times larger than the unwrapped pier.

Prefabricated FRP tubes can be filled with concrete and serve at the same time as

formwork, flexural reinforcement and confinement reinforcement. Davol et al. (2001)

tested prefabricated round shells filled with concrete in flexure with satisfactory results.

The concrete filled FRP shells exhibited a ductile behavior. Mirmiran et al. (1998)

manufactured round and square FRP tubes that were filled with concrete and then tested

in compression. The round tubes increased the peak axial stress by as much as 2.5 times

the peak axial stress of unconfined concrete and reached axial strains 12 times higher

than the axial strain at peak stress of unconfined concrete.

Concrete Confinement Failure Criteria and Modeling

In order to determine the failure stress of confined concrete a failure criterion is

necessary. Researchers have used the Mohr-Coulomb failure criterion due to its

simplicity and relative accuracy (Li et al. 2003; Mei et al. 2001; Gandappa et al. 2001).

This failure criterion is based on the well-known Mohr's circle. Once concrete is loaded

in axial compression a stress state consisting of normal stresses develops. Concrete is

assumed to fail when its compressive capacity is reached. The shear stresses are due to

the Poisson effect that causes tension in concrete in the hoop direction which also causes

vertical cracking. When confinement is present the concrete is in a triaxial stress state

that counteracts the tension stress in the hoop direction caused by the Poisson effect

delaying failure. This is reflected in the higher axial compressive load required to









produce failure (see Fig. 2-1). The two lines intersecting at point O represent the Mohr-

Coulomb failure envelope. The points of tangency between the two circles and the failure

lines are the points at which the combination of the axial compressive and Poisson

tension stress state for the unconfined and the triaxial compression stress state for the

confined concrete produces failure.














Unconfined Confined
Concrete Concrete
f, unconfined i, r ,9i l
f confinement pressure
f.c confined I, ,rgl

Figure 2-1. Mohr-coulomb failure criterion

Assuming the concrete is in triaxial compression due to the presence of the

confining pressure, the confined compression strength of concrete in terms of the

confining pressure and the unconfined strength is expressed as follows:

fcc = f + k f, (2-1)

where fc is the compression strength of confined concrete,fc is the compression strength

of unconfined concrete, k is a constant also referred to as the effectiveness coefficient and

f is the confining pressure.









One of the shortcomings of the Mohr-Coulomb failure criterion is that it will

predict the failure load as being the peak load which is usually accurate when concrete is

highly confined but it will not work for low confinement concrete because most of the

ductility of such concrete is produced after reaching the peak strength. Highly confined

concrete is usually produced when relatively high amounts of FRP confinement

reinforcement are used.

Other failure criteria have been used to determine when failure of confined

concrete occurs. Richart's failure criterion is similar to the Mohr-Coulomb failure

criterion as expressed in Equation 2-1 with k equal to 4.1 (Xiao and Wu 2003; Li and

Hadi 2003; Xiao and Wu 2000; Samaan et al. 1998). Tsai-Wu failure criterion is a failure

criterion that focuses on the FRP laminate failure and takes into account the interaction of

the axial compressive and tensile hoop stresses that produces an earlier failure of the FRP

encasement compared with ignoring the axial compressive stress and accounting only for

the hoop tensile stress (Mandal et al. 2005; Cho et al. 2005; Barbero 1998). The Tsai-Hill

failure criterion is similar to the Tsai -Wu failure criterion with the difference that the

stress values used can only be tensile or compressive but not both (Cho et al. 2005;

Barbero 1998). For example if pure tension stress state is assumed in all directions the

Tsai-Hill criterion yields the same results as the Tsai-Wu criterion.

Confinement models to predict the maximum stress or the whole stress-strain curve

of confined concrete have been developed (Campione and Miraglia 2003; Li and Hadi

2003; Li et al. 2003; Xiao and Wu 2000, 2003; Fam and Rizkalla 2001). Most models

that describe the whole stress-strain curve of FRP confined concrete employ a bilinear

curve (second portion of the curve ascending) that in most cases works well. Most









models have been refined using data from concrete that is confined by FRP composite

materials that their amount and properties produce such behavior. Cases with lower grade

material or smaller amounts of FRP composites are scarce and have not been used to

demonstrate the applicability of the available models.

Ductility Factors

Two ductility factors are usually used to measure the ductility of structural

components. The displacement ductility factor (uj) is defined as the ratio of the ultimate

displacement (6,) over the displacement at first yield (6y).


a (4-1)


The second factor is the curvature ductility factor (up) defined as the ratio of the

ultimate curvature (0,) over the curvature at first yield (0y).


/ 0A Y (4-2)


The definition of ultimate and yield displacements or curvatures is simple when the

behavior is elasto-plastic. Definition of these parameters is more complicated when the

behavior is not elasto-plastic. Usually the behavior of reinforced concrete is not perfectly

elasto-plastic. Therefore, the need for a consistent definition of the ultimate and yield

displacements or curvatures was realized. Researchers have proposed definitions of

ultimate and yield displacement and curvature as well as instructions on how to calculate

them.

The ultimate displacement (or curvature) has been defined as the displacement (or

curvature) at which the lateral load in the descending portion of the load-displacement

curve is not less than 80% of the maximum load, P,, (Priestley and Park 1987; Zahn, et









al. 1990; Sheikh and Khoury 1993; Yeh et al. 2002). Park and Pauley (1975(b)) have

argued that the available ultimate deformation is not necessarily the deformation that

corresponds to the maximum load capacity. They further said that "when survival without

collapse is the criterion, it is too conservative to define ultimate deformation as the

deformation corresponding to the maximum load-carrying capacity. It would seem

reasonable to recognize at least some of this deformation capacity after the maximum

load has been reached and to define and to define the available ultimate deformation as

that deformation when the load-carrying capacity has reduced by some arbitrary amount

after maximum load. For example, a 10 or 20% reduction in maximum load-carrying

capacity could be tolerated in many cases, but the exact amount would depend on the

particular case".

The yield displacement is defined as the displacement at the intersection of the

horizontal line representing the ideal lateral capacity, P,, (nominal capacity using the ACI

318 approach and a reduction factor of unity) and the straight line that passes through

zero and the point in the load-displacement curve at 75% of the ideal lateral capacity

(Priestley and Park 1987; Zahn et al. 1990; Sheikh and Khoury 1993). The definitions of

yield and ultimate displacements are depicted in Fig. 2-2.

Because FRP reinforced concrete exhibit different behavior than steel reinforced

concrete due to the absence of a yield point of the FRP reinforcement researchers have

attempted to produce ductility factors also called deformability factors that apply to FRP

reinforced concrete. There is the notion that FRP reinforced concrete structures have to

be treated in a different way in terms of ductility than what traditionally has been done

with steel reinforcement. Two basic methods have been proposed.









The first method is an energy based method in which the ratio of total energy of the

structural system to the elastic energy is used to calculate an energy ductility factor (see

Fig 2-3). This was first introduced by Jeong (1994) that proposed the following

expression for determining the energy ductility factor (uE):


PE = 0.5 Etot +1 (2-2)
Eela )

where Etot is the total energy under the load-displacement curve and Eea is the portion of

the total energy which is considered elastic.

PI

Pu -------------- --- -----------------
Pi ------------ ---------------- --------
0.8 Pu -----------

0.75 Pi -------- ---










0 6y or 6c du 6


Figure 2-2. Schematic for ductility factor component definitions

Many researchers have used this method to characterize the ductility of FRP

reinforced concrete structures. Grace and Sayed (1998) tested bridge models prestressed

with CFRP tendons and used the energy method to determine ductility. However, they

had to measure the amount of inelastic energy of their bridge models. They did that by

subjecting their bridge models to loading and unloading cycles near 90% of their ultimate









capacity. Others have also used the energy method to determine ductility factors for FRP

reinforced concrete structures without having to measure the amount of inelastic energy.

They estimated the elastic energy as the area under a straight line drawn from the point

representing failure load and having a slope equal to the average of the initial and

secondary slopes of the load-displacement diagram of the structure (Alsayed and

Alhozaimy 1998; Vijay and GangaRao 2001; Li and Wang 2002).

p S=[P 1S1+(P2-P1)S2]/P2
S3
P3 --------- ------- ---------------- --.---
S2

P2 -------- -----







PI --- Inelastic Elastic
P1 Elastic
Inelastic
Energy Energy
Energy





0 8or


Figure 2-3. Schematic for energy method ductility factor

Grace et al. (1998) however discovered that the average slope used to estimate the

elastic energy was different that the one measured from their tests for a number of their

specimens and proposed the introduction of four more parameters to eliminate the

differences between the experimentally measured slopes and the average slope based on

the initial and secondary slopes. This made the process complicated and also raised

questions about the reliability of this particular method and whether it can be used to









determine ductility factors without having to experimentally measure the slope. It should

also be noted that using the initial and secondary slopes of the displacement diagram is

not as simple as it might be at first though. Typically there are no distinct slopes which

mean that a decision on which slopes to use has to be made which is subjective and

dependent upon the person that makes the decision. This can generate inconsistent

results.

The second method that has been proposed is a deformation based method. The

ductility factor, also referred to as J-factor, is the product of a strength factor and a

deformability factor. The strength factor takes into account the increase in the moment or

load capacity while the deformability factor takes into account the increase in either the

curvature or the displacement of the structure relative to a specific load level. This

specific load level has been defined as the load at which the concrete compressive strain

is equal to 0.001 (Fig. 2-4) (Theriault and Benmokrane 1998; Wang and Belarbi 2005) or

the cracking load (Zou 2003) or the service load (Newhook et al. 2002).

Based on the diagram in Fig. 2-4 the load factor (LF) and deformability factor (DF)

are the following:

Po
LF = (2-3)
P0 001

where P, is the ultimate load and Po.0oo is the load at a concrete compressive strain equal

to 0.001.


DF = (2-4)
0001

where 6, is the ultimate load and 60.00oo is the load at a concrete compressive strain equal

to 0.001.









The J-factor (JF) is then calculated as the product of the load factor and the

deformability factor as follows:

JF = LF DF (2-5)

There is no general agreement as to the load or deformability point with which the

ultimate values are compared to calculate the strength and deformability factors needed to

determine the J-factor. Therefore, the results obtained using this method, are based on an

arbitrary selection of a starting point which makes them unreliable. Li and Wang 2002

also pointed out that the use of J-factor values seemed to contradict experimental results

that indicated higher ductility for specimens that had low J-factors. Another shortcoming

of this method is the fact that a large J-factor can be obtained even for a perfectly linear

load displacement diagram which goes against conventional ductility definition which is

the amount of plastic deformability of the structure.

PI

PU -------------------------------
Pu









P0 001






0 60001 6u f

Figure 2-4. Schematic for deformation method ductility factor









The ductility factors calculated based on the above mentioned methods for FRP

reinforced concrete can not be directly compared to the ductility factors for steel

reinforced concrete because they are based on different approaches. For the case of the

CFRP grid reinforced concrete a method that can produce ductility factors in the spirit of

the ductility factors for steel reinforced concrete is needed. Such a method will be a

measure of the inelastic deformations of the FRP reinforced structure that take place due

to concrete confinement.

Non-Linear Static (Push-Over) Analysis

Push-over analysis is a practical method of analyzing a structure for dynamic

loading such as impact and seismic loading. Push-over analysis uses monotonic loads that

represent the dynamic loads and a non-linear description of the structure. The non-

linearity of the structure can be derived from the moment-curvature (M-D) relationships

of the piles or columns. Although push-over analysis is not itself a dynamic analysis it

can produce accurate results especially in the case were the fundamental mode of

vibration is predominately translational which is the case for single degree of freedom

systems (SDOF).

The California Department of transportation allows the use of an inelastic static

analysis (ISA), or push over, for the seismic analysis of bridges (Caltrans 2004(a)).

Mackie and Stojadinovic (2003) successfully used static push over analysis to investigate

seismic demand for performance based design of bridges. Fenves and Ellery (1998) also

used nonlinear static analysis to analyze a multi-frame highway bridge that failed in the

1994 Northridge earthquake. They were able to construct the load-displacement curves of

the bridge frames and to determine that the failure of the bridge frames was due to









inadequate shear capacity which prevented the bridge from utilizing the ductility

available for a flexure failure mode.

Hasan et al. (2002) used push-over analysis based on the nonlinear relationship of

the M-D curves for the analysis of two steel frame multistory buildings and were able to

determined overall ductility demands and identify the existence of 'soft' stories in the

buildings. They were also able to assess the adequacy of the earthquake-resistance

capacity of the buildings.

Halabian et al. (2002) used push-over analysis to analyze free standing reinforced

concrete TV towers. They used the M-0 relationships to account concrete cracking and

reinforcement yielding. Their analysis compared well to the time history analyses from

three earthquakes.

Saatcioglou and Razvi (2002) conducted push over analyses on confined concrete

columns and the results were a good match with the available experimental data from

reinforced concrete columns.

Plastic Hinge Length

Determination of the plastic hinge length is a complicated matter and no universal

equation exists. Researchers have introduced empirical equations that can be used to

estimate the plastic hinge length (1p) that for the most part are related to the effective

depth and the distance of the critical section from the point of contra-flexure (Baker and

Amarakone 1964; Corley 1966; Sawyer 1964; Baker 1956;). The experimental research

by the above researchers was conducted on reinforced concrete beams and frames.

Priestly and Park (1987) tested concrete bridge columns under seismic loading and

proposed an equation for estimating plastic hinge length. The equation estimates the

plastic hinge length as a function of the distance of the critical section from the point of









contra-flexure and the diameter of the longitudinal reinforcing steel. The experimental

average plastic hinge length was found to be equal to approximately one half the diameter

or depth of pile section. Watson and Park (1994) performed similar tests on reinforced

concrete columns and used the same empirical equation proposed by Priestly and Park

(1987) for estimating the length of the plastic hinge.

Budek et al. (2000) proposed an empirical expression for estimating the length of

the plastic hinge which was derived based on tests conducted on bridge drilled-shaft

reinforced concrete piles. The plastic hinge length in that expression was a function of the

pile/column diameter and the above grade height of the pile or column. The California

Department of Transportation also provides equations for the estimation of plastic hinge

lengths for use in the design of structures undergoing dynamic loading such as seismic

(Caltrans 2004(b)). For columns and type II shafts Caltrans requires using an empirical

equation based on the length of the column or shaft and the yield strength and the size of

the longitudinal steel reinforcement. For type one pile shafts/columns Caltrans requires

using a different empirical equation that is based on the diameter or the least dimension

of the pile shaft and the length of the pile shaft/column from the point of maximum

moment to the point of contra-flexure.

Conclusions

Based on the information obtained from the literature review of previous research

the following conclusions can be drawn:

* Testing has shown that when the CFRP composites are used as flexural reinforcement
the elements generally behave in a non-ductile manner.

* Confinement of concrete using FRP wraps or jackets improves concrete ductility and
strength. It was found that if enough FRP reinforcement is used to confine concrete its
strength can be improved up to 150% and its ductility up to a factor of ten.









* No evidence of CFRP grid use as confinement reinforcement was found, but the
available research suggests that it could be possible to improve concrete ductility by
using the CFRP grid as confinement reinforcement.

* CFRP composite materials do not seem to have any serious issues with durability in
marine or alkaline rich environments. However, it has been suggested that if glass
fibers are exposed to marine or alkaline environments serious degradation is likely.
Therefore the use of GFRP reinforcement in these environments is risky and should be
avoided.

* The methods used to determine ductility factors for FRP reinforced concrete structures
are different than the methods used for steel reinforced concrete and therefore the
factors from the different methods are not comparable. A similar method to the one
used currently for steel reinforced concrete is needed to provide comparable factors for
the FRP reinforced concrete.

* Non-linear static analysis can be used to analyze structural systems under dynamic
loads and can produce good results.














CHAPTER 3
CARBON GRID CONFINED CYLINDERS

Introduction

Column wrapping with CFRP composites is a popular alternative for improving the

seismic resistance of columns. Fiber fabrics and prefabricated FRP composite jackets or

tubes cover the entire area of the concrete element and therefore cannot be embedded in

concrete. The carbon grid has approximately 69% open surface area allowing the grid to

be embedded in the concrete. Light grids are easily formed into a tubular shape and can

provide more effective confinement than wraps that are forced to follow the column

cross-section, which might be square or rectangular.

It has been suggested that rather than wrapping the columns with CFRP fabrics

confinement of concrete can be provided by embedding carbon grid. The effectiveness of

the carbon grid in confining concrete was not known. Therefore, nine standard (6 x12 in.)

cylinders were tested in axial compression to investigate the level of confinement

provided by the grids.

The CFRP grid improved both the strength and ductility of the concrete. The CFRP

grid did not produce highly confined concrete because the amount of CFRP material

provided by the grid was low due to its large openings. Significant improvement was

observed in the ductility of the concrete cylinders with embedded CFRP grid. The

ultimate strain for the CFRP grid reinforced cylinders was approximately two times

larger compared to the control cylinders. Grid confinement also resulted in an increase in

the concrete strength of approximately 11%.









An empirical model was developed using available knowledge from research on

concrete confined using FRP sheets and prefabricated jackets or shells. The empirical

model is presented in this chapter. The model was in good agreement with the

experimental data available from the CFRP grid cylinder tests.

Manufacturing

Nine standard (6 in x 12 in) cylinders were cast. Table 3-1 contains the test matrix

of the cylinders. Two layers of grid, formed into concentric tubular configurations and

held with plastic ties, were cast into six of the specimens while the remaining three

cylinders were cast without reinforcement. The cylinders with the CFRP grid were

designated as grid cylinders. The grid cylinders were divided into two groups (3 cylinders

in each group) with each group having a different grid diameter. The CFRP grid for the

first group was formed into a tubular configuration that was approximately 11.4-in long

with a diameter of 5.25-in and a diameter of 5.5-in for the second grid cylinder group

(Fig. 3-1). Two layers of the grid were applied with the grid lapping the 2 layers for an

additional 7 in for development purposes. The grid openings were aligned to facilitate the

flow of concrete through the grid. The CFRP grid round tubes were placed inside plastic

cylinder molds and concrete was added (Fig. 3-2).

A Class II standard FDOT bridge deck concrete mixture was used to make the

cylinders. The specified minimum compressive strength of this concrete at 28 days is

5000 psi. Concrete was sampled as per ASTM C172 (ASTM 2004). Both the control and

grid cylinders were cast in the field according to ASTM C31 except they were ambient

cured rather than moist cured (ASTM 2003).

All concrete cylinders were allowed to cure in the field inside the plastic mold for

approximately one month and were then taken to the laboratory where they remained









until two weeks before testing. At that time they were removed from their molds and

sulfur cement caps were placed on each end. The total curing time for all cylinder

specimens was 125 days.

Table 3-1. Cylinder test matrix
Cylinder Number CFRP Grid Grid
type of grid layers dia.
specimens (in.)
Control 3 No 0 N/A
Grid 3 Yes 2 5.25
Grid 3 Yes 2 5.5


(a) (b)

Figure 3-1. CFRP grid round tubes: (a) cross sectional view and (b) longitudinal view








('FRP Gr'idl


j!; >;;I
(a) (b)

Figure 3-2. CFRP grid cylinder casting in the field: (a) beginning and (b) end









Experimental Program

CFRP Grid Testing

The CFRP composite grid tested in this program was fabricated from carbon fibers

embedded in an epoxy matrix. It was supplied in the form of rolls that were 41 inches

wide and 300 yards long. The strand spacing in the longitudinal direction was 1.8 inches

and in the transverse direction 1.6 inches (see Fig. 3-3). The CFRP grid had an openness

of 69% which means that only 31% of the surface area was covered by the carbon fibers.












(a) (b)

Figure 3-3. CFRP grid: (a) rolls and (b) tubular configuration

Tensile properties of the grid were determined by testing two strands from each

direction using the specimen configuration shown in Fig. 3-4(a). Each end of the strand

was embedded into a short section of steel pipe for approximately 4 in. The pipe was then

filled with an expansive grout leaving a free length of approximately 8 in. Two foil strain

gauges were placed near the middle of the free-length of the specimen. Steel angles

welded to the opposing ends of the pipe anchors were used to attach the specimen to the

loading apparatus (Fig. 3-4(b)). Loading apparatus consisted of a hydraulic actuator

mounted to a stiff steel frame in which load was measured with a ring load cell. The

average load rate for the four specimens was approximately 33 lbf per second with data

acquired approximately every half second.



























(a) (D)

Figure 3-4. CFRP strand tests: (a) CFRP grid strand specimen and (b) test set-up

Table 3-2 shows the results of the tensile tests. Strands taken from the longitudinal

direction are designated longitudinal (L) and strands taken from the transverse direction

are designated transverse (T). All the specimens ruptured at peak load. Three specimens

ruptured away from the anchor and only one close to the anchor. All specimens ruptured

at an interception of a longitudinal and a transverse strand. The average peak load per

strand was approximately 951 lbf and was approximately 16% lower than the load

provided by the manufacturer which was 1100 lbf (TechFab 2004). The average cross

sectional area was approximately 0.097 in2. The average strength was approximately

100.8 ksi and the average tensile modulus 9235 ksi. The strength of each specimen was

calculated by dividing the peak load by the cross sectional areas while the modulus was

determined by a linear regression of the stress-strain data (Fig. 3-5). The average of the

two strain gages was used as the strain for each stress level. The data shown in Fig. 3-5

do not extend to the rupture strength of the specimen because the strain capacity of the

strain gauges was exceeded.










Table 3-2. Results for CFRP grid specimens
Specimen Grid roll Area Peak Strength Modulus
direction (in2) load (ksi) (ksi)
(lbf)
T1 Transverse 0.0123 841.5 68.5 7433
T2 Transverse 0.0091 1147.5 126.2 8514
L1 Longitudinal 0.0094 924.8 98.0 9486
L2 Longitudinal 0.0080 891.0 110.8 11508

120

100- Ol T1 AT2 oL1 XL2
.,- 80-----y=11516x
0 80
y80 = 9671.2x
60y = 8548.9x
S60
y = 7665.4x
40

20


0 0.003 0.006 0.009 0.012
Strain (in/in)

Figure 3-5. Stress-strain curves of CFRP grid strands

Although insufficient tests were conducted to reveal statistical significance, some

indication of strength consistency can be determined from the test data. The coefficient

of variance (COV) for the strength was 24.2% while for the tensile modulus 17.4%. Both

COVs were high and were attributed to the variability between the CFRP strands. Some

strands had a thick layer of epoxy resin covering them, which resulted in a lower fiber

volume fraction. According to the manufacturing company (TechFab 2004) strands in

both the longitudinal and transverse direction have the same capacity. Tests conducted

here indicated 9% higher capacity for the longitudinal strands compared to the transverse

strands but that was attributed to the high variability and the small number of specimens

in each direction.










Cylinder Testing Details

Nine cylinders (three control and six grid) were tested in displacement control

mode in order to capture the post peak behavior of the specimens.

The smallest rate that the MTS loading frame could handle was approximately 0.06

in. per minute that resulted in a load rate of approximately 106 psi per second. This load

rate was approximately two times higher than the maximum load rate allowed by ASTM

C39 (ASTM 2001). Typical load head movement rate and load rate curves from the

control cylinders can be seen in Figs 3-6 and 3-7 respectively. The same load head

movement rate was used for all cylinder specimens tested in displacement control mode.

0.12


0.09


S0.06


0.03


0.00
0 20 40 60 80 100
Time (sec)

Figure 3-6. Typical load head movement rate for control cylinders

For the cylinder specimens to be tested in displacement control the 500 kip loading

frame was used. Two Linear Variable Displacement Transducers (LVDTs) were used to

continuously record the length change of the specimens as load was applied. The two

LVDTs were placed on opposing sides of the cylinder to determine the average length

change of the cylinder specimen (Fig. 3-8).










Load and movement data from the loading head as well as data from the LVDTs

were collected using a data acquisition program at a rate of 50 Hz. This high rate was

necessary to capture the post peak behavior of the cylinders.



6


4s


S2



0 20 40 60 80
Time (sec)

Figure 3-7. Typical load rate for control cylinders








LVDT








Lo.l





Figure 3-8. CFRP grid cylinder test set-up

Cylinder Results and Discussion

The average strength for the control cylinders tested in displacement control mode

was 6.83 ksi and the COV 1.1%. Results from the control cylinders can be found in Table









3-3. The control cylinders did not exhibit any significant post peak behavior but rather

crushed after reaching the peak load. Typical control cylinder types of fracture were: (a)

cone and split and (b) cone and shear. A control cylinder after testing can be seen in Fig.

3-9(a). The stress-strain curves for the control cylinders are depicted in Fig. 3-10. The

first control cylinder after reaching its peak load lost approximately half its strength

almost immediately but did not fall apart and continued to carry load contrary to the other

two control cylinders that lost all load carrying capacity abruptly soon after peak load.


















(a) (b)

Figure 3-9. Cylinders after testing: (a) control, and (b) grid (arrows indicate ruptured
CFRP grid strands)

The average strength of the grid cylinders was 7.67 ksi with a COV of 8.5%. Table

3-3 contains results from all grid cylinders. Grid cylinders typically failed when CFRP

grid strands ruptured. As expected, the concrete cover spalled off of the grid specimens

before the peak load was reached but the cylinders maintained most of their load carrying

capacity until grid strands started rupturing which took place in sequential rather than in

an abrupt manner.










10

8

6

4

2

0
0.


000


Figure 3-10.


0.004 0.008 0.012 0.016
Axial Strain (in/in)

Stress-strain curves for control cylinders
1 ._ .1 ... .... 1- _


able 3-3. CLlinder results
Type Grid Peak Strain at Conc. Peak Aver. COV
dia. load peak core stress stress (%)
(in.) (kip) load area (ksi) (ksi)
(in/in) (in2)
Control 1 N/A 192.33 0.00251 28.274 6.80
Control 2 N/A 191.97 0.00232 28.274 6.78 6.83 1.1
Control 3 N/A 195.88 0.00236 28.274 6.92
Grid 1 5.25 184.65 0.00281 21.647 8.53
Grid 2 5.25 146.33 0.00200 21.647 6.76
Grid 3 5.25 178.16 0.00256 21.647 8.23
7.67 8.5
Grid 4 5.5 167.19 0.00279 23.221 7.20
Grid 5 5.5 174.39 0.00256 23.221 7.51
Grid 6 5.5 180.66 0.00279 23.221 7.78


The carbon fibers in the CFRP grid are embedded in an epoxy matrix that creates a

smooth surface on the outside faces of the CFRP strands, which may have contributed to

spelling. A grid cylinder after testing with ruptured hoop CFRP grid strands can be seen

in Fig. 3-9(b). Experimental stress-axial strain curves for specimens Grid 1 to 3 and

specimens Grid 4 to 6 were plotted in Figs 3-11 and 3-12 respectively. The stress values

for the grid cylinders were calculated based on the area of the concrete core enclosed by

the CFRP grid and the axial strain was calculated as the average change in the length,


-B- Control 1
-- Control 2
-A- Control 3





A










measured by the two LVDTs mounted on the loading plattens, of the cylinder over the

original length.

10
-- Grid 1
8 --Grid 2
-- Grid 3





2


0.000 0.004 0.008 0.012 0.016
Axial Strain (in/in)


Figure 3-11. Stress-strain curves for grid cylinders 1, 2 and 3

10
Grid 4
8 Grid 5
Grid 6



4

2


0.000 0.004 0.008 0.012 0.016
Axial Strain (in/in)


Figure 3-12. Stress-strain curves for grid cylinders 4, 5 and 6

The post peak behavior for all grid cylinders was different than that of control

cylinders. Grid cylinders reached higher peak loads and accommodated larger

displacements than the control cylinders. This is especially evident in Fig. 3-13 where

typical experimental stress-axial strain curves from both control and grid specimens were

plotted. The areas of the stress-strain curves are presented in Table 3-4. The area under

the stress-strain curve of the grid cylinders was typically 2.5 times larger than the area of










the control cylinders. Specimens Grid 4, 5 and 6 had approximately 25% more area under

the stress-strain curve than specimens Grid 1, 2 and 3.


2

0
0.


000


0.004


0.008
Axial Strain (in/in)


0.012


0.016


Figure 3-13. Stress-strain curves for typical control and grid cylinders

Table 3-4. Area under stress-strain curve
Type Area Aver. area
(ksi in/in) (ksi in/in)
Control 1 0.0169
Control 2 0.0157 0.015
Control 3 0.0124
Grid 1 0.0341
Grid 2 0.0368 0.0338
Grid 3 0.0304
Grid 4 0.0395
Grid 5 0.0412 0.0421
Grid 6 0.0456

All grid cylinders reached a peak axial load followed by a descending post peak

curve. Other researchers observed such a behavior in lightly confined concrete. Harries

and Kharel (2003) made similar observations for their one and two-ply E-Glass confined

cylinders. Sfer et al. (2002) studied the behavior of concrete under triaxial compression

and their axial stress-strain curves at low confining pressures had a descending post peak

curve. The increase in the concrete strength was between 10% and 20%, which compares

to the 11% increase observed for our cylinders. In the case of the CFRP grid confined


-8- Control 2
-A- Grid 3
8- Grid 5









concrete even with the two grid layers the concrete was still considered lightly confined

since the two CFRP grid layers added up to less than one layer of carbon fiber fabric

when the CFRP grid strand thickness was spread uniformly over the surface area of the

concrete core. In addition the strength and modulus of the CFRP grid was found to be

lower than typical carbon composites, which further reduces its confinement

effectiveness. The post peak behavior observed for the CFRP grid cylinders verified the

observations made by Harries and Kharel (2003) and Sfer et al. (2002).

Empirical Confinement Model

Most models for concrete confined with CFRP reinforcement assume a single layer

of carbon fabric will provide adequate reinforcement to sufficiently confine the concrete.

When the CFRP grid is used as confinement reinforcement it is expected that the

confining pressure and confinement effectiveness will be less than that of a fully jacketed

system. Therefore models developed using data from relatively highly confined concrete

may not be adequate. Some of the models investigated calculated a stress-strain curve for

the grid confine concrete that was bilinear with ascending portions which contradicts the

experimental curves.

Several existing models were investigated to model the behavior of CFRP grid

confined concrete. All of the existing models examined are based on a constant thickness

of the FRP material that fully covers the external surface of the concrete. The hoop grid

strands only cover part of the area. One approach when using the existing models is to

determine an equivalent full coverage thickness for the hoop strands. The equivalent grid

thickness (teg) was calculated based on the following expression:


teg "* b* g (3-1)
h










where ni was the number of CFRP grid layers, ngs was the number of grid strands, bg was

the width of the grid strands, tg was the thickness of the grid strands and h was the height

of the cylinder.

The secant modulus of elasticity of concrete (Ec) was calculated based on existing

empirical expressions (Nawy 2003):

E = 57.f7 (3-2)

wheref'c was the minimum specified compressive strength of concrete, in psi, at 28 days

and Ec is in ksi.

To determine the confinement strength (fr) simple pressure vessel mechanics were

used (see Fig. 3-14). The equilibrium condition required the force from the confining

strength be equal to the force in the FRP encasement.

Carbon grid










fgu teg fgu teg




Figure 3-14. Cylindrical pressure vessel

The equilibrium condition for the confined cylinder was expressed as follows:

f,, dg = 2 teg fgu (3-3)









where f, was the confinement strength, dg was the diameter of the CFRP grid tube andfg,

was the ultimate strength of the CFRP grid strands.

By rearranging equation 3-3 the confinement strength (fI) was calculated using the

following:

2-t
fru = fg (3-4)


Assuming that the confined concrete was in a triaxial stress state, the increase in

strength provided by the confinement was reflected in the maximum stress (f"cc) for a

cylindrical specimen, which was defined as (Mander et al. 1988):

fl = f + k, f (3-5)

where k, was the confinement effectiveness coefficient. The confinement effectiveness

coefficient for concrete confined by steel is usually taken between 2.8 and 4.1. Campione

and Miraglia (2003) found that the above values overestimate the confinement

effectiveness coefficient for concrete wrapped with FRP. They found the confinement

effectiveness coefficient for FRP wrapped concrete to be two. Therefore, the confinement

effectiveness coefficient was assumed to be equal to two.

The axial strain of CFRP grid confined concrete at the peak stress (eco) was

determined in a similar manner as unconfined concrete using the following expression

(MacGregor 1997):


8 =1.8f (3-6)
E,

Equations 3-5 and 3-6 were combined with the modified Hognestad (Park and

Paulay 1975(a)) stress-strain equation as follows:










2. 2]
f = I a r (3-7)


f, = J; "[1- D, (, -o)] (3-8)

where ec was the concrete strain, eo was the strain at peak stress of unconfined concrete

and e,, was the ultimate strain. These equations were plotted in Fig. 3-15. The modified

Hognestad equations model the ascending branch (AB) with a parabolic relationship and

the descending branch BC with a linearly descending curve. The equation for region BC

is based on the deterioration constant (Dc) that controls the slope of the line.

Stressfc Region AB







c
fp___ B Region BC



I I


Sg Strain F,
A o en

Figure 3-15. Modified Hognestad stress-strain curve

The material properties of the CFRP grid strands were used to construct the stress-

strain curve of the CFRP grid confined concrete. The average strength of the control

cylinders tested in displacement control mode was taken as the strength of unconfined

concrete (f'c). An average CFRP grid tube diameter of 5.375 in. was used. The ultimate

concrete strain cu, was assumed to be 0.0061 in/in. The average stress-strain curve for the

CFRP grid confined concrete was calculated using data from all grid cylinders. The










deterioration constant was taken equal to 120 to match post peak experimental data. The

experimental and empirical model stress-strain curves are depicted in Fig. 3-16.

10

8 -- Exper. (aver. of 6 tests)
-E- Empirical model


4

2

0
0.000 0.003 0.006 0.009 0.012
Axial Strain (in/in)

Figure 3-16. Experimental and empirical model stress-strain curves

The modified Hognestad curve calculated using the empirical model matches well

with the average experimental curve calculated from the data available from the CFRP

grid confined cylinders. The average experimental peak stress was 7.7 ksi while the peak

stress calculated from the empirical model was 7.5 ksi. The calculated value was 2%

lower than the experimental average. The average experimental strain at the peak stress

was 0.00259 in/in while the model predicted a strain of 0.00288 in/in at peak stress. The

predicted strain value was 11% higher than the average experimental value.

Conclusions

Based on the results presented the following conclusions were drawn:

* The CFRP grid does not produce a highly confined concrete. This was expected since
the amount of CFRP material provided by the grid is low due to its large openings.

* Significant improvement, however, was observed in the ductility of the concrete
cylinders with embedded CFRP grid. The ultimate strain for the grid cylinders was 2
times the ultimate strain of the control cylinders.

* Grid confinement also resulted in an increase in the concrete strength of approximately
11%.






40


* The larger CFRP grid diameter cylinders were more ductile compared to the smaller
CFRP grid diameter cylinders with the exception of cylinder Grid 2. However the
difference in diameters and the number of cylinders was small and therefore this
conclusion is drawn with caution.

* The equivalent grid thickness was a valid way of converting the concentrated thickness
of the CFRP grid to an equivalent thickness over the surface area of the concrete core.

* The modified Hognestad provides an accurate empirical prediction of the behavior of
concrete confined with the CFRP grid.














CHAPTER 4
RECTANGULAR CONCRETE SECTION WITH CFRP GRID TUBES

Introduction

Two rectangular beams were built and tested to evaluate the effect of grid tubes

made from CFRP grid on the behavior of a non-ductile beam. The purpose of the beams

was to measure the amount of ductility that confinement of the compression zone can

produce in a compression controlled beam and to improve beam ductility.

Testing of these beams verified the assumption that confinement and therefore

concrete ductility can be achieved without having to wrap the whole beam with the CFRP

grid but by confining the compression zone with a series of carbon grid tubes.

Both beams were designed to fail by concrete crushing. The beam with the grid

tubes had an improved ductility compared to the beam with no grid tubes due to concrete

confinement of the compression zone. The cover concrete in the compression zone of the

tube beam crushed earlier than the concrete inside the CFRP grid tubes.

Experimental Program

Specimen Construction

Table 4-1 contains some of the construction details for the two rectangular beams.

The first beam had no grid tubes and served as the control beam (See Fig. 4-1) and the

second beam (tube beam) had two grid tubes placed in the compression zone (See Fig. 4-

2). The width of the beams was 12 in. and the height 18 in. The flexural reinforcement

consisted of 8 #10 steel reinforcing bars (60 ksi, 1.25 in. diameter) placed in two rows

(Figs 4-1 and 4-2). The amount of steel used in the beams is large because the beams








were designed to be overeinforced to force the failure into the compression zone. Steel

stirrups (0.375 inches) were spaced at 3 in. to provide shear resistance. Stirrups were not

placed in the center portion of the beams (see Figs 4-1 and 4-2). In the case of the tube

beam the two CFRP grid tubes were placed next to each other approximately 0.75 in.

from the top of the beam (Fig. 4-2). The tubes did not extend to the ends of the beam but

rather were cut short approximately 1.5 ft from each end. The CFRP grid tubes had a

diameter of 6 in. and were made with two CFRP grid layers.

Table 4-1. Test matrix for tube beams
Beam Grid tube No. of No. of Dia. of
grid grid grid tubes
tubes layers (in)
Control No 0 0 N/A
Tube Yes 2 2 6


5" 3"
I\ \ IIIII IIII IIII IIII IIII


F


1_


6' 3" 2' 8" 6' 3"
16'


#3 Stirrups


Figure 4-1. Longitudinal (top) and cross-sectional (bottom) views of control beam


IIIIIIIIIIIIIiiiIIIII11111 F 611






43


The CFRP grid was formed into a circular tube using a 6 in. diameter plastic pipe

and was held in place by a thin rope wrapped around the tube along its length (See Fig. 4-

3). The CFRP grid was laid in the sun for a few hours to soften the epoxy matrix and

facilitate the formation of the tubes. More details on the properties of the CFRP grid can

be found in chapter 3.

5" 13'


SI


6' 3"


2' 8"
16'


S'1' 36
.. . .


1" Clear
0.75" 1" Clear



#3 Stirrups


18"
8 #10 Bars

2.75"
2" Clear


12"


Figure 4-2. Longitudinal (top) and cross-sectional (bottom) views of grid tube beam

Both beams were cast using ready-mix concrete with 28-day design strength of

5000 psi, and maximum aggregate size of 0.375 in. The control beam (See Fig. 4-4(a))

concrete was placed and vibrated in typical manner (Fig. 4-4(b)).

One grid tube was inserted in the tube beam before concrete placement began to

allow room for placing and vibrating the concrete (see Fig. 4-5). When the concrete

reached the bottom of the first grid tube the second tube was installed next to the first









grid tube and the remainder of the concrete was placed. Vibration was also applied to the

tube beam.


Figure 4-3. Formation of CFRP grid tubes


(a) (b)


Figure 4-4. Control beam: (a) concrete casting, and (b) concrete vibration









Once the form was full, the top of the beams was finished and the beams were left

in the laboratory to cure. The beams were allowed to cure for a total of 44 days before

testing.























7 -: k.





Figure 4-5. Concrete placing (tube beam)

Eight standard (6 x 12 in.) cylinders were cast along with the beams (see Fig. 4-6).

The cylinders were tested on the same day as the beams to determine the actual concrete

strength at testing.

Test Set-Up and Procedure

The two beams were tested in a simply supported four-point bending configuration

(see Fig. 4-7) in displacement control mode, that is, a constant displacement rate was









applied independently of the amount of load. The span length between the two supports

was 14 ft, whereas the total length of the beams was 16 ft.


Figure 4-6. Concrete cylinder casting


LVDT S Tilt Meter 60 mm Foil Gauge


Figure 4-7. Test set-up for both beams









A hydraulic actuator was used to apply the displacement to the beams. The applied

displacement was distributed to the two load points using a steel spreader beam. From the

spreader beam the displacement was transferred to the beam using two steel rollers. The

rollers allowed the loading mechanism to follow the rotation of the beam as the load

increased, whereas steel plates distributed the load to avoid localized failure of the

concrete material that could happen if the load was applied to a very small area or single

point. A load cell was used to measure the applied force. The load points were located

5.5 ft from each support. This created a 3-ft region in the center of the span with pure

flexure.

The beams were loaded at a rate of 0.004-in. per second. The displacement was

applied monotonically until the beam could no longer sustain a significant load.

Instrumentation

A series of 15 linear variable differential transducers (LVDTs) were placed at 12-

in. intervals to measure the displacement of the beam at different locations along the

length of the beams (see Fig. 4-7). The LVDTs were labeled from north to south as Dl

through D 15.

Four tilt meters, two at the supports and two at 3 ft from the supports, were used to

measure the rotation of the beams at those locations (see Fig. 4-7). The tilt meters were

labeled from north to south as T1 through T4.

Foil strain gages were attached on the sides of the beams at mid-span (Fig. 4-8) and

on top of the beam (Fig. 4-9). The strain gages at the side of the beams were labeled from

the top down as SE1 through SE7 for the east side and SW1 trough SW7 for the west side

of the beam. The two bottom strain gages on the sides of the beams were located

approximately at the same level as the two layers of the steel flexural reinforcement and









they were place there to measure the strains in the concrete at those locations. Before

concrete cracking the strains in the concrete and the steel are the same. The strain gages

on the top of the beams were labeled from north to south as ST1 through ST3.

B eam Top


SE2
4 @1.5" I SE4 SE3
---^^SE5SE4

3" __-- 1_._ SE6
I
-' ---L = -- SE7



Beam Centerline

Figure 4-8. Strain gage arrangement (side view of center portion of the beam)


Figure 4-9. Strain gage arrangement (top view of center portion of the beam)

The strain gages on the side of the beams were used to measure strain across the

cross-section of the beams whereas the strain gages on top to measure any transverse

expansion of the compression zone due to the Poisson effect.

Data from all instrumentation devices were recorded using a data acquisition

system at a rate of 4 Hz.









The actual test set-up with all the instrumentation placed at the appropriate

locations is depicted in Fig. 4-10.























Figure 4-10. Test set-up for both beams before testing

Results and Discussion

Cylinder tests

The cylinders were tested on the same day as the beams. A total of 8 cylinders were

tested using a cylinder tester. All cylinders tested were capped using a sulfur cement cap

at each end to uniformly distribute the load from the loading head to the concrete

cylinder.

Table 4-2 contains the results from the cylinder tests. The average compression

strength for the cylinders tested was 6.06 ksi and the coefficient of variance was 2.3%.

Typical cylinder types of fracture were: (a) cone and (b) cone and shear. The low

coefficient of variance was an indication of strength consistency of the concrete.










Therefore, the unconfined strength of the concrete in the beams to be tested was taken as

the average of the 8 cylinders.

Beam tests

The load-displacement (P-A) curve for the control beam was bilinear (Fig. 4-11).

Two distinct slopes can be distinguished: The slope of the initial part of the P-A curve

remains constant up to a load of approximately 100 kips. The slope of the curve from 100

kip total load to peak load was lower possibly due to the reduction of the effective cross-

section caused by the growth of concrete cracks. It was evident that the lack of any post

peak behavior exhibited by the control beam resulted in a non-ductile failure.

Table 4-2. Experimental results from cylinders tests
Cylinder Peak load Concrete Peak stress Aver. stress COV
(kip) area (in2) (ksi) (ksi) (%)
1 172.16 28.274 6.09
2 175.89 28.274 6.22
3 164.70 28.274 5.83
4 173.17 28.274 6.13
6.06 2.3
5 167.54 28.274 5.93
6 173.10 28.274 6.12
7 168.31 28.274 5.95
8 174.90 28.274 6.19


160
140
- 120-
* 100-
80
3 60
H 40


0
-- Control
20 -6 Tube
0 f^-------------------
0.0 0.3 0.6 0.9 1.2 1.5 1.8
Displacement (in)


Figure 4-11. Load-displacement curves for control and tube beams






51


The curve for the tube beam was also bilinear up to peak load (Fig. 4-11).

However, the post peak behavior of the tube beam was significantly different compared

to the behavior of the control beam. Although the tube beam did loose a portion of its

load bearing capacity instantly when it reach peak load it maintained most of its capacity,

approximately 88% of peak and continued to displace.

The peak loads were approximately 148 kips for the control beam and 153 kips for

the tube beam. There was a nominal increase in the peak load of the tube beam of

approximately 3% compare to the control beam.

The control beam failed due to concrete crushing in the constant moment region at

peak load (See Fig. 4-12(a)). The tube beam also failed due to concrete crushing in the

constant moment region (See Fig. 4-12(b)). However, the amount of damage to the

compression zone of the control beam was more severe than that of the tube beam (See

Fig. 4-12). The visual evidence also point towards a better performance of the tube beam

compared to the control beam.














(a) (b)

Figure 4-12. Compression zones for both beams after testing: (a) control beam and (b)
tube beam









The concrete inside the CFRP grid tubes maintained the circular shape of the tube

even after the tube failed and confinement was lost (Fig. 4-13). The CFRP grid ruptured

at a particular location and not throughout the constant moment region which was why

the concrete maintained that shape.





















Figure 4-13. Tube beam compression zone after testing

Fiber Model Analysis

The peak loads for both beams were calculated using a fiber model analysis of the

beam cross-section. The compression zone of the tube beam was separated into two

regions with regard to concrete properties. The first region was the concrete cover on top

of the CFRP grid tubes and the second region was from the neutral axis to the top of the

CFRP grid tubes (see Fig. 4-14). The first region was extended approximately 0.25 in.

below the top of the CFRP grid tubes to account for the unconfined concrete at the sides

and between the grid tubes. The first region was assigned unconfined concrete properties

and the second region confined properties. The concrete area from the neutral axis to the









bottom of the grid tubes was unconfined but was treated as confined concrete for

simplicity and because the strains in that area close to the neutral axis were small and

therefore the effect on the strength was minor. The unconfined region was divided into

one rectangular fiber layer while the confined region into eight rectangular fiber layers.

For the control beam case the compression zone was treated as an unconfined concrete

region and was divided into eight fiber layers.

Some of the assumptions employed in this fiber model include perfect bond

between concrete and the reinforcing bars (strain compatibility), plain sections remain

plain (linear strain distribution), the area below the neutral axis was considered cracked

and was ignored in the force and moment calculation and monotonic loading and

deformation of the section.

1" 0.75"




S.... ........ Gd Tube
c-" .A.
---- ------_ GrdTube



_. _, _- __9 9.. 'iA

** *


Unconfined concrete

X Confined concrete

Figure 4-14. Tube beam cross-sectional fiber model









The compressive force in each fiber layer was calculated as the product of the area

of the fiber layer and the average stress. The average stress was determined based on the

strain in the fiber layer and the stress-strain curves of concrete. The Hognestad parabola

was used to calculate the stress-strain curve of unconfined concrete. The modified

Hognestad was used to calculate the stress-strain curve of confined concrete. The

parameters of the modified Hognestad were determined based on the available data from

confined concrete cylinder tests.

The tensile force was calculated as the product of the area of steel reinforcement

and the steel stress which was determined based on the average strain of the two steel

layers. The steel stress was calculated based on an assumed elastic perfectly plastic

stress-strain curve with yield strength of 60 ksi and modulus of elasticity of 29000 ksi.

The moment in the cross-section for the applied curvature distribution was

determined by summing moments about the neutral axis.

The moment curvature diagram was calculated by applying increasingly larger top

concrete compressive strains (ec) to the cross-section and varying the location of the

neutral axis (c) until equilibrium of the axial forces (zero) in the cross-section for the

applied strain was achieved. The curvature of the section (0 = c /c) was then calculated

based on the concrete compressive strain and the location of the neutral axis.

The fiber model peak loads were 151 kips for the control beam and 156 kips for the

tube beam. The experimental peak loads were 148 kips and 153 kips for the control and

tube beams respectively. Therefore the fiber model calculated the peak loads for both

beams and could be used to calculate peak loads for beams utilizing the CFRP grid tubes.

The fiber model peak loads were approximately 2% higher that the actual loads.










Analysis of Strain Data

The strains on the two opposite beam sides (east and west) were the same as it is

evident from Fig. 4-15. This was typical for all strain gages in the compression zone of

the each beam.

Based on the fact that the strains on the two opposite beam sides were the same, the

strain at each gage location was taken as the average of the two strain gages at that

location. For example, the strain at 1 in. from the top of the beam (S1) was taken as the

average of SE1 and SW1. The same approach was used for all other locations.

160
140
^ 120
100 -
S80
0 60
S-A- SE1
40 -
-8- SW1
20
0
0 1000 2000 3000 4000
Compressive Strain (microstrains)


Figure 4-15. Load-strain curves for strain gages at opposing locations (control beam)

The maximum average strain at peak load recorded during the test for the control

beam was at S1 location and was approximately 2840 pE (see Fig. 4-16). The other

average strains were smaller as expected, been closer to the neutral axis of the beam, but

when concrete crushing started the average measured strains at S2, S3, S4 and S5

increased rapidly due to the fact that the loss of concrete moved the extreme compression

closer to their location. This was typical for the tube beam as well. However the strains

recorded for the tube beam were smaller than the strains for the control beam. The

maximum average strain recorded at peak load for the tube beam was at location S1 and










was approximately 2550 [E which was approximately 10% lower than the strain recorded

for the control beam.

160
140
S120
3 100
80
7g 60
S40
2 0-Si -SA- S2 -8-S3
20 <-S 4 E- SS5

0 1000 2000 3000 4000
Compressive Strain (microstrains)

Figure 4-16. Load-strain curves for control beam

The compressive strain for the extreme concrete fiber can be calculated by plotting

the strain profile (see Figs 4-17) of the beam. Assuming a linear distribution of strain

through the beam cross-section a straight line can be fitted and the equation of the fitted

line can be used to determine the strain at the extreme concrete fiber. The fitted lines

were in good agreement with the experimental results as it was evident in Figs 4-17. The

average R2 value (the proportion of the variance in y attributable to the variance in x) of

the fitted lines for the tube beams was 0.999 which was close to a perfect match (R2 = 1).

This was typical for both the control and tube beams. The high R2 values support the

assumption of a linear distribution of strain through the beam cross-section which also

suggests that plane sections remain plain.

The strains at the extreme concrete fiber in compression at increasing load levels

were calculated based on the fitted line equations and are presented in Table 4-3. The

strain at the extreme compression fiber at peak load (crushing strain) for the control beam

was approximately 3170 tE whereas for the tube beam was 3010 tE. The crushing strain










for the tube beam was approximately 5% lower than the crushing strain calculated for the

control beam.


0 1000


0

S-2

S-4
C
S-6

S-8

-10


Strain (microstrains)
2000


Figure 4-17. Compressive strain profile for control beam

Table 4-3. Experimentally calculated top compressive strains
Beam Load (kips) Experimentally
calculated top
strain (ps)
Control 21.9 333
43.7 681
65.6 1048
87.3 1436
109.0 1883
148.0 3167
Tube 22.4 421
45.4 770
67.4 1127
89.2 1481
110.2 1891
152.3 3010

Design codes usually assume a concrete crushing strain of 3000 p, (ACI

Committee 318), which agrees well with the crushing strains calculated from the

experimental data. Typically, concrete crushing strains vary from 3000 to 4000 p, (Nawy

2005; Hasoun and Al-Manaseer 2005; Hassoun 2002; MacGregor 1997). Lower strength

concretes (less than 5000 psi) are typically more ductile and have higher crushing strains


\ /+ +P= 21.9 kips
SP = 43.7 kips
o P = 65.6 kips
/ J x P = 87.3 kips
OP = 109.0 kips
AP = 148.0 kips









than higher concrete strengths (more than 5000 psi) that tend to be more brittle and have

lower crushing strains.

The strength of the concrete used in these beams was approximately 6100 psi

which was relatively high. Based on the crushing strain values it can be concluded that

the concrete used in this beams was brittle as expected based on its high strength.

The compressive strains were reduced due to the presence of the CFRP grid. This

was attributed to the fact that the CFRP grid restrains concrete movement which is

manifested in the reduction of the strains. As the concrete in the compression zone is

compressed it also expands laterally. That lateral expansion of the tube beam however

was restrained by the CFRP grid which also reduced the longitudinal shortening of the

compression zone hence the reduction in the measured strain.

Assuming that plane sections remain plane the strains at each steel layer can be

determined using similar triangles (see Fig. 4-18). Strains for both steel layers using this

procedure are presented in Table 4-4.




c

C


d N.A.




d c




Figure 4-18. Assumed strain distribution









Table 4-4. Steel strains calculated using experimental data
Beam Load Steel strain layer 1 Steel strain layer 2
(kips) (tp-) (ts)
Control 21.9 248 141
43.7 550 324
65.6 850 502
87.3 1150 676
109.0 1452 840
148.0 2008 1059
Tube 22.4 418 264
45.4 812 522
67.4 957 575
89.2 1199 707
110.2 1442 831
152.3 1829 942

The strain in steel layer 1 at peak load was approximately 2010 Es for the control

beam and 1830 Es for the tube beam. This represents a difference of approximately 9%.

Both values were close to the yield strain the 60 ksi steel calculated based on Young's

modulus as 2070 gE.

In reality the CFRP grid tubes reduce the rotations of the tube beam which also

means a reduction in the curvature of the beam. The lower curvature obviously causes a

reduction in the compressive strains as well as the tensile steel strain.

Three strain gages (ST1, ST2 and ST3) on the top of the beams were used to

determine transverse expansion of the compression zone due to Poisson effect. The rate

of strain increase was relatively small up to a load of 120 kips and increased after that

(see Fig. 4-19). The rate was higher for gage ST2 located at mid-span. Very close to peak

load the transverse strain at the mid-span location increased very rapidly an indication of

an imminent concrete failure. This was typical behavior for both the control and tube

beams.










The reason gages ST1 and ST3 did not record a rapid increase of strain as did gage

ST2 was due to their location. Gages ST1 and ST3 were located close to the load plates

that provided confinement to the surrounding concrete. The confining effect of the load

plates was much higher close to the load points and decreased away from the load points.

At the mid-span location that was located the farther from the load points than any other

point inside the constant moment region the effect of the load platens was much smaller.

The confinement from the load plates restrained the tensile lateral expansion of the

concrete and reduced the lateral strains at the two locations close to the load points.

160
140
s 120
S100
S80o
so
3 60
H 40 -A-ST1 -B-ST2 -e-ST3
20
0
0 1000 2000 3000 4000
Top Poisson Strain (microstrains)

Figure 4-19. Transverse expansive strains for control beam

The strain gages attached to the top of both beams in the transverse direction were

able to detect the impending concrete failure as the data from gage ST2 indicated.

However the peak strains recorded by gage ST2 for the control and tube beams were

significantly different in magnitude. The peak strain of the control beam was

approximately 3170 tE while the peak strain for the tube beam was 2230 tEs. That

difference can be explained by the presence of the CFRP grid tubes. As the concrete tries

to expand laterally, due to the Poisson effect, the CFRP grid tubes restrain and resist that









movement. That results in a reduction of the lateral expansion which is obvious by the

lower recorded strain.

Measured Rotations

Four tilt meters were used to measure the rotations of the beams. The rotations for

both the control and tube beams at increasing loads are reported in Table 4-5. The

measured rotations of the control beam were lower that the measured rotations of the tube

beam for the same amount of load. That was due to the CFRP grid tubes improving the

resistance of the tube beam against rotation. The differences in rotation grew as the load

increased from approximately 20% for a load of 21.9 kips to approximately 25% for a

load of 109.1 kips.

Table 4-5. Rotations measured by tilt meters
Beam Load Tilt Tilt Tilt Tilt
(kips) meter T1 meter T2 meter T3 meter T4
(degrees) (degrees) (degrees) (degrees)
Control 21.9 -0.1377 -0.1209 -0.1244 -0.1528
43.7 -0.2979 -0.2660 -0.2628 -0.3240
65.6 -0.4705 -0.4239 -0.4100 -0.5066
87.3 -0.6530 -0.5942 -0.5749 -0.7011
109.1 -0.8590 -0.7987 -0.7735 -0.9144
148.0 -1.3169 -1.2593 -1.2236 -1.3776
Tube 21.9 -0.1080 -0.0943 -0.0977 -0.1218
43.7 -0.2350 -0.2089 -0.2045 -0.2511
65.6 -0.3685 -0.3283 -0.3176 -0.3868
87.3 -0.5106 -0.4595 -0.4456 -0.5326
109.1 -0.6678 -0.6136 -0.5948 -0.6894
152.8 -1.0527 -1.0000 -0.9724 -1.0675

The rotations of the two beams based on the displacement profiles were also

calculated by fitting a 6th order polynomial curve to the displacement profiles and then

taking the first derivative of the polynomial equation. The calculated rotations for the

same loads and locations are presented in Table 4-6.









The rotations calculated based on the displacement profiles typically exhibited the

same trends as the rotations recorded by the tilt meters.

The tilt meter rotations were higher than the rotations calculated based on the

displacement profiles. That could be due to the fact that the tilt rotations were essentially

the rotations of the beam at the point the tilt meters were located whereas the calculated

rotations were based on a line that was fitted through several points along the entire

length of the beam.

On the average the tilt meter rotations were approximately 24% higher than the

rotations calculated from the displacement profiles from the control beam (see Fig 4-20)

and approximately 10% for the tube beam (see Fig. 4-21). The rotations for the T2

location were graphically presented for both the control and tube beam and were used to

demonstrate the differences. These differences were typical for all four rotation locations.

Table 4-6. Rotations calculated based on the displacement profiles
Beam Load Rotation Rotation Rotation Rotation
(kips) at TI at T2 at T3 at T4
location location location location
(degrees) (degrees) (degrees) (degrees)
Control 21.9 -0.1027 -0.0909 -0.0858 -0.1530
43.7 -0.2306 -0.2002 -0.1914 -0.2968
65.6 -0.3425 -0.3193 -0.3094 -0.3991
87.3 -0.4611 -0.4485 -0.4287 -0.5429
109.0 -0.6073 0.6016 -0.5717 -0.7047
148.0 -0.9282 -0.9626 -0.9110 -1.1150
Tube 22.4 -0.0549 -0.0867 -0.0776 -0.1402
45.4 -0.1728 -0.1966 -0.1814 -0.2667
67.4 -0.2999 -0.3116 -0.2931 -0.4008
89.2 -0.4202 -0.4388 -0.4147 -0.5301
110.2 -0.5346 -0.5901 -0.5611 -0.6704
152.3 -0.8938 -0.9798 -0.9397 -1.0600

Based on the rotation data it can be concluded that the calculation of beam rotations

from the displacement profiles was valid. The fact that the two methods of determining











beam rotations yielded comparable results makes both methods acceptable. Therefore,

determining the curvature of the beams using the displacement profiles was also validated

based on the rotation results. If rotation results were valid then curvature results were also

valid because the same basic equations were used to determine both.

160
140
120
S100
80
60 3
T2-Tilt 40
-- T2-Displ.
20


-1.5 -1.2 -0.9 -0.6 -0.3 0.0
Rotation (degrees)


Figure 4-20. Measured rotations at increasing loads (control beam)


160
140
120 ,
100
80
60 -g
60

-A-T2-Tilt I 40
-B- T2-Displ. 20

0
-1.5 -1.2 -0.9 -0.6 -0.3 0.0
Rotation (Degrees)


Figure 4-21. Measured rotations at increasing loads (tube beam)

Moment-Curvature Analysis

The LVDT measurements, at different locations along the length of the beams,

were used to construct the displacement profile curves (see Fig. 4-22) at increasing loads.

The displacement profile equation was generated by fitting a sixth order polynomial line










to the displacement profile curves (Fig. 4-22). The fitted lines were in good agreement

with the displacement data (average R2 = 0.997). The polynomial displacement profile

equation of the beam was used to determine the curvature at specific points along the

length of the pile. The second derivative of the polynomial displacement profile equation

is the curvature equation.

Displacement Location from North Support (in)
0 30 60 90 120 150 180
0 --I I I I I
y =2.6E-13x6 1.3E-10x + 2.1E-08x 1.3E-06x3 + 3.6E-05x2 -4.0E-03x- 5.8E-02

-0.1


-0.2


-0.3
0 P= 43.7 kips
Poly. (P = 43.7 kips)
-0.4


Figure 4-22. Displacement curve and fitted polynomial line for control beam at 43.7 kips

To model the behavior of the beams a program that generated the sectional

moment-curvature (M-PD) relationship was used (Consolazio, Fung and Ansley 2004).

The program describes cross sectional geometry using piecewise linear segments

for both the exterior and interior boundaries of the section. Interior boundaries represent

voids in the section. Curved boundaries such as the boundaries of circular sections are

approximated by using multiple linear segments. The reinforcing bars are modeled as

cross-sectional areas located at specific locations.

Some of the assumptions associated with the program are the following:

* Sign convention is positive for compression and negative for tension

* Plain sections remain plain which means that the strain distribution for the cross-
section is linear









* Perfect bond between the reinforcement and the concrete (strain compatibility)

* Monotonic loading and deformations of the section

* Ignore confining effect on concrete

The internal section forces of the cross-section are generated for a specified section

curvature and a specified axis location. The elastic centroid of the cross-section is

choose as an arbitrary reference centroid. The flexural moments of the section are

computed with reference to axes that pass through the reference centroid.

The contribution to the axial force and moment of the compression zone of the

concrete is determined by first meshing the geometry into trapezoids and then applying

numeric integration procedures. By numerically integrating the concrete stress surface

over each trapezoid in the meshed section the contributing force from each trapezoid is

found. The sum of all the trapezoid forces is the contribution of the concrete to the

internal axial force. The moment contributions are computed by multiplying the force

from each trapezoid with the distance between the reference centroid and the force.

The strain in the reinforcing bars is assumed to be uniform and is used in

conjunction with the reinforcement stress-strain diagram to compute the stress. The force

in the bar is the area of the bar times the stress taking into account concrete displaced by

the reinforcement bars. The sum of all bar forces is the contribution of the reinforcement

to the internal axial force. The moment contributions of the reinforcement are computed

in the same manner as for concrete using the distance from the reference centroid.

The total internal axial force is the summation of all the concrete and reinforcement

axial forces with their respective signs. The total moment of the section is the summation

of the moment contributions of concrete and reinforcement.









The complete moment-curvature diagram is calculated by applying increasingly

larger levels of section curvature to the cross-section using a moment curvature algorithm

to find the location of the neutral axis by iteration.

For the case of the tube beam a concrete confinement model was integrated into the

M-D program. However, the M-D program is not configured to assign different material

properties for confined or unconfined concrete but rather assigns the same properties

throughout the section. Therefore when used to produce the M-0 curve of the tube beam

confined concrete properties were used for the entire section. However, the top cover

layer was removed and the section was analyzed as a section with a depth of 17 in. rather

than the actual 18 in. This solution is a lower bound solution for the strength evaluation

of the CFRP grid tube beam. From hereon the results from the moment curvature

program will be referred to as theoretical results.

The M-0 curves for both beams were also calculated based on the fiber model

described in a previous section in this chapter.

The experimental, theoretical and fiber model M-0 diagrams were calculated for

both beams. The theoretical and fiber model M-D diagrams for the control beam (see Fig.

4-23) were the same. However, the theoretical peak load is approximately 5% lower that

the peak load calculated using the fiber model. This difference was attributed to the

different models used to represent the stress-strain behavior of concrete between the two

models. The stiffness of the mid-span location was lower that the theoretical fiber model

stiffness. The stiffness of the south load location was comparable to the stiffness of the

diagrams calculated theoretically and using the fiber model.










500

400

|300

S200
-e-Exp. Mid-Span
S-- Theoretical
100 -IE- Exp. South Load
-*- Fiber Model

0 0.0002 0.0004 0.0006 0.0008 0.001
Curvature (rads/in)


Figure 4-23. Experimental and theoretical M-D curves for control beam

The experimental M-D behavior of the tube beam was comparable to the behavior

calculated by fiber model (see Fig. 4-24). The theoretical 1 behavior is different than the

experimental in that it does not capture the loss in capacity due to cover concrete

crushing but this was expected because the program used only one stress-strain curve to

characterize the properties of the concrete section. The non-linear second part of the

curve was the behavior of the beam with the whole section confined with the top cover

layer removed. Curve theoretical 1 was a close match with the mid-span experimental

curve up to the peak load. Although the capacity loss was not captured by the theoretical

analysis the plateau noted on the experimental curve was also noted on the theoretical 1

curve. Curve theoretical 1 was a lower bound solution of the tube beam. Curve theoretical

2 had the same shape as curve theoretical 1. Curve theoretical 2 was obtained by

assuming confined concrete properties for the whole section and including the top cover

layer. Curve theoretical 2 was an upper bound solution of the tube beam.

The improvement in the ductility of the tube beam compared to the control beam

was evident when the experimental M-D curves for both beams were compared (See Fig.

4-25). The area under the load-displacement curves represents the amount of energy a










structure can absorb before failure. The amount of energy is also a good indicator of

ductility. Ductile structures usually can absorb higher amounts of energy compared to

non-ductile (brittle) structures.

500

400

,300

S200
-- Exp. Mid-Span
-- Theoretica 1
100 -E- Exp. South Load
-6- Fiber Model
S-8- Theoretical 2

0 0.0002 0.0004 0.0006 0.0008 0.001
Curvature (rads/in)

Figure 4-24. Experimental and theoretical M-PD curves for tube beam

The areas under the experimental moment-curvature curves, of both beams, were

calculated and compared. The area under the load-displacement curve of the tube beam

was approximately 37% more than that of the control beam. The energy up to peak load

was elastic energy while the energy post peak was inelastic. Therefore, the 37% extra

energy was primarily inelastic energy which indicated the ability of the tube beam to

undergo inelastic deformation contrary to the control beam.

Ductility Factors

The displacement ductility factor ([tA) and the curvature ductility factor (to,) were

used to determine the ductility of the grid beams. Details on the definition of the ductility

factors (Equations 2-2 and 2-3) as well as definitions for of ultimate and yield

displacements or curvatures are found in chapter 2.

The ductility factors calculated based on the energy and deformability methods,

described in detail in chapter 2, can not be directly compared to the ductility factors for










steel reinforced concrete. The reason is because they are based on different approaches.

For the case of the CFRP grid reinforced concrete a method that can produce ductility

factors in the spirit of the ductility factors for steel reinforced concrete is needed. Such a

method will be a measure of the plastic deformations of the FRP reinforced structure that

take place due to concrete confinement.

500

400

S300

S200

100 -+- Control
-e- Tube

0 0.0002 0.0004 0.0006 0.0008 0.001
Curvature (rads/in)

Figure 4-25. Experimental M-D curves for both beams

The following method, to determine ductility factors for CFRP grid reinforced

concrete is recommended. Because the mode of failure for the grid reinforced structures

is concrete crushing and not yielding of steel there is a need for a new parameter that will

replace yield displacement or curvature in the ductility factors. This need is especially

evident in the case of concrete structures with FRP flexural reinforcement. The new

parameter to replace yield displacement or curvature is named displacement or curvature

at crushing (6c or Oc). This follows the same logic as the yield displacement or curvature.

For the yield displacement or curvature first yield is used to define the displacement or

ductility while for the CFRP grid reinforced structures first crushing is used. First

crushing is defined as the point at which the load causes the cover concrete to spall which

is assumed to happen at a concrete compressive strain equal to 0.003 (ACI Committee










318, 2002). Any further activity beyond the 0.003 strain is considered contribution of the

concrete confinement to the ductility of the structure. The capacity of the structure at a

compressive concrete strain of 0.003 is the ideal capacity that is used to determine the

displacement or curvature at crushing spellingg) using the same procedure used for

determining the yield displacement or curvature. The ultimate ductility was determined in

the same way as discussed in chapter 2 based on Park and Pauley (1975(b)) (see Fig. 2-

2).

The curvature ductility (up) was approximately 1.52 and 2.02 for the control and

tube beam respectively. The schematic for determining 0, and "c for the control beam is

shown in Fig. 4-29. Ideal moment (M,) is the moment at a concrete compressive strain of

0.003. The same approach was used in determining the ductility factor for the tube beam.

The curvature ductility of the tube beam was approximately 33% higher than the

curvature ductility of the control beam.

500

400

J300. :-

1 200--------

100


0 0.0002 0.0004 0.0006 0.0008 0.001
Curvature (rads/in)

Figure 4-26. Curvature ductility factor for control beam

Using the same approach used to calculate the curvature ductility factor the

displacement ductility factors of the two beams were calculated. They were

approximately 1.33 and 1.55 for the control and tube beam respectively. The









displacement ductility of the tube beam was approximately 17% higher than the

displacement ductility of the control beam.

Both ductility factors identify the ductility improvement that was evident from the

load-displacement curves and at the same time quantify it as been 17% or 33% depending

on the ductility factor used.

The curvature ductility factor using the fiber model moment-curvature diagram of

the control beam was approximately 1.58 which was approximately 4% higher than the

experimental. On the other hand, the curvature ductility factor of the tube beam was

approximately 2.56 which was an overestimate of approximately 27%.

The fiber model curvature ductility factor for the tube beam was an overestimated

compared to experimental curvature ductility factor. Than can be due to failure of the

CFRP grid at lower strain than the one assumed in the fiber model that used a stress-stain

curve for grid confined concrete based on grid cylinder tests. However, only one beam

was tested and therefore it is unknown whether the fiber model consistently overestimates

the curvature ductility of CFRP grid confined beams.

Conclusions

In this chapter the testing of two compression controlled concrete beams was

described and results from the tests were presented. The results from the experimental

results were compared to results obtained using two models.

Based on the results presented in this chapter the following conclusions can be

drawn:

* The results from the two beams indicate that the CFRP grid provided confinement to
the concrete. Confinement was achieved using a series of small diameter CFRP grid
tubes rather than wrapping the entire cross-section.









* There was a nominal increase in the peak load of the tube beam of approximately 3%
compare to the control beam. The load increase was considered minor.

* The displacement ductility of the beam utilizing the CFRP grid tubes was improved
by 17% compared to the control beam with no grid tubes. This was due to concrete
confinement provided by the CFRP grid.

* The curvature ductility of the beam utilizing the CFRP grid tubes was improved by
27% compared to the control beam with no grid tubes.

* The average improvement in the ductility of the tube beam was significant,
approximately 25% increase, considering the small amount of CFRP that was used to
confine the compression zone.

* The energy dissipation of the tube beam was 37% higher compared to the controlled
beam due to the effect of concrete confinement. This increase in the energy
dissipation of the element also represents an improvement in the ductility due to
concrete confinement from the CFRP grid tubes.

* The beam model used predicted the capacity and behavior of the beams. The
difference between the experimental and predicted peak loads was 2%. The beam
model was also accurate in predicting strains in both the concrete and the steel. The
difference between the experimental and theoretical strains was less than 20% with
the exception of the lower loads (22 and 46 kips) of the tube beam that the difference
tended to be approximately 36%.

Based on the test observations and data presented in this chapter the following

recommendations are offered:

* This technique could potentially be used in cases were dimensional restrictions
prevent the design of concrete structural elements according to the relevant codes.
The CFRP grid tubes can potentially improve the ductility to the extent that the
structural element meets the requirements and specifications of the relevant structural
code.

* Cover concrete to the CFRP grid tubes should be kept to a minimum to minimize the
loss of capacity to the beams when the unconfined cover concrete crushes.

* If the option to assign different concrete properties to different sections of a concrete
structural element is added to the theoretical M-0 program it could became a very
helpful tool in design and prediction of structural behavior of carbon reinforced
concrete elements that use CFRP grid confinement.














CHAPTER 5
CAST IN PLACE CONCRETE SECTIONS WITH FRP BARS AND GRID

Introduction

To investigate the behavior of concrete piles reinforced with FRP bars and carbon

grids four 20-ft pile specimens were constructed. The piles were constructed and tested in

flexure to demonstrate the feasibility of ductility improvement of a non-ductile pile

through concrete confinement using a CFRP grid.

The pile specimens were cast in place and were produced in two shapes (round and

square). The specimens were divided into two groups. Group 1 (specimens 1 and 2)

included one square and one round specimen reinforced with GFRP bars and CFRP grid.

Group 2 (specimen 3 and 4) included 2 round specimens reinforced with CFRP bars.

Only one specimen (specimen 4) was reinforced with the CFRP grid.

Group 1 specimens were tested in four point bending configuration. For group 2,

specimen 3 was tested in four point bending configuration while specimen 4 was tested in

three point bending configuration.

The higher ductility factors of specimens 1 and 2 and 4 (grid reinforced) compared

to specimen 3 (no grid reinforcement) indicated a ductility improvement due to the

confining effect of the CFRP grid. The experimental displacement ductility factor of

specimen 4 was approximately 1.73 times the ductility factor of specimen 3.

Approximately the same improvement was observed when comparing the experimental

curvature ductility factors of specimens 3 and 4. The curvature ductility factor of

specimen 4 was 1.67 times the ductility factor of specimen 3.









Experimental Program

Pile Specimen Construction

Table 5-1 contains details of all four pile specimens constructed. The specimen

variables included shape, type and size of reinforcement and use of CFRP grid.

Table 5-1. Specimen details for cast in place pile specimens
Specimen Shape/Size Flexural FRP bar No of CFRP
reinforcement size grid layers
(in.)
1 Square/16 in. 8 GFRP bars 0.75 2
2 Round/16 in. 8 GFRP bars 0.75 2
3 Round/16 in. 12 CFRP bars 0.375 0
4 Round/16 in. 12 CFRP bars 0.375 2

The total length for both specimens 1 and 2 was 20 ft (see Fig. 5-1). Specimen 1

had a square shape but a tubular reinforcement arrangement (see Fig. 5-2(a)) because it

was easier to form the grid in that shape. Specimen 2 had a tubular shape and a similar

reinforcement arrangement as specimen 1 (see Fig. 5-2(b)). The longitudinal

reinforcement for both piles was eight 0.75-in. diameter GFRP reinforcing bars.

Centerline




1 Grid Layer 2 Grid Layers 1 Grid Layer
7' 6' 7'

20'


Figure 5-1. Longitudinal view of specimen 2

Specimens 3 and 4 also had a length of 20 ft. Both specimens had identical

reinforcing bar arrangements. Twelve 0.375-in. diameter CFRP reinforcing bars were

used as longitudinal reinforcement in specimens 3 and 4 (see Fig 5-3). Most CFRP bars

were placed in bundles of two (see Fig. 5-3) at the bottom of the piles to force a










compression failure. Specimen 3 had no grid in the 6-foot center section of the length

(see Fig 5-4) while specimen 4 had identical CFRP grid arrangement as specimen 2 (see

Fig. 5-4).


S 0.5" clear
-I----


I I


Figure 5-2. Cross-sectional view: (a) specimen 1 and (b) specimen 2


12.5" 12.5"

SBending axis Bending axis

OD 0 C o OD OD OD 00 OD

I CFRP grid


(a) (b)

Figure 5-3. Cross-sectional view at mid-span: (a) specimens 3 and (b) specimen 4

Specimens 3 and 4 also had a length of 20 ft. Both specimens had identical

reinforcing bar arrangements. Twelve 0.375-in. diameter CFRP reinforcing bars were

used as longitudinal reinforcement in specimens 3 and 4 (see Fig 5-3). Most CFRP bars

were placed in bundles of two (see Fig. 5-3) at the bottom of the piles to force a










compression failure. Specimen 3 had no grid in the 6-foot center section of the length

(see Fig 5-4) while specimen 4 had identical CFRP grid arrangement as specimen 2 (see

Fig. 5-3).

Centerline


616

1 Grid Layer No Grid 1 Grid Layer
7' 6' 7'

20'


Figure 5-4. Longitudinal view of specimen 3

All specimens were cast using a standard concrete pump mixture with a maximum

aggregate size of 0.375 in. The specified 28-day compressive strength of the mixture was

5000 psi.

Round Sonotubes, 16-in. diameter, were used as formwork for specimen 2, 3 and 4

(see Fig. 5-5). Wood formwork was used for specimen 1 (see Fig. 5-6).



I7baaa/


Figure 5-5. Placement of concrete (specimens 2, 3 and 4)









Test Set-Up and Procedure

Specimens 1 and 2 were tested in a simply supported four-point bending

configuration. The span length was 18 ft and the loads were applied 6 ft from each

support (see Fig. 5-7 and 5-8). Specimen 3 was also tested in a simply supported four-

point bending configuration with loads applied at third points (see Fig. 5-9). However,

the instrumentation for specimen 3 was different than the instrumentation of specimens 1

and 2 (see Fig. 5-9).


Figure 5-6. Placement of concrete (specimen 1)

Actuator 1 Actuator 2
DlI D10 D9 D8 D7 D6 D5 D4 D3

t ( |Emt Et C


D2 D1


II -I I
South North
Support LVDT Support


Figure 5-7. Schematic of test set up for specimen 1








Compression failure was the target failure mode for all specimens. Specimen 3,
however, failed in flexure-shear. Consequently, a simply supported three-point bending
configuration was adopted for specimen 4 to force a flexure failure mode (see Fig 5-10).
Actuator 1 Actuator 2
D11 D10 D9 D8 D7 D6 D5 ID4 D3 D2 D1


Figure 5-8. Schematic of test set up for specimen 2

D21 D20 D19 D18 D17 D16 D1 14 D13 D12 Dll D10 D9 D8 D D6 D5 D4 D3 D2 D1

I 6@12" 8 @ 9" 6 12"


T


6' 6' 6'
I I


ml


I I -I
South North
Support LVDT Support

Figure 5-9. Schematic of test set up for specimen 3
For the four-point bending configuration two hydraulic actuators were used to
apply the displacements to the piles at approximately the same rate. Load cells were used
to measure the applied force. The loading configuration created a 6-ft constant moment


I







region in the center of the span, which allowed evaluation of the pile behavior in pure
flexure. Displacement for the three-point bending configuration was applied to the pile in
a similar manner as for the four-point bending case using a single hydraulic actuator. The
displacement rate was approximately 0.034 in/sec for specimen 1 and 0.0154 in/sec for
specimen 2. For specimens 3 and 4 the displacement rate was 0.008 in/sec.

D21 D20 D19 D18 D17 D16 D15 D14 D13D12 D1 0 D D9 D8 D7 D6 D5 D4 D3 D2 D1

6I 6@12" 8 @ 9" 6 @ 12"


Th


9' 9'
A I 5


South North
Support LVDT Support

Figure 5-10. Schematic of test set up for specimen 4
Steel saddles were used for all round shaped piles at both the support and load
locations. The saddles followed the shape of the pile and evenly distributed the load
while at the same time providing stability for the specimens.
Instrumentation
Eleven displacement transducers (LVDTs) were used to measure the displacement
of the piles at different locations for specimens 1 and 2. The LVDTs were spaced at 2 ft
intervals outside the constant moment region and 1.5 ft intervals inside the constant
moment region. The LVDTs were labeled from north to south as Dl through D11 (see
Fig. 5-7 and 5-8).


4






80


For specimens 3 and 4, a total of 21 LVDTs were used to measure the

displacements. The LVDTs were spaced at 1 ft intervals outside the constant moment

region and 9 in. intervals inside the constant moment region. The LVDTs were labeled

from north to south as Dl through D21 (see Fig. 5-9 and 5-10).

Data from all instrumentation devices were recorded using a data acquisition

system at a rate of 1 Hz.

Material Properties

To obtain the strength of the concrete used in piles tested, 6 x 12 in. concrete

cylinders were cast and tested in compression. The cylinders were tested on the same day

that the respective piles were tested. A total of 8 cylinders were tested using a cylinder

test machine. All cylinders were capped using sulfur as capping material. Table 5-2

contains the results from the cylinder tests.

Table 5-2. Results from cylinders tests
Pile Cylinder Peak Aver.
Specimen stress stress
(ksi) (ksi)
1&2 1 6.78 6.62
2 6.46
3 1 5.54 5.60
2 5.63
3 5.64
4 1 6.08 6.15
2 6.10
3 6.28

The physical and mechanical material properties for the flexural FRP reinforcement

were obtained from the manufacturer (Hughes 2002(a); Sika 2003) while the properties

for the CFRP grid were obtained through testing as described in Chapter 3. The

properties (diameter, cross-sectional area, tensile strength and modulus) of the FRP

materials are presented in Table 5-3.









Table 5-3. FRP reinforcement material properties
Type Dia. Area Tensile Modulus Elongation
(in.) (in2) Strength (ksi) at rupture
(ksi) (%)
Glass Rod 0.750 0.4580 90 5900 2.00
Carbon Rod 0.375 0.1100 405 22500 1.80
Carbon Grid N/A 0.0097 100 9200 1.05

Results, Observations and Discussion

The load displacement curves (Fig. 5-11) for specimens 1 and 2 have 3 distinct

areas. The initial portion of the curves is linear up to first cracking, which occurred at

approximately 7.5 kips for specimen 1 and 5.5 kips for specimen 2. After cracking the

slopes are reduced due the reduction in cross-section stiffness from flexural cracking yet

remain linear up to the plateau. The plateau seen in the load-displacement curves (see

Fig. 5-11), was attributed to a combination of the following three factors: (1) concrete

confinement, (2) the post peak curve that GFRP bars exhibit prior to rupture and (3) the

shape of the cross-section of the piles. The shape of the cross sections was tubular for

both cases once concrete spelling took place. The square pile had a tubular reinforcement

arrangement and therefore once the cover concrete spalled it had the same compression

zone shape as the round pile. That was the reason the square pile had a plateau associated

with its load-displacement curve. For specimen 1 a noticeable loss in capacity was

observed before the plateau which was attributed to spelling of the top cover concrete.

The information available by the manufacturing company of the GFRP bars

indicated a post peak curve for the bars (Hughes 2002(a)). Chaallal and Benmokrane

(1996) reported that the GFRP bars they used in concrete beams also exhibited some post

peak behavior rather than rupturing at peak load.











60

50

40

30-

20
-8- Specimen 1
10 --A- Specimen 2

0
0 2 4 6 8 10 12
Displacement (in)


Figure 5-11. Load-displacement curves for specimens 1 and 2 (mid-span)

The top cover concrete, outside the grid encasement, crushed (spalled) (see Figs 5-

12 and 5-13) but the concrete core enclosed by the CFRP grid maintained its shape and

did not spalled. This was an indication of some confinement had been provided by the

CFRP grid.


Figure 5-12. Crushed cover concrete (specimen 2)


Figure 5-13. Specimen 2 after the end of the test