A Survey of existing building facilities and conditions of Rolf's Hall
ALL VOLUMES CITATION SEARCH THUMBNAILS MAP IT! PAGE IMAGE ZOOMABLE
Full Citation
STANDARD VIEW MARC VIEW
Permanent Link: http://ufdc.ufl.edu/UF00102908/00003
Finding Guide: Historic Preservation Documents
 Material Information
Title: A Survey of existing building facilities and conditions of Rolf's Hall
Series Title: A Proposal for the adaptive use of Rolf's Hall
Physical Description: Archival
Language: English
Creator: Myers, John
Manning, Ray
Gonzalez, Sergio Jr.
Publisher: John Myers
Place of Publication: Gainesville, Fla.
Publication Date: 1976
 Subjects
Subjects / Keywords: Architecture -- Florida   ( lcsh )
Architecture -- Caribbean Area   ( lcsh )
Historic preservation
Coordinates: 29.649239 x -82.344518
 Notes
General Note: UF AFA Historic Preservation document 181
 Record Information
Source Institution: University of Florida
Holding Location: University of Florida
Rights Management: All rights reserved by the source institution and holding location.
Resource Identifier:
Classification:
System ID: UF00102908:00003

Table of Contents
    Title Page
        Page 1
    Table of Contents
        Page 2
        Page 3
    First floor
        Page 4
        Page 5
        Page 6
        Page 7
        Page 8
        Page 9
        Page 10
        Page 11
        Page 12
        Page 13
        Page 14
        Page 15
        Page 16
        Page 17
        Page 18
        Page 19
        Page 20
        Page 21
        Page 22
        Page 23
        Page 24
        Page 25
        Page 26
        Page 27
        Page 28
        Page 29
        Page 30
    Second floor
        Page 31
        Page 32
        Page 33
        Page 34
        Page 35
        Page 36
        Page 37
        Page 38
        Page 39
        Page 40
        Page 41
        Page 42
        Page 43
        Page 44
        Page 45
        Page 46
        Page 47
        Page 48
        Page 49
        Page 50
        Page 51
        Page 52
        Page 53
        Page 54
        Page 55
        Page 56
        Page 57
        Page 58
        Page 59
        Page 60
        Page 61
        Page 62
        Page 63
        Page 64
        Page 65
        Page 66
        Page 67
        Page 68
        Page 69
        Page 70
        Page 71
        Page 72
        Page 73
        Page 74
        Page 75
        Page 76
        Page 77
        Page 78
        Page 79
        Page 80
        Page 81
    Third floor
        Page 82
        Page 83
        Page 84
        Page 85
        Page 86
        Page 87
        Page 88
        Page 89
        Page 90
        Page 91
        Page 92
        Page 93
        Page 94
        Page 95
        Page 96
        Page 97
        Page 98
        Page 99
        Page 100
        Page 101
        Page 102
        Page 103
    Fourth floor
        Page 104
        Page 105
        Page 106
        Page 107
        Page 108
        Page 109
        Page 110
        Page 111
        Page 112
        Page 113
        Page 114
        Page 115
        Page 116
        Page 117
        Page 118
        Page 119
        Page 120
        Page 121
        Page 122
        Page 123
        Page 124
        Page 125
        Page 126
        Page 127
        Page 128
        Page 129
        Page 130
        Page 131
        Page 132
        Page 133
        Page 134
        Page 135
        Page 136
        Page 137
        Page 138
        Page 139
        Page 140
        Page 141
        Page 142
        Page 143
        Page 144
        Page 145
        Page 146
        Page 147
        Page 148
        Page 149
        Page 150
        Page 151
        Page 152
        Page 153
        Page 154
        Page 155
        Page 156
    Slide list
        Page 157
        Page 158
    Appendix
        Page 159
        Page 160
        Page 161
        Page 162
    Bibliography
        Page 163
        Page 164
        Page 165
        Page 166
        Page 167
Full Text
UNIVERSITY OF FLORIDA, COLLEGE OF ARCHIITECTURE
AE- 683 TECHNOLOGY OF PRESERVATION 111, SPRING 1977
PRESERVATION PROGRAMh, GAINESVILLE, FLORIDA









A SURVEY OF EXISTING BUILDING FACILITIES AN~D CONDITIONS OF:


PREPARED BY:
SERGIO GONZALEIZ JR.
RAY MAN1NINGr
JOHN MYERS


PHILLI~P WISLEYT, INSTREUCIOR


F~rObFS ~


HA P~LLS












TABLE, OF CONTENTS:


PART 1 GROUND FLOOR


PART 11 SECOND _FLOOR


PART 111 THIRD FLOOR


PART IV FOURTH FLOOR


PART V ATTIC FLOOR


PART Vl ROOF CONDITIONS


PART Vll WE~ST W~ALL FASCADE


PART V111 SITE CONDITIONS


PART 1X COLDR SLIDES AND LIST


PART X APPENDIX AND ORIGINAL PLATES








-~~~rr~l srm us wsI us vesr vniaa es et u eay aeu


IIlIB "3oK
IlllII -



na. sol udl i-
assBBsa
PE~ar FIEL



noLM on sll sson
EOt 0~


so LOT IsFREE ist OU savia
GE.7
ALS aso o r
I.c ruLrrrs

SORO TIE

a~d RES B C o o n

BU RI~

;Eat 9 P Rill tNG L n










..Uon 'eZ 5et onT see
sw*nr vsU



ooauJULYr I, 1976 RETIC D *L ARE I 0





r~a CMP





1 ST F LOO R





Description

Plaster ceiling painted
white.2 Suspended flou-
rescent light fixtures.
An exposed electrical
cable runs thru the ceil~
ing. An exposed metal
duct also runs across
the ceiling.

Concrete block plaster
wall divided into three
sections one by a picture
moulding and another moul
ing approx 3 1/2' from
the floor.0riginal wood
door is blocked by the
east wall partition.A
pipe runs horizontally
just below the picture
frame moulding.

Wood stud partition with
2 doors leading to two
separate rooms.An expose
duct is visible approx.1


Conditions

Ceiling is in good condition.







Wall is in excellent condition
except for blocked door which
has been left exposed.


Recommendations

None


Remove door or cover with wall
material.


None


Wall is in good condition

'h.


Area


Ceiling I


North wall


East wall


(i~)


Final Exercise
A1E-683
Spring, 1977


School of Architecture-Department of Preservation
University of Florida -Gainesville,florida


n7 Room


University of Florida
n Survey of existing Const-ruction "


( )





































Floor is in very poor condition
with many tiles broken and
damaged beyond repair.



Door is in excellent working
condition. Varnish has worn of:
in some areas especially around
door handles.


Entire floor must be replaced
or covered with carpet or
Other type of flooring.


Plaster is cracking on the lef
side of wall,Apparently there
was a previous opening that ha
since been filled.The wall haE
many scratches and markings.


Eliminate cracks on wall '
and replaster. Repaint entire
wall except for top white
portion which is in good
condition.


Wall in general is in good
condition.Some nail holed
and dirt marks are visible.


Clean wall and remove small
exposed nails and repaint if
necessary.


Concrete plaster wall.
Electrical outlet with
exposed cables running
thru wall.Two recessed
wood cabinets approx.2x3
are on the wall.An elec-
trical cable runs verti-
cal from picture mould-
ing to about 2'and then
it runs into hole in
wall.


Concrete block plaster
wall with entrance door
and exposed metal duct
and an a/c grille.Pic-
ture moulding at approx.
10'frome floor and a
moulding at 3 1/2' from
floor.Column projected
from center of wall.
Electrical switches alsc
on this wall,with expose/
electrical cable. Tele-
phone boxes .are also
exposed on this wall.


Floor is of vinyl tiles
approx. 8x8" in size




Wood frame door with a
translucent glass panel
above.A return air gril
is at the lower half of
door.


Revarnish door.





~T I -i


II


Door on
East wall


Wood frame door


Door is in good condition


None


WOOD:

a) baseboard


b) picture
moulding

c) moulding
3 1/2'
from floo2


Wood baseboard along en-
tire perimeter of wall.

Wood picture moulding


Wood moulding


Clean baseboard and revarnish
if necessary.

None


None


Baseboard missing on portions
of wall. Dirt is also evident.

in good condition


in good condition
















Description


Plaster ceiling painted
white. Two suspended
flourescent light fixtur


Concrete block plaster
wall with an a/c grille
at the center. A door is
on this wall leading to
adjacent office.


Conditions


Ceiling is in good condition
except for some paint peeling.

Walli ngo odt




Wall is in fil good conditin



tion with the exception of som
wall peeling off.


Recommendations


Scrape paint and repaint with
good quality paint.


Scrape peeiling paint and repal
affected areas. Paint entire wal
if necessary.


I I


Room


ROL F SHALL
University of Fl3or~ida

" Survey of existing Construction "


Area


Ceiling


None


North wall


East wall


Concrete block plaster
wall with entrance door.
Columnn projects from
wall. An a/c grille is
located above door.Expo-
sed telephone cables
and exposed boxes.Elec-
trical are also exposed.
A wood wall cabinet is
suspended on wall.


-





None











None







Machine clean and waxing is
necessary.




None



Revarnish door.







None


Concrete block plaster
wall with door opening.
Wps a door oroginaly
leading to an adjacent
room which now is divided
into two.A wood cabinet
is mounted on wall. Expoi
sed electrical cable.Des1
with back splash is also
fixed on wall.


Wood partition with wood
closet and doors.A wood
frame door leading to
adjacent room is also
on this wall.


Partition is in good condition


Wood frame door with a
translucent glass panel
with wood frame glass
transom above. A return
air grille is at the
lower half of door.


Wood frame door


Door is good working condition
except for varnish which is
worn off especially at the door
handle.


__


fSouth wall


Wall is in good condition.


West wall


Floor


Vinyl tiles approx.8x8" -
in size.


Floor has many scratches and
markings .


Door on
north wall


Wood frame door


In good condition


Door on east
wall






Door on
west wall


in good condition






'WOOD:

a) baseboard


b) picture
moulding

c) moulding


ti II -


~I


Clean baseboard and revarnish
if necessary.

None


None


wood baseboard along
entire perimeter of wall.

Wood


Wood moulding approx.
3 1/2' from floor.


|Baseboard is in good condition
except for some dirt .

in good condition


in goog condition

















Description -


Conditions


Suspended ceiling is in good
condition with only a slight
warp in one area. One of the
light fixtures not working at
full capacity due to a burn
out lamp.


Recommendations

The warp in the ceiling should
be investigated to determine
cause. Light fixture should be
checked for lamp replacement.


:Remove, nails and cover holes.
Wall should be repainted to
cover hole markings ahd also
scratches due to footmarks and
furniture. Some areas can be
washed and no painting would
be necessary.


Wall should be repainted to
eliminate all markings.


Acoustical tile suspen-
ded ceiling with conceal
ed track.tiles are 1x1
asbestos. Wood square
trim approx 2'x2' in clg
for access to plenum.2
flourescent light fix-
tures. Exposed a/c ducts
This ceiling is not ori-
ginal to building.
1/4 round wood trim at
ceiling perimeter.


Wood stud wall partition
with drywall.This wall
is not original to build
ing. A few nails are ex-
posed.



Concrete block wall with
plaster finish. Column
proj ecting from wall.
Entrance door from cor-


The plaster on wall is in good
condition. Areas near the floo
have scratches and markings of
shoes and furniture.


Floor


!z f


ROLFS HALL
University of Florida

" Survey of existing Construction "


Area


Ceiling


This wall is in good condition
except for exposed nails'.


North Wall


East wall





Description


Plaster ceiling painted
white.2 exposed heating
pipes thru ceiling.0ne
suspended flourescent
light fixture.

Wood stud partition.This
partition is a later
addition and not original:
to room or building.


Concrete wall with window
opening. Two exposed hea
ing pipes run vertically
in front of wall.Electri
cal outlet with exposed
conduit,


Concrete plaster wall
divided into three sec-
tions by a picture mould
ing at 10' from floor an


Conditions



In very good condition




Wall is in good condition.





Wall is in good condition exce
-for some markings on the lower
portion of wall.


Recommendations


None




None


ptClean all markings from lower
Portion of wall.


Wall has numerous small holes
with expansion bolts. Some nai
are also exposed on wall sur-
face. Markings such as scratch


Remove all expansion bolts
s and exposed nails.Cover all
holes with plaster and-repain
s entire wall except for top


-J


Area



Ceiling


North Wall


East Wall


South Wall


13)


Exercise
School of Architecture-Department of Preservation
-683 University of-Florida -Gainesville,florida
e-1977


n oom


ROL F SHALL
University of Florida

" Survey of existing Const-ruction "




















Entire floor must be replaced
or covered with carpet or othe
type of flooring.


Wood stud partition with
entrance door and a a/c
grille above the door.


Floor is~of vinyl tiles
approx. 8x8" in size.


n Some cleaning is required.






Clean baseboard and revarnish
if necessary,

Add moulding to match those
existing,



None


2-double hung wood frame
windows with 9 glass pan/
on each frame.




Wood baseboard along the
entire perimeter of room

Wood picture moulding
approx. 10' from floor.



Wood moulding at approx.
3 1/2' from floor.


a wood moulding at about
31/2' from floor.


part of wall which is in
good condition.


t Clean wall.


Wood frame door


Revarnish door.


dirt etc. are also evident.
Electrical outlets with expose
cables run horizontally at the
top of the baseboard.Top secti
of wall is in good condition.


Wall is in good condition exce
for some dirt markings at the
lower part of wall.


Floor is in very poor condition
with nany tiles broken and
damaged beyond repair.


Door is in good operable con-
dition.Varnish is worn in
some areas. Hardware is in goo
condition.


Window is in excellent conditi
s and apparently working well.


Dirt accumulation is evident.


In good condition but missing
from north wall and west wall
due to due walls were added
later.Moulding is in good con-
dition.
In good condition






us1.
ridor located on this
wall. Light switch and
one electrical outlet
also is located on this
wall


The drywall is marked with
scratches of furniture and
shoes. In general this wall
is in good condition.


Wall should be cleaned and
repainted if necessary to cove'
all markings on wall.


Floor should be cleaned and
waxed for protection.






O,


Same as in east wall.


Same as in east wall.


Concrete block wall wit1
plaster finish.Part of
window is not visible
due to west wall and
bookcase obstruction.
West wall is in center
of room.Two electrical
outlets on this wall.

Wood stud partition and
drywall. This partition
wall is not original to
building and is located
in center of original
room. It is obstructing
the operation of a win-
dow.A door leading to
a second room is locates
on this wall.Three elec
trical outlets on this
wall. There is a hole
in the upper part of
wall with a/c ducts go-
ing thru to next room.
Vinyl asbestos tiles
8x8 squares withI white
and grey color.


South Wall


West Wall


Floor is in good condition
except for very few markings.


Floor







Window on
south wall


Wood frame double hung
window with 12 glass
panes on each window
frame. Upper part of
window is partially
covered by suspended
ceiling.Sun blind loca-
ted on the inside and
screen on the outside. E
stud wall is placed on
center of window obstruc
ting and impeding the us
of the window.Bookcase
in front of window is
also obstructing window.


This window in general, is in
good condition. Window is not
in service due to wall obstruc-
tion and is completely soiled,
in addition to blind and screen
It is not determined if window
can be placed into operation.
Paint on frame and window app-
rs to be in good condition.


This window should be put bac
into service. One way to do.
this is by removing wst wall
stud partition. It is poorly
placed and should be removed.
Bookcases also should be relo-
cated. Window should then be
thoroughly checked and put into
service once again.This window
would offer proper ventilation
for room in case a/c fails to
function,it also provides for
extra light to come into space.
Remove all peeling paint and
prime and repaint to restore
window. Glass panels should be
cleaned and checked for damage.


Door and glasspanel should be
restored to original condition
This can be done by careful
removing white paint from door
and by priming and revarnishin
until door total restored.
a/c grille on door should be
cleaned for better air cicula-
tion,


None~,(probably will be
removed if wall is removed as
recommended)





clean and repaint where neces-
sary to eliminate all stains.

None


Door is in excellent condition
Except for new paint on the
interior.This paint is not
original to door and therefore
it has affected original ap-
pearance. Glass panel above
door has also been painted
white. .



Door and frame in excellent
-condition,






in good condition but with man
shoe and furniture markings.

in good condition


Wood door with wood fra~-
me.Door is 1/2 glass &
1/2 wood with a return
air grille in lower cen-
ter panel.0perable glass
panel above door.Door has
original paint .on the
exterior and has been
painted white on interior

Wood hollow core door
with wood frame,Pencil
sharpner located on
right hand side of door,



8" baseboard on all wall


1/4 round on all corners
of room and ceiling.


Door on East
Wall


Door on wept
wall


WOO0D:

a)baseboard


b) 1/4 round

















Description


Conditions


Suspended ceiling is in excel
lent condition.


Recommendations



None


_ _


-Wall should be cleaned or re-
painted to cover all markings
and to cover scratches due to
shoe and furniture markings.


Wall is in good condition,
except for drywall markings.


Room


University of Florida

n Survey of existing Construction "


1214


Area


Acoustical tile suspended
ceiling with concealed
track.Tiles are 1x1 as-
bestos.Two flourescent
light fixtures in ceiling
This ceiling is not ori-
ginal to building.1/4
round wood trim at ceil-
ing perimeter.Two opening
in one corner of ceiling
with two pipes going thr
and another opening in
right side of ceiling
with one pipe going thru

Wood stud partition with
drywall. This wall is no:
original to building.
Line markings on wall
indicate drywall panels.
Blackboard is on wall.
Electrical outlets with
exposed conduits.


Ceiling


North Wall





Wall should be cleaned and
c repainted if necessary to
eliminate all markings.


Wall should be cleaned and re-
painted as necessary to elimi-
nate all markings.


Wood stud wall partitior
and drywall. This parti-
tion is not original to
building and is located
in center of original
room. It is obstructing
the operation of a win-
dow. A door leading to
previous room entrance
room is located on this
wall. A/C grille on up-
per center of room.
Bookcases and desks
mounted on wall. Three
electrical outlets with
exposed conduits on thiE
wall.


Concrete block wall wit
plaster finish. Part of
window is not visible
due to east wall locate<
in center of original
room.


Concrete block wall wi~t1
plaster covering. Three
windows openings on this
wall. Two exposed pipes
run in front of wall on
the left side and ano-
ther pipe runs in front
on the right side.
Bookcases and desks~are
mounted on wall. Three
electrical outlets with
exposed conduits.


Vinyl asbestos tile
12x12 inch squares.


in good condition


Remove nails and repaint wall:
This would also take care of
markings on wall.


Wall is in good condition witl
some exposed nails. Some mark-
ings due to shoes or furniture
also visible on wall.


East Wall


The plaster on wall is in goot
condition. Areas near the flo<
have scratches and markings
of shoes and furniture.


South Wall


Wall appears to be in good
condition with only surface
markings due to shoes and
furniture.


West Wall


Floor


Floor should be cleaned
and waxed for protection





1


Same window described in room
no.


Wood frame double hung
window with 9 glass
panes on each window
frame. Upper part of
window is partially
covered by suspended
ceiling. Sun blind on
the inside.


Wood hollow core door
with wood frame.


Window appears to be in good
condition except that they do
not appear to used regularly.
Blinds are being used to bring
light into ~space. All glass
panes are intact and look very
clean.



Door in excellent condition


None ( probably will be remove
if wall is removed as recommend
ded)




Clean and repaint where neces-
sary to eliminate all stains.

None


__ _


O


Same window described in room
no.




None


Window on
south Wall


Same window described it
room no.


Window on
West wall


Door on
East wall


WOOD:

a) baseboard


b) 1/4 round


8" baseboard on all wal:


1/4 round on all corners
of room and ceiling.


In good condition but with
many shoe and furniture
markings.
In good condition. -
















Conditions


This ceiling appears to be a
recent addition and is clean
and in good condition.Suspendes
ceiling has been installed ove:
existing wood trim on wall.


Plaster has shrinkage cracks
over total visible area. Plas-
ter appears to have been pain
ted several times. Exact caus
of cracks cannot be determined
immediately but they appear to
be caused by poor plastering
procedures and poor maintenance

PLaster in same condition as
in north wall.
Markings on previous door open
ings are due to compression.


Recommendations




None


Entire wall must be scrapped to
original surface. This would
eliminate all cracks. Wall shou
be replastered if necessary and
good quality paint to cover.


Plaster to be treated as in No.
wall.
Special precautions should be
taken in the new plaster appli-
cation to avoid door markings
from reappearing.


Description


Acoustical tile ceiling
(suspended)with exposed
metal track and 2x4 tile
with four recessed light
fixtures.


Plaster wall with window
openings.A 4' high wood
paneling and wood trim
approx. 10'high.There ar
two exposed pipes in
front of wall.one pipe
approx. 4" in dia. and
the other 1 1/2" in dia.


Plaster wall with a 4'h.
wood paneling and wood
trim approx. 10' high.It
is evident by markings
on wall and plaster that
there were 2 door open-
ings which are now <:
covered with plaster.


University of Florida

" Survey of existing Construction "


Area




Ceiling


North Wall


East Wall


~:~~ ~~





__


Plaster in same condition as
in noth wall.


11


Replace damaged tiles.



Must be maintained regularly,
such as waxing, polishing etc


Paint peeling off must be sc-
rapped and repainted.
Windows must be cleaned regu-
larly, and checked for rough-
ne~ss(their operation).Blinds an
screens also must be maintain
ed and cleaned,-Hardware must
be checked for rust and trea
ted if necessary with antirus
chemicals,


Wood frame double hungry
windows with 12 glass /
panes on each panel. up-
per part of windows are
partially covered by sus
pended ceiling. Sun bli-
nds on the inside of win
dow and screen on the
outside.


The condition is good. Some
squares must be replaced
which have been damaged by
heavy objects, heal marks,
or cigarrete burns. It is
poorly maintained due to stain
and dirt acumulation.

Windows are in operable con-
dition and all glass panes
are intact. Paint is peeling
off in many areas such as
around panes and on frame.
Blinds are in operable condi-
tion as well as screens.
Hardware is also intact with
no evidence of ware.Windows
are extremely poorly maintain-
ed due to heavy dirt acumula-/
tion .


I _


South Wall


Plaster in same condition as
in north wall.


Same as in north wall.


West Wall


PLaster wall with entr-
ahee door from corridor
and a 4' h. wood panel-
ing and wood trim appro:
10' h. Light switch on
right over paneling and
2 a/c grilles on top
end of wall. Wood stor-
age closet made of same
material as wood panel-
ing. This closet is
approx. 8' h. with shel
ves of wood.



Plaster wall with priv-
ate door leading to
office wiht a 4'.h. wd.
paneling and wood trim
approx. 10'h.


Same as in north wall.


Vinyl asbestos tile fl.
with 6x6 squares color
red and white.


Floor


Windows on
north wall






















1x3 wood baseboard with
2-1/4 rounds on floor &
wall

1x6 tungg &r groove ver-
tical approx. 4c'high wit1
1x3 trim and 1/4 round
moulding.

Approx.3/4" x 2" milled
trim and painted white
to match wall.


Door .is in excellent condition
and operating well. Varnish
around door handle worn due toi
use.



Baseboard in good condition.
Slight warp on east wall at
joint.

Trim in good conditions. Slight
ly loose on all walls. Chair
markings on paneling.


Trim in good condition. Trim
is separating -from south wall.
Two existing picture frame
mounts onwest wall and two
holes on east wall trim.


Door and frame should be
revarnished.




Clean and revarnish if neces-
s~ary .

Clean and revarnish to elimi-
nate markings. Reinforce trim
with proper nailing.


Remove picture mounts and cove
holes.Also cover holes on trim
on east wall. Re-nail loose
trim on south wall.












O,


Door and frame should be revak~
nished and return air grille
and cleaned regularly for pro-
per efficiency.


Door on
South Wall





Door on
West wall


Wood frame door with a
nontranslucent glass pa-
nel on half of door and
with an operable glass
panel independent to dool
above. Return air grille
mounted on lower half of
door.


Door is in excellent condition
and operating very well. Hard-
ware is also operable.Varnish
around door handle has been
worn due to use.


Wood frame door


Wood:

a) baseboard



b) Waincoat
paneling
and trim

c) Trim
wall be-
low clg.





ecormmendations


None









Repaint entire wall.






Reapaint entire wall


Ceiling is in good condition.









Wall is in good condition except for
many scratches and dirt marks.


Wall is in good condition except for
markings and scratches.


_ _ J


Roo.


ROL F SHA~LL
University of Florida

" Survey of existing Consl-ruction "


Area


Ceiling -


Conditions


North wall


East wall


Description


Acoustical tile suspended
ceiling with 2x4' tiles with
exposed track and two floue
cent light fixtures. An a/c
grille is installed in the
center of the ceiling.This
ceiling is no original to
room.


Wood stud partition with a
door leading to adjacent
office. Electrical outlets
are on this wall as well as
tel. box.


Concrete block plaster wall
with a wood moulding approx.
4' from floor. A door leads
to an adjacent office is
located on this wall. A light
switch is also on this wall.
Electrical outlets with ex-
posed conduits are on the waJ
A col.also projects on wall.


0>


r


Final Exercise
nE:-683
Spring 1977


School of Architecture-Department of Preservation
University of Florida -Gainesville,florida


I'


-











11


Wood frame door with a return
air grille at the bottom.


Floor is in very poor condition with
same tiles missing and same broken
beyond re~pair.


-----------~II


Remove white paint fran frame and
revarnish to original color.


__l __ __


Concrete block plaster wall
with a wood moulding at appro2
4' fran floor. A door opening
blocked by a plywood panel
is at the center of the wall.


Wall is in good condition except for
plywood on door opening.


Remove plywood and reinstall door at
door opening and repaint wall.


West Wa~ll


Floor


Vinyl
size.


tiles a~pprox.8x8" in


Install new floor.


Door on North
Wall


Door is in good condition.


None


.Door on East
wall


Wood frame
air grille
of door,


door with a return
at the lower half


Door is in good operable condition
Door frame was originally varnished
and was painted white later.


Door and frame are in very good con-
dition but can be restored. Trans-
lucent transa~n was eliminated and
plywood was installed. Door frame
has been painted with white paint
and some areas of frame has been
left with original varnished exposed.


Door on south
wall


Wood frame door with a trans-
lucent glass panel at the
upper half and a return air
grille at the lower half. This
door had a translucent glass
transom above just like other
doors in corridors. It has no
two wood plywood panels ins-
tead.

Door frame with no door
existing.


Remove plywood panels frar translucent/
transom. remove all white paint on
door frame and transom. Revarnish
door and frame.


Door on west
wall


Frame has been painted white.


Remove plywood panel fran door open-
ing and reinstall a door to match
that one on east wall. Remove white
paint from frame and varnish door and

frame




O1










































It_


Wood :


Baseboard is in poor conditions. Was
originally varnished in color and
has been painted white.
Moulding was originally varnished
nd now it is painted white.


Remove all white paint and revarnish


a) Baseb~oard


b) wood
moulding


Wood baseboard approx. 6" hig]
on entire perimeter of wall
and painted white.
Wood moulding approx. 4' from
Floor and painted white.


Ren~ove all white paint and revarnishec
Install missing moulding on south
wall .


OJ

















ecrmanendations


Clean all marks and repaint if neces-
sary.


Description


Concrete plaster ceiling with
two suspended flourescent
light fixtures and exposed
electrical conduits. Two heat
ing pipes are visible thru
ceiling .


Conditions


Ceiling is in good condition except
for samne minor scratches and marks.


11I


11


11i


Area


Ceiling _


Wall :'s in good condition except for
somne scratches and marks.


Clean all mawks and repaint if neceSsa


North wall


Concrete plaster wall with 3
window openings. Two heating-
pipes run vertically in front
of wall. Electrical outlets
with exposed conduits and.a
telephone box is on the wall.
Wall is divided into three
sections by wood mouldings.


Clean and repaint lower section of
wall .


East wall


Concrete block plaster wall
also divided into three sece
tions.Book cabinet is mounted
on this wall. A tel.box is
also on wall.


Wall is in good condition. Somne natsk
ings and scratches are on the wall.


n oom --


ROLFS HALL
University of Fl~orida

" Survey of existing Conlst-ruction "






















Same door as in roan 107
North wall.


Wood frame door with a door
missing.




3 Wood frame windows with 9
frames on each freme. Sun
blind is on the inside.




Wood baseboard approx.6' high
and runs entire perimetek of
wall .
Wood moulding approx. 4'high.


West, wall


Concrete plaster wall also
divided into three sections.
Door opening without door
but instead a plywood panel
to block opening.


Wall is in good condition.


None


Floor


Same as in room 107


Door on south
wall


Door on west
wall


;Plywxx1 panel has been installed to
replace door opening.Frane has been
Painted white when it was originally
varnished.


Wirxkws are in good operable condi-
tion ibut very dirty.


Remove plywood panel and reinstall
door .


Window on NJorth
wall .


Wood :

a.) baseboard


b) ~Moulding


c) Picture
moulding


Clean window properly.


In very
ginally
painted
In very
ginally
painted
In good


good conditionixd; was dri-
varnished except now it was
white .
good condition but was ori-
varnished except now it is
white .
condition.


Remove all nails and screws.Clean and
repaint if necessary.

Remove white paint and revarnish.


Wood picture moulding
10' fromn floor.


None .


approx .


0,

















SConditions


ailing is in good condition except
for same paint peeling around pipe.





In good condition



In good condition





In good condition


Reconunendations


iScrape peeling paint around pipne
and repaint.




'None



None


~I 1


11


Conrete block plaster wall
with two window openings. A
beating pipe is opposed on
the wall. Wall is also
divided into three sections
by .wood mouldings.


Roo.


RO ~L F SHALL41
Universi ty of Florida


" Survey of existing


Construction "


Area


Ceiling


tWorth wall


East wall


Description


Concrete plsater ceiling with
one suspended light fixture.
A heating pipe is visible thru
the ceiling.


Steel Wall with decorative -
wood paneling


S'tud wall with decorative
wood paneling. An; a a/c grille
is at the top of wall. A tel.
is mounted on the wall.


South wall



West wall


Concrete block plaster wall
divided into three sections
by wood mouldings.


Wall is in good condition





II


O


Vinyl asbestos tiles aprox.
8x 8"


Wood frame door


Floor


Door on west
wall


Window on east
wall


Wood :

a) baseboard

b) Moulding

c) Picture
Moulding


In good condition.


None


in good condition


None


Tw~o wood frame windows with
9 glass panes on each frame.
Sun blind is in the interior.


Clean windows.


Window is in good operable condition
except that it is very dirty.


Wood baseboard approx. 6" higl

Wood moulding 4' from floor.

Wood picture moulding approx.
10' frasn floor.


In~ good condition

In good condition

In good condition


Name

None

None





Description


Reconunendations


None


Conditions


_


Ceiling. /I


Same wall as East wall room
101


Concrete block plaster wall
with 3 window openings. Two
pipes approx. 4" in dia.run
vertically on this wall. Wall
is divided into three sections
by wood mouldings.Lower sectic
covered with wood paneling.


__


Roo.


Ceiling


Concrete plaster ceiling
painted white with two sus-
pended flourescent light
fixtures. Two pipes run thru


In good condition


North wall


Same wall as
in roomn 101


in south wall


East Wall


South wall


Wall is in good condition except
for exposed pipes.


None


C~


Exercise
-683
a 1977


School of Architecture-Department of Preservation
University of Florida -Gainesville,florida


T-


RO,~3LF HA ~LL
Universi ty of Florida

" Survey of existing Const-ruction "


Area





3`Wood frame windows with -
9 panes on each frame. Sun
blinds are in the inside.





Wood picture moulding approx.
10' fran floor and runs entire
perimeter of wall.


Windows appear to be in good conditic
and operating well.


Concrete plaster wall also
divided into three sections
A box covering pipes is
mountedon wall. Lower sector:
of wall is covered with
paneling. A wood cabinet is
mounted on the wall.


Wal is in good condition


None


West wall


Floor


Same as in rocam 101


Door on north
wall


Same door as
room 101


in south wall


Windows on
south wall


Wood :

a) picture
moulding


None


In good condition.





2 ND F LOO R












--


Description

Painted plaster with 2-
2x4' suspended flourescer
light .fixtures and one
heater pipe near the east
wall.


Pinted plaster wall with
picture moulding approx.
10' above the floor.


Conditions

The paint and plaster are in
good condition with only sligl
paint chipping off at the easi
wall intersection. The seal or
the pipe is out of position.


Paint in good condition but tl
plaster is in fair condition.
A poor plaster repair runs the
entire length of the wall
about 3' above the floor.


Nicks and chips have been
painted over and large cracks
are at the window opening. A
mount for the conduit has
chipped the wall in two places




Wall is in good condition.


Recommendations

Scrape paint at chipping area al
:apply good quality paint and sec
the loose seal in its proper
location.



ERemove the paint over the repa:
area and bring up to standards
then apply a good quality pain




Remove the paint from the
damaged areas, fill nicks and
repair cracked area then apply
a good quality paint.
Move conduit mount and repair
chipped area.


Two windows are at the
center of the painted
plaster wall. A picture -
moulding is about 10'
above the floor with a
phone hook up and conduit
near the baseboard.


11


Painted plaster wall.


University of Florida

SSurvey of existing Constructlion "


North wall


East wall


South wall


None


Room


Area


Ceiling
















The floor is in good condition
with only minor scratches. A
2' wide section of a sheet
vinyl has been installed in pL
of the tiles at the north end.


Windows are in good condition
and operating well with all
glass intact. Paint in good
condition but the hardware has
also been painted over. Paper
has been stuffed in one window
to stop wind rattling.



Recent installation in good
condition.


The base is in good condition
but the paint is chipping in
places.




The paint and base is in good
condition.


Uiean one smuagea areas or
the well wrth a suitable
cleaning solvents.




Replace the sheet vinyl with s
type tiles as the rest of the
floor.
ce


1x5" baseboard with
clamshell moulding on
top and 1 x 1/2" strip
at the floor. This base
is only on the east and
north walls.

1/4 round and 3" moulde<
baseboard is used only
on the south and west
wall.


Scrape chipping areas and
repaint with good quality pain





None


I-ne wall ana paint are in goo,
Condition with a smudged area
near the base. .


West wall


Floor


raLLaceal piascer wall wit]
a flush door at its cents
A 3x6' black board and
an a/c vent are also on
the wall.


8x8" vinyl asbestos tile
floor.


Windows on
the east wall


2 wood frame windows
double-hung withl2/12
panes on each frame and
9/9 on the other. Sun
blind on the interior.


Remove paint from the hardware
and treat with a antitrust
chemical. Repair the loose wini
to stop the rattle.


Door on
west wall


Flush wood door


None


Base





_II


I


Conditions


Paint and plaster are in good
condition except over the wind
where the plaster is chipping
off at the wall intersection
The seals at the points where
the pipes enter the ceiling
are out of position. At one
small area near the north wall
it appears paint was applied
over wet plaster with the
resulting cracks.and separatir
sheets of paint.


Recommendations


Repalce bad plaster above the
wwind~ow and scrape area where
it is chipping. Repaint repaired
areas with a good quality pain
and secure the pipe seals pro-
perly.


Painted plaster with 3
2x4' suspended flourescen
light fixtures.2 heater
pipes entering near the
northeast corner.


I I


Clean surface and touch up
paint if necessary.


RoomV


University of Florida

" Survey of existing Construction "


Area



Ceiling


Description


North wall


A 7' high partition inter
sects the wall at its
center with a 4x10' black
board on the east side.
The painted plaster wall
has a mounted desk that
extends from the partitic
to the west wall.


Recent paint and plaster is it
good condition with dirt and
black smudges being the only
problem.


~CE~


J





Piant is in good condition but
has been applied over existing
dents and writing in plaster.
Two areas of poor plaster
repairs are on the lower porti
of the wall and another is are
one side of the a/c vent. Dirt
and chair scratch marks are on
the lower portion with screws
located for pictures on the
wall on the upper portion.


Same condition as north wall



e Tiles appear to be a recent
installation and are in good
arcondition. The only problem i
a slight bulge in the surface
at the southwest corner.


The recent paint is in good
Condition but has not been
applied behind the heater.
Where the heater pipes enter
bwthe wall. The plaster around
the hole is in very rough
condition.


Windows are in operable condi-
Stion with all glass intact~.
Paint is in fairly good condi-
tion but is very grainy on the
.sills.Painted hardware is inta
except-for the handles on-one
window and a broken sash cord.
Numerous holes are in the fram
and the sill.Paint build up
are over many areas. A 6" wide


12x12" vinyl asbestos ti
floor. The two heater
pipes enter the floor n
east wall.


Remove tiles over the buldge
and locate the problem,repair
and replace the existing tiles


----~------ II


Sand the window sill, remove
paint build up and paint runs.
Remove the paint from the har
ware and replace the missing
titems. Fill all holes and re-
place the plywood with the
proper moulding. Repaint
frame and window with
a good quality paint.
(,J


A painted plaster wall
with a transom and door
at the center along with
a a/c vent.


Plaster over dents and marks
after paint removal and bring
plast-er repair areas up to stan
dards. Paint wall with a good
quality paint.
nd


West wall


South wall


Same as north wall


Same as north wall.


Floor


East wall


Apply the same type of paint
behind the heater and repair
the plaster around the pipes
that enter the wall and provide
seals.


Two windows on a painted
plaster wall with a heat
pipe in front of it Near
the north end.A heater
is located below the win
with two of its pipes
entering the wall just
above the baseboard.


Two wood frame double
hung windows with 12'/12
panes. Sun blind are on
the inside of the window


Windows on
the east
wall























1x5 wood baseboard with
clamshell moulding on to
and 1/4 round on the flo
his type base is only ~on
the east and west wall.


piece of plywood has replaced
the two moulding strips betwes
the windows.A small piece of
moulding has been placed
between the window moulding
below the window sills.


The door and transom work well
and are in good condition. The
hardware is intact and in good
condition. The paint is in goc
condition but a few nail hole
are in the frame and door. A
few of the seams are seperatir
on the door and the moulding
is coming loose on the transom

In fair condition on the west
Wall with a few nails holesat
ra 6" section reproduced in
concrete to match the wood
baseboard.The east wall base-
board is'in poor condition
with a large number of holes
and is separating from the
wall for most of its length,
Two heater pipes enter the
wall and the base was badly
notched to allow clearance.

In good condition
ter



A recent addition and in good
-condition with only dirt and
black smudges on its lower
portion.


The base on the east wall shou
be completely -replaced due to
its poor condition or a great
deal of repair work is needed.
Replace the imitation concrete
base with the original type
and paint to match. All holes
should be filled and the notch
should be sealed at the pipes.
A good quality paint should
then be applied.


Wood frame door with a
translucent glass panel
on the upper half of the
door.A return air grille
is located on the lower
panel and a transom is
above the door.


Holes should be filled and the
moulding secure in place.The sc
operation should be repaired
then the door should be repaint
with a good quality paint.


Vinyl base is on the
north and south walls an
the partition in the cen
of the room.


A 7' high stud wall pari
ticle board siding.A s1 /
ding door is at the cen
of the partition.


None


Clean dirt and marks
from the wall surface.


oi














I I I I


Description


A painted plaster- ceiling
with 2-2x4' surface moun-
ted flourescent light
fixtures. and 2 heater
pipes entering the surface
near the east wall.


Painted plaster wall witt
a painted picture mouldir
approx. 10' above the flc
A chair moulding is apprc
4' from floor.


2 Windows are in the cent
of a painted plaster wall
one pipe and a wall heated
are in front of the wall.
Various electrical out-
lets and conduit are on
the lower portion of the
wall.


Conditions


The ceiling is in good conditi
but the seals are out of place
at the point where the pipes
enter the ceiling.




The wall is in good condition
Sbut a few areas have slight
,rcracking in the paint.




!rThe paint is in good condition
but the wall is only fair.
A small poor plaster repair
.area and nicks are at the win
dow openings.


Recommendations


I Secure The seals on the pipes
in their proper location.


Scrape areas with cracking and
repaint with quality paint.




Paint should be scrapped from t:
damaged area and the nicks fill
then bring the repaired area up
to standards.


University of 'l~orida

" Survey of existing Construction "


Room


H















The wall and paint are in gooc
condition with a small amount
of dirt on the lower p-ortion
of the wall.


Clean the dirt from the wall
with a .suitable cleaning sol--
vent.


Unrepaired dents in floor cause
by heavy objects and black
stains due to dirt accumulatic


d Repair dents and attempt to
rekove stains, if this is
..not possible replace floor
material.



None



Replace the cracked glass and
remove the paint from the hard
ware and window frame. Fill the
holes and paint the frame and
Window with a good quality pain
Maintenance must be regularly
to assure long life.






O!


11


A recent installation that is
in very good condition.


Windows are in operable condi-
tion with one cracked pane. .
The hardware is painted but it
intact and operating well. Cut
tain brackets have been remov
from the frame and left hole
and an mismatched painted ares
An excess built up of paint is
on the frame which is over
unrepaired holes.


condition,


None


South wall


West wall


painted picture moulding
and chair moulding appro
10' and 4' above the flo
respectively.Al single
old electrical outlet is
located on the lower
portion of the wall.


A painted plaster wall
with a flush door at the
north end. A 4x10' black
board is mounted on the
wall with a a/c grille
above it.


Sheet vinyl in 6' wide
sections


Floor


Door on
East wall


Wood flush door


Windows on
west wall


Two wood frame double
hung windows with 9/9
panes on each frame.
Sun blinds are on the
interior.





O


1x5 baseboard with clam-
shell moulding on the
top and a 1" x 1/2"
strip at the floor.
Painted 1x2" milled stri


WOOD:
a)baseboard



b) Picture
moulding

c) chair
Moulding


The base is in good condition
except for minor nicks and
dirt.

The trim is in good condition
but the paint was applied in
a poor manner.
The moulding and paint are in
good condition but a few seam
are pulling apart and it is
dirty in a few areas.


Fill nicks and touch up repairs
with original type paint. Clear
base with suitable cleaning
solution.

Repaint after scrapping off ol<
finish with a good quality pail

Pull seams back into place and
secure properly. Clean with a
suitable cleaning solution.


wood





Recommendations


1 None





Remove paint from damaged area
and fill nicks then bring repai:
work up to standards. Apply a
good quality paint to the sur-
face.


Conditions


The ceiling is in good conditil
and is clean. The only problem
is slight bends in the metal
tracking.



The paint is in good condition
but the plaster is in fair con-
dition. The plaster is nicked
over the wall surface and at
the corner of the mechanical
shaft. A poor plaster repair
runs the entire length of the
wall about 3' above the floor.


The wall is in good condition
with dirt and smudges marks on
its lower portion.


I


Acoustical tile suspended
ceiling with 2-2x4' re-
cessed flourescent light
fixtures and an a/c
grille.

Painted plaster wall wit1
an enclosed mechanical
shaft at the west end.
Exposed conduit and an
electrical outlet is on
the lower portion of the
wall.



Painted Plaster wall wit1
a flush door at its mid-
point and an outlet with
exposed electrical condu:


Clean wall surface with a
suitable solvent.


__


J


)


.


University of Florida

" Survey o~f existing Construct~ion "


Area


Description


Ceiling


North wall


East wall


r


Final Exercise
AE-683
Spring 1977


School of Architecture-Department of Preservation
University of Florida -Gainesville,florida


0 RoomL


-


















A door and transom are
at the mid-point of the
painted plaster wall.


Same as east wall.




Replace the sheet vinyl with tl
same type of .tile that is on tl
remainder of the floor. Maintaj
floor regularly to assure a lot
life.


8x8" vinyl asbestos tile : The floor is in good condition
with only minor scratches. A
2' wide section of sheet vinyl
has beeh installed in place of
the tiles at the north end.


Fill in the scratches and pain
repaired areas. If true restore
tion is to beaccomplished
the ceiling must be removed or
raised to allow the transom to
be put back into operation.


Locate exact cause of the cracks
repair- and replaster then paint
repaired area. Clean the dirt
and smudge marks from wall with
a surface cleaning solvent.


f South wall


Painted plaster wall wit1
an electrical outlet at
its center. -


The paint and wall are in good
condition. A crack is in the
west corner joint from the
floor to ceiling. The cause
seems to be poor installation
between the original and the
newer wall.Dirt and smudge
marks are on the lower portion
of the wall.


The wall and paint are in good
condition with small dirty are
on the lower portion.


West wall


Floor


Flush wood door


Recent installation in very
good condition.


Door on
East wall



Door on west
wall


None


Wood frame door with ~a
translucent glass panel
on the upper half of the
door and air reurn grilL
is on the lower portion.
A glass transom is a.t th
top but with a plywood
sheet over it and the
ceiling intersecting
it at its center.


The paint and door in good
condition but-with a few
scratches that have been pain-
ted over. The hardware on the
door is intact and operates
well. The transom is covered
by a plywood panel and the
hardware has been removed.





__ _L_


None





Fill in nicks and repaint
patched areas.


a)baseboard


1x5" baseboard with clam
shell moulding on top &
a 1x1/2" strip at the fl
This base is used on the
north & west walls only.

1/4 round and 3" moulded
baseboard is used on the
south and east wall.


The base and paint is in good
condition with an electrical
wire mounted on its lower por-
tion.


The base and paint are in good
condition with a few nicks
painted over.





I I


0 Room


I


Description


Conditions


1The ceiling appears to be a
recent installation and is
clean and in good condition.
The ceiling has been suspended
at the midpoint of a door
tansom.


Recommendations



None





The paint and plaster are in
good;:condition with the only
problem of: small amounts of
dirt and smudge marks.

Same condition as the north
wall.


clean wall and repaint if
necessary.



Clean wall and repaint if
necessary.


University of Florida

" Survey of existing Constructiion "


Acoustical tile suspended
ceiling with exposed
metal track and 2x4'
panels with one recessed
glourescent light fixtur
An a/c grille is in the
center of one of the
panels.

Painted plaster wall wit
book shelves in front of
most of it.


Ceiling


North wall


Painted plaster wall wit
2 flush wood doors near
each end.


East Wall


Final Exercise
AE-683
Spring 1977


School of Architecture-Department of Preservation
University of Florida -Gainesville,florida


Area


( )


I






































Lightly sand door and apply
good quality paint.Remove
paint from hardware and apply.
clear protective coating.


South Wall


Painted plaster wall wit
a door at its center anc
a mechanical shaft to
the right of the door.
An old sink plumbing
hook -up is at the soutt
east corner.


Painted plaster with a
door and transom at its
center.


Same condition as the north
:wall. The drain for the sink
is now used for the water
cooler beyond the weast wall
by means of connecting P.V.C.
pipe.



The paint is in good condition
but the plaster is not.Paint
has been applied over unre-
paired nicks and poor plaster
repair work. P.V.C. ~pipe `from
a water cooler on the other
side of the wall protruds
thru a hole that is too big
and connects with a drain on
the south wall.


Slight nicks and dents~ due to
weight of heavy objects.
rest of floor in good condi-
tion.

Doors are in very good condi-
tion


Clean wall and repaint if
necessary.


West Wall


Remove paint and plaster nicks
and bring plaster repair work
up to standards. Place a seal
around drain pipe to cover hole
Apply a good quality paint to
the wall.


Replace damaged tiles and main~
tain floor regularly such as
waxing, polishing etc.


Vinyl Asbestos tile
floor .with 8x8" tiles.


Floor


2 Flush wood doors that
are recent installation:


Door on West
Wall


None


Single panel wood door
that is painted to match
the wall.


The door is in good condition
but the paint is not, dirt is
in the finish. Hardware is
painted to match the wall.
Paint is is also worn.New
hinges ahve been installed.


Door on South
wall





O


Clean door and remove or raise\
ceiling to allow complete
operation of the transom and
the proper installation of
ita missing hardware.


Two panel wood frale doc
with a translucent glast
panel in the upper half,
A transom is located
above but is partially
blocked by the recent-
ly installed ceiling.
A return air grille is
located on the- bottom
portion of the door.


The door is in good condition
and operates well. The paint
is in good condition. Ply-
wood has been used to block
out the transom where the
ceiling meets it.The hardware
for the door is intact and
working well, but the transom
hardware is missing.


WOOD:

a)baseboard
west and
south wall



b)North and
east wall


1x5" board with 1" clam-
shell moulding and a 1x
1/2" strip at the floor
it is painted to match
the trim.

Wood baseboard of 1/4
round and 1x3" moulding
board.


The paint and base are in good
condition. The paint is chipp-
ing and peeling in a few areas
and a few holes and nicks are
painted over.

The paint and base are in good
condition. The paint is scrat-
ched in a few places and worn
off by a table leg at another
place.


Scrape paint and repair nicks
and holes and apply good
quality paint.



Repaint base.


Door on
West Wall










--


Conditions


The ceiling appears to be a
Lrecent addition and is clean
land in good condition.The ceil
ing has been suspended at the
center of a door transom.


Recommendations



None






Clean wall and repaint where
necessary.


Acoustical tile suspended
ceiling with exposed met
track and 2x4' panels wi
2 recessed flourescent
light fixtures.An a/c
grille is in the center
of one of the panels.


I I


Plaster wall with a door
opening at its center.It
appears a new-plaster
wall was placed over the
existing wall, by a 1"
build up beyond the door
frame.


Plaster wall with a door
and transom at its center
Some wallbuild up is on
the north wall.

PLaster wall with elec-
trical conduit on its
lower portion and the
corner.


Paint and plaster in same con-
dition as the north wall.


Paint and plaster in good
condition.


Area



Ceiling


Description


The wall and paint are in good
condition.Slight nicks,dirt
and dark smudges are only pro-
blem.


North wall


West wall


Same as in north wall.


South wall


None


/3>


School of Architecture-Department of Preservation
University of Florida Gainesville,florida


0~ Room


University of Florida

" Survey of existing Construction "












Repair damaged areas or replace
entirely. In either case lo-
cate and remove material caus-
ing bumps.Maintain regularly
such as waxing. polishing etc.


Two panel wood frame
door with a translucent
glass panel in.the-upper
half.A transom is locat-
ed above but is partially
blocked by the recently
installed ceiling.A re-
turn air grille is lo-
cated on the bottom of
the door.


Single panel wood frame
door


Clean door and for proper res-
toration remove or raise ceilin
to allow complete operation of
the transom and the proper ins-
tallation of its missing hard-
ware.


Sand door lightly, smooth out
patches and nicks then apply
light coat of good quality
paint


11_


jA painted plaster wall
with a new flush door
installed.


Paint and plaster in same con-
dition as north wall, .



Fair condition with damaged
areas due to heavy objects
denting floor and some mater-
ial below the surfacr causing
bumps to rise and expose the
surface to premature ware.


Like new condition ekeept for
frame and moulding are 1/4"
above the floor due to poor
installation.


The door is in good condition
and operating well. The paint
is also in good condition witl
only a little dirt on it.Ply-
Swood has been used to .block
out the transom where the ceil
ing meets it.The hardware for
the door is intact and work-
ing well but th'e transom
hardware is missing.


The door operates well and the
paint is in good condition but
does have dirt in the finish.
The hinges have recently been
replaced ahd are not at the
original door locations.A
fairly good fitting patch was
installed in the old hinge
mount location.The frame is
slightly nicked in various
places.


East wall


Same recommendation as the
north wall.


Floor


Sheet Vinyl


Door on east
wall


Recently installed flust
wood door with wood fran


None.


Door on West
wall


Door on
North wall





_ ___~_ __


nick


Scrap off paint the repair
and scratch. Apl1y a good
quality paint.


WOOD
TRIM


A wood baseboard is made
of 1/1+" round and 1x3"
noulding board.


The paint is ~in poor condition
with' numerous nicks and scrat-
chs that have been painted ove2
Dirt and black smudge marks are
spread all over baseboard.


O1














Description


Painted plaster with 10,
3 segment 4' flourescent
light fixtures. Steel ca]
plates have been used to
cover old light mounts.
Six insulated heat pipes
enter the ceiling in
front of the north wall,
allbut one have a steal
seal.


Conditions


The paint is in poor condition
with cracking and chipping
evident in many places.Around
the hole area where each pipe
enters has a blackened area
and one has a large unprotect
ed hole.Water damage is eviden
at numerous locations.


Recommiendations


Scrape and repaint the ceiling
and at this time check condi-
tion of plaster and replaster
if necessary.Insulate pipes
where they enter the ceiling
and secure seals properly.Repai
large hole at one pipe and
install the proper seal.Locate
source of water damage and stop
the cause then replaster and
paint.


The wall should be scrapped and
the various holes and marks re-
paird.A good quality paint should
Id be used in this room.Poor
plaster repairs of the past
should be brought up to quality
standards. Attempt to discover
reason for warps and repair the
same to maintain a straight wal


The paint and plaster are in
rough condition- in numerous
places. Cracks are in the plas
ter at various places and at
the window opening at the east
end. The paint is scratched,
:chipped and badly marred where
temporary partitions where once
installed.Holes from these
partitions wre never repaired.
Holes are spread throughout
the wall surface. A warp is
evident in the wall at the eas
end.


Room


ROL FI SHL
University of Florida

" Survey of existing Construction "


Area




Ceiling









North Wall


A painted plaster wall
with 3 bays of windows.
Electrical cover plates.
outlets and conduit are
exposed on the lower por
tion of wall.Six heater
pipes are located in frol
of the wall along with
3 radiator type heaters.


Final Exercise
AE-683
SPrine 1977


School of Architecture-Department of Preservation
University of Florida -Gainesville,florida







































Paint and plaster same condi-
tion as north wall. A 2" sq.
hole is located at the edge of
the door frame.


Same recommendation as on nort
wall.


__


II -


Same recommendation as on
north wall. Locate source of
water damage and get under
control.


Plaster in same condition as
in north wall. In addition tapt
marks have damaged paint. A
large 1' square hole has been
repaired at the north end.Mis-
match paint was used on part
of the wall. Water damage is
evident at the top left corner
of the window opening.


East Wall


South wall


Plaster and paint in same con-
dition as the north wall.Num-
erous locations at the upper
portion of the wall have water
damage and resulting cracks
holes for paper towel holders
are numerous and unrepaired
around the sink area.Poor ins-
tallation of the a/c grille ha
resulted in unnecessary wall
damage.


Same recommendation as in the
north wall. Locate water damage
and bring under control and
repair plaster around A/C gril


West wall


/A painted plaster wall
:with a 4 pane wide window
at its center.A picture
frame moulding and wains-
coat are on the wall at
approx. 10' and 4' res-
pectively. The wainscoat
drops down about 6" to
accommodate the large
window.


Three transom doors are
located at various points
on this painted plaster
wall one at the center
and one near each corner
Picture frame moulding
and a wainscoat are app-
rox 10' and 4' above the
floor.3 a/c grills are
located at the picture
frame moulding level. A
corner sink is located
by one of the pilasters
at the east end. An
addition capped plumb-
ing hook up is located
near the west corner.


A painted plaster wall
with a panel door loca-
ted towards the south
corner. 'Two phases of
plaster and plaster dama-
ge by door frame indicate
door may have been a la-
ter addition. A wainscoa-
approx 4' above the floo:
and a 10' high picture
frame are on this wall.





II 1 -


Vinyl asbestos 8x8" sq.
Tiles are used as floor
surface.6 heater pipes
anter the floor and all
but one have steel seals
at the intersection poin


Wood frame double hung
windows in 3 bays across
the wall. The center cor
sisting of 3 12/12 pane
window and the other twc
bays with the center
window a 12/12 and the
window to either a 9/9
pane.A number of windows
have glass air deflector
Blind mounts are on the
frames but blinds are
not installed.


Wood frame double hung
window with 12/12 panes.
Blinds are used on this
window but no sun screen
An electrical wire runs
around the frame which
is used for mounting.


Three wood frame doors
with translucent glass
panels on the upper hal
are located on the sout
wall.Return air grille
are mounted on the lowe2
portion and have~glass
transoms.


Numerous tiles are broken and
damaged by heavy objects. One
heater pipe missing,its seal
has lead to damage of the
surrounding tiles.



The original varnished frames
have been painted to match the
walls. The paint is in fair
condition with some chipping
and peeling evident.A few of
the locks are broken but the
windows are still operable,
and the hardware is in place
The frame is loose at the win-
.dow on the far right side of
the wall. Windows are very di-
rty with loose caulking.



The window is in good conditi<
and is operable. The frame has
been painted to match the wall
and a poor job was done.Paint
is on the glass and is peelin~
and cracking off in some pla-
ces. All hardware and sash
cords are in place.

All door hardware is intact
except the door to the far
east which has its striker
plate held in position-with
scotch tape.Only one transom
is operable but it is slight
warped out of form.The other
two are nailed shut and have
only one part or none of thei
operating hardware.is intact.
The paint is in fair condition


Replace damaged tile and
locate a seal around the piping
that is without one. The surface
must be maintained regularly to
assure long life.



Remove paint and revarnish or
repaint the total units. Replac
the broken lock and tighten the
loose frame. A periodic maint-
enance schedule must used to
maintain a long operable life.


1 Remove painp:and revarnish or
repaint the window and frame.
Periodic maintenance must be
used.


Floor






Windows on tb
north wall


Windows on
the east wall


Dor on the
south wall


Remove paint and prepare surface
and apply good quality paint.
Secure the striker plate secu-
cely and replace transom hard-
neare if possible and free to op-
*erate.Al nicks and holes should
me filled prior to painting.
R11 loose moulding and glass
panes should be properly
secured.







with some chipping and peeling
evident. The frames are nicked
with random nail holes. The
center door has loose moulding
on the return air grille and
the glass is loose.


1x5" wood Baseboard with
a 1" clamshell moulding
at the top and A 1x1/2"
strip at the floor. Pain;
over original varnish.









lx2" milled wood and
painted to match the
wall.


A poor quality of paint was
applied to the original var-
nish finish. The frame is in
good condition except for a
crack in one corner.The mouldi
is separating from the door in
the panels. Evidence described
in the west wall section indi-
cate this may be a later ins-
talled door.




The moulding is cracked,separa
ting and missing in various
places.The base and moulding
have been damaged from earlier
installation of temporary par-
titions. The baseboard was poo
ly installed at the door on th
west wall.Electrical conduit
is attached in many places
which contributed to many hole
found in the baseboard. The
paint is in poor condition wit:
chipping and peeling at many
locations.
The paint is in fair condition
but the moulding is in needof
repair. Seams are pulling apar
and are dealigned.Nail holes
are spread over the moulding.
In some aeras the moulding is
separating from the wall.


~_~__


Scrape surface and apply a good
quality paint.Repair crack to
stop further spreading and
secure moulding porperly.


Door on West
wall


ITwo panel wood frame doot


WOOD:

a) baseboard













b)picture
frame
moulding


Replace missing and cracked
moulding then secure properly
where it is loose.Relocate con-
duit to mount on the wall just
above the baseboard and repair
all holes and blemishes.After
scrapping and properly preparit
the surface apply a good quality
paint.





Scrap and repair loose and
dealigned moulding.Remove nails
and fill all holes then apply
a good quality paint.















I I _


Description


Painted plaster with 4
unsuspended flourescent
light fixtures.A heating
pipe enters the ceiling
near the west wall.



Recent painted plywood
addition with a hidden
door at its center.A
painted pisture frame
moulding is located
approx. 10' above the
floor in addition to a
1/4 round moulding along
the top and side corners
A 5x12' black board is
located near the west
wall.A 7' high partition
intersects the wall and
the door at its midpoint
Recent electric outlets
and conduits have been
installed.


Conditions


The paint surface has two 1"
water bubbles and is peeling
in other areas.The steel seal
at the point where the pipe
enters the ceiling is not in
place.


The plywood seams are exposed
and slightly separated in some
places. The paint used is not
of good quality and is peeling


Scrape surface anld locate sour-
ce of water damage.Repaint cei-
ling with good quality paint.
Secure pipe seal in its proper
location.


Rloom


University of Fl3orida

" Survey ofE existing Const~ructJion "


Airea



Ceiling





North Wall


Recommnendations


Secure loose plywood seams and
seal with caulking or other
similar material Apply good
quality paint to surface.
Remove or relocate the partitio
that blocks the door or remove
the door that is in the plywood
wall.


~pf


I







Plaster and paint are in good
condition.


1Clean wall to remove all
stains.









Investigate and correct cause
of cracks and replaster affec-
ted areas. Remove marks from
the wall and place a seal arou:
the phone wire where it enters
the wall.Repaint wall with gooi
quality paint.


East
Wall








South
Wall


Painted plaster with a
transom door at its mid-
point.Painted base and
picture frame which is
about 10' above the
floor. An a/c vent in-
tersects the picture
frame moulding to the
wall with 2'x4' wood
braces.


Painted plaster with a
panel door at its mid-
point.A 7' high tempo-
rary partition intersect
the wall to the left of
the door. Exposed elec-
trical outlets with con
duit and a 2x12' desk
are mounted to the wall


Paint is in fairly good condi-
tion.Cracks have formed in the
plaster where the partition
Iwas attached and more cracks
are along the longer portion
of the wall. Conduit has been
removed in the past and has
left paint build-up which form
its outline. A small hole for
a telephone is located at the
east end.


The paint and plaster are in
fairly good condition although
the plaster hasbeen damaged
around the window frame and
has been poorly repaired.
Minor cracking an the plaster
is also evident.


Painted plaster with a
bay of three windows. A
heater and a vertical
heater pipe are located
in front. Electrical
outlets and conduit
along with telephone
wire run along the face
of the wall.Picture fral
moulding and base are
painted to match the
wall.A 7'high temporary
partition intersects
the bay of windows at
one of the frames.


Bring plaster repair work up t<
standards to match the wall.
Perform necessary repairs to
cracked areas and apply good
quality paint.












O/


West
Wall





--





Due to inappropriate tiles
used for repair work, it would
be best to replace entire floo


Wood frame double hung
window with 12/12 glass
panes on each frame.Sun
blinds are in the inside
and sun screens are on
the outside.



Two panel wood frame dool
painted to match wall.
Frame has a 1x5" board
at the top to allow use
of a shorter door.A 1x18'
Return air grille is lo-
cated on the lower portic
of the door but is block-


    Two panel woo0d frame dool
    (not original installa-
    tion).A simple 1x5" boar<
    frame and door are paint<
    to match wall.


    Wood frame door with a
    translucent glass panel
    on upper half of door an<
    a glass transom above.A
    return air grille is
    mounted on the lower
    prtion


    The vinyl surface has been da-
    damaged by heavy objects and 5
    tiles appear to be for repairs
    with respect to this problem.
    A few seams are separating and
    pulling away from the wall in
    places. Stain and wax build-up
    are also evident.


    The windows appears to be in
    good operable condiiton. All
    Hardware and frames have been
    painted to match walls and were
    poorly painted. The caulking
    is separating from the window
    in various places.


    The original Varnish finish ha;
    been painted over very poorly.
    The moulding on the grille is
    loose and the plywood is un-
    painted. Small nicks and holes
    are around the frame along witl
    lan electric wire that runs
    completely over the frame.



    Door is inoperative due to tem
    porary partition attaching
    directly to the center of the
    Idoor.Paint in good condition
    but further inspection is
    hindered by storage cabinets.

    Door is in good condition and
    operating well. The frame,door
    and the transom hardware are
    painted to match the wall.The
    paint is in fairly good condi-
    tion but is damaged around th
    rille moulding.


    Remove paint from the hardware
    and clean existing paint from
    windows. Recaulk the windows
    to maintain water tightness.
    Regular maintenance is needed
    for long useful life.



    Remove paint and old varnish.
    Apply good quality varnish to
    restore original finish. Remove
    the plywood and secure the
    loose moulding.Patch all holes
    and nicks.


    Remove partition that is interim
    fering wiht operation or removE
    door.




    Remove paint from door hardwarE
    and apply a clear protective
    coat of paint. Fill small holes
    in frame and revarnish thC)
    door.


    6' wide sheet vinyl with
    5-8x8" tiles placed in
    it


    Floor


    Window


    Door on
    South Wall


    Door on
    North Wall


    Door on
    East wall














    Paint is chipped in some pla-
    ces but otherwise it is in
    good condition. Some nails an<
    holes and a phone plug are on
    the base.



    Paint in good condition.
    Regular matching of moulding
    with the 1/4 round in the
    corners of the north wall.


    Fill holes and repaint with
    good quality paint.





    Remove paint and fill nail ho-
    les and apply good quality pai
    Relocate phone plug to a wall
    installation.




    Install a suitable connection
    between the 1/4 round and the
    picture frame moulding and the
    same for the a/c grille. Clean
    and paint picture frame mould-
    ing.


    Painted baseboard on
    north wall is 1x6" with
    1/4 round on top and at
    the floor. Electrical
    wiring runs along por-
    tion of the base.

    Painted base on remain-
    ing wall is 1x5 with
    calmshell on the top
    and 1/4 round at the
    floor. Electrical lines
    run along the base at
    various points.

    approx. 3/4"x2" milled
    wood painted to match
    wall.About 10' above
    the floor with a a/c
    grille intersecting it
    on the east wall.


    The paint is fairly good con-
    dition with few minor holes.


    Clean existing paint and touch
    up nicks with matching paint.



    Same as partition "a"


    Painted plaster partitior
    7'high that divides room
    north to south.An accor-
    dion door is located at
    the center with a vinyl
    base.
    A painted plaster parti-
    tion that joins the west
    wall at its center be-
    tween two windows and
    extends approx. 8' into
    the space to the east.
    it is approx. 7' high
    with a 4'high cross sec-
    tion at the end for
    sun~nort


    The plaster and paint is in
    good condition with a few nick
    from desk edges and damage
    from tape adhesive.


    The plaster and paint is in
    good condition with heel marks
    on its lower portion,


    0,














































    ..:

















    Description


    Painted plaster with 10
    2'x4' suspended floures-
    cent light fixtures.Five
    insulated pipes run thru
    ceiling near west wall.















    Painted plaster wall wit1
    door opening(nodoor) At
    midpoint of wall wood
    picture frame moulding
    runs across about 10'
    above the floor level.


    Conditions


    The ceiling appears to be in
    good condition.A recent install
    lation of light fixtures left
    many holes from the old fixtu-
    res.
    The openings where the pipes
    pass thru the ceiling have a
    black residu surrounding it.
    This is probably due to the
    absence of insulation at this
    point.
    A small area around one of the
    pipes appears to be suffering
    from water damage. Tje paint
    is building and peeling around
    the affected area.
    Slight cracking and peeling
    of the paint is evident in few
    scattered areas.


    Plaster has shirinkage cracks
    but appears to be in good con-
    dition. Cracks are probably
    due to paint build up.


    Recommnendations


    Refill holes and paint as
    required.


    Clean and paint all area affec-
    ted.Apply insulation around
    pipes at ceiling level.


    Find source of water leakage
    and take preventive measures
    to stop further damage. Scrape
    and paint affected areas.

    Scrape and repaint as required.


    I


    Room


    Plaster wall should be Scrapped
    to eliminate cracks.Repaint wit
    good quality paint.


    Final Exercise
    AE-683
    S ring 1977


    School of Architecture-Department of Preservation
    University of Florida -Gainesville,florida


    - ~wf


    a- .. A .. ..
    University of Florida

    " Survey of existing Construct~ion "


















    The condition of the floor is
    fair About 20(8x8") tiles
    are of unmatched color,used
    for repairs to surface. Nume-
    rous damaged areas are the re-
    sult of heavy storage cabinets
    and heavy desk legs.


    Windows are in operable condi-
    tion with all glass panes in-
    tact. Paint is peeling off and
    the caulking is in poor condi-
    tion.The unvarnlsh;:d" frame is
    also in good condition except
    for wall paint on them and
    some loose pieces of trim in
    some areas.The handle on one
    of the window is missing.The
    sash cords on a few of the
    windows are also missing.Re-
    maining hardware is intact wit
    no evidence of extreme ware.
    Some nail holes are present in
    some of the frames and sills
    Windows are extremely soiled
    and poorly maintained.


    The varnish on frame is in
    good condition.


    Scrape peeling paint and remov
    loose caulking. Secure loose t
    and install missing hardware
    and replace broken sash cords
    Fill all nail holes in the
    frames and sills then apply a
    good quality coat of paint.
    Maintain regularly to assure
    long life.


    Locate 2 pnldoors similar t
    type in building the finiq
    to match other.


    cont.


    Old picture mount-holes which
    poorly repaired are also evi-
    dent.


    Due to extensive damage and
    inappropriate repair entire flo
    ing material should be replace
    Maintain regular maintenance
    to assure long life.


    Floor


    Windows on
    West wall


    the wall along with ra-
    diators. Exposed con-
    duits and electrical
    outlets are located near
    floor level. Electrical
    and telephone Equipment
    is mounted near floor
    level at north end.


    Sheet vinyl 6' wide wit1
    four pipes intersecting
    it along the west edge
    The points where the
    pipes meet the floor ar
    protected by steel seal-
    ing cap.


    Wood frame double hung
    windows with 12/12 glast
    panes on each frame.
    Sun blinds on the inside
    The frames are painted
    varnished.


    Door on
    North wall


    Wood door frame with
    door missing.









    ff- B


    Replace missing transom hard-
    ware and return transom to
    operating condition.Varnish
    grille moulding to match the
    door or replace with proper
    type wood. Fill nail holes arou
    the transom, door and frame
    then apply a good quality~paint


    Door on
    East wall


    f


    Wood frame door with a
    glass panel on upper
    half of door and with
    a glass transom. A re-
    turn air grille is
    mounted on the lower
    portion of the door.


    Door is in good condition and
    fully operable.The varnish
    finish and hardware is also in
    good condition. The transom
    hardware is not intact and
    nailed closed. The grille
    moulding is a later installa-
    tion of mis-match wood. Variou
    nail holes are located around
    the the frame.


    None


    Door on Soutt
    Wall


    Door inspection not
    possible due to storage
    cabinets.


    Wood:

    A) bsaeboard









    B) Picture
    frame
    moulding


    Scrape off wall paint and secur;
    loose moulding properly. Replace
    cracked moulding and fill nail
    holes then apply a good quality
    paint.





    Scrape oof wall paint and pro-
    perly dress around a/c grilles.
    Secure moulding properly in
    place fill all nail holes and
    apply a good quality paint.


    1x5 wood baseboard with
    clamshell moulding on
    top of a 1x1/2 strip
    at the floor. It has a
    varnish with electrical
    wiring attached in a few
    location.



    Approx. 3/4"x2" milled
    wood with a varnish fin-
    ish. Finish about 10'
    Above the floor. A/C
    grilles interact the
    moulding on the east wal:


    In fairly good condition.The
    The varnish is in good con-
    but with small amounts of wall
    paint on the top portion.
    The base was used as a nailer
    for electrical wiring and the
    result is numerous nail holes.
    The clamshell moulding is
    loose in some places with oc-
    cassional splits at the corner
    The moulding is in good con-
    dition with some wall paint on
    it.Nails and nail holes are
    evident in the moulding.The
    moulding was poorly cut for th
    installation of a/c grilles an
    is also separating from the
    walls in other places.
















































    LI





    Description


    Painted plaster with 4-
    2x4' suspended floures-
    cent light fixtures.Ther
    are heating pipes enter
    ing the ceiling near two
    walls.


    Painted palster with a
    door and transom at its
    midpoint. A varnished
    wood picture-frame moul
    ding is 10' above the
    floor along with a wains
    coat about 4' above the
    floor. A a/c vent and
    electrical outlet with
    conduit have been added
    since original condition
    A sink and its accesso-
    ries are located between
    a 2x3' mechanical equip-
    ment shaft and a corner.
    Two heated pipes are lo-
    cated in front of the
    wall.


    Conditions


    The plaster is in good condi-
    tion and the paint is chipping
    in only a few places. The meta
    saels on two pipes are loose
    and out of place while two are
    completely missing.


    Plaster is in good condition
    with fairly recent coat of
    good paint but with small area
    of minute cracks. A 10'sq.in.
    poorly repair hole is in the
    plaster at east corner.The two
    pipes have damaged about 18"
    of the plaster on the beam
    face located at the top of the
    wall.


    Recommnendations


    Scrape the chipping paint areas
    and repaint with a good quality
    paint.Replace 2 missing seals
    and secure loose ones in place




    Scrape areas with cracking pain
    and bring plaster repair area
    up to standards. Relocate pipes
    away from the wall surface and
    properly repair the surface the
    apply a good quality paint.


    ~-~--- --


    I Y _


    University of Fl3orrida

    " Survey of existing Con~stru~ction "


    Final Exercise
    AE-683
    Spring 1977


    School of Architecture-Department of Preservation
    University of Florida- Gainesville,florida


    Room


    -






    IF- II


    None


    Same condition of East wall.


    Painted plaster with a
    varnished wood picture
    frame moulding about 10
    above the floor and a
    wainescoat about 4'
    above the floor.


    6'wide sheet vinyl with
    2 heater pipes entering
    it by the south wall.


    Damage marks from heavy-desks
    and storage cabinets that have
    ot been repaired. A large sec-
    tion is missing in the South-
    east corner and a small water
    stained area is below the sink


    Wall paint is on the frames
    and the varnish is woen off
    the sills. Phone lines run
    across the frame and tied
    down with staples.


    Three panels of varnish
    ed wood frame double
    hung windows with 12//12
    glass panes on each
    panel.Blind brackets
    are on the interior and
    sun screen on the exte-
    rlor.


    _ _I____~__I_^_L__


    Fill holes then remove old
    finish and revarnish.Relocate
    phone line to just above the
    base on the wall surface.


    East Wall


    Painted plaster with a
    varnished wood picture
    frame moulding about 10
    above the floor and a
    wainscoat about 4' abov<
    the floor.


    Painted plaster with
    three windows at its
    center. Two heater piper
    and a heater are loca-
    ted in front of the
    wall. Recently added
    electrical


    Plaster is in good condition
    with a fairly recent coat of
    good paint in good condition.


    Same condition of East wall.


    None


    South Wall


    West wall


    None


    Replace damaged and missing
    tiles. Maintain regular mainter
    ance toassure long life.


    Floor


    Windows on
    the south
    wall






    > ll 1 .


    Secure loose moulding and fill
    all miscellaneous holes.Remove
    old finish and reaplly quality
    varnish and provide seals where
    pipes enter the base.


    _ I~ll~m~


    _~___~_


    Fill miscellaneous holes and
    apply good quality varnished.


    The door is in excellent condi-
    tion and operates freely.Hard-
    ware is intact and operable for
    the door and the transom. Paint
    spots are on the door and wall
    paint is on the frame.The varn-
    ish is in poor condition on the
    door and the grille moulding is
    of unmatched wood and unvarn-
    ished.Small holes are at variot
    places around the frame.


    Spotted paint and wall paint
    as on the surface along with
    numerous nail holes. The clam_
    shell moulding is separating
    from the south wall. The point
    where the pipes enter the base
    was poorly cut and is damaged.

    Finish is in fairly good con-
    dition but with numerous nail
    holes and pines.Slightly loose
    in a few locations.

    Finish in fairly good condition
    with a few small holes.


    Fill all holes then remove
    old finish and reapply varnish.
    Stain moulding around grill to
    match the door or replace with
    same wood as used on the door,


    Varnished wood frame
    door with a nontranslu-
    cent glass panel on the
    upper half of the door
    and a return air grille
    on the lower portion.
    A glass transom is above
    the door.


    Door on
    the North
    Wall.








    WOOD:
    a)Baseboard


    1x5" wood baseboard with
    clamshell moulding on
    top and a 1x1/2" strip
    at the floor. A varnish
    finish with two heating
    pipes entering it at the
    northeast corner.

    1x4" varnish wood about
    4' above the floor.



    Approx. 3/4"x2" milled
    wood with a varnish fin.
    about 10" above the floo2
    An a/c vent intersects
    it at one point.


    Fill miscellaneous holes
    secure properly in place
    revarnish.


    and
    and


    Ib) wainscoat


    c) Picture
    frame
    moulding




    iT


































    \h
    \fe



    iiL












    --- e-


    Conditions


    Ceiling is in good condition
    except for loose seals at poini
    where pipes extend into ceilin~


    Re commnenda t ions



    Secure seals in place.








    Scrape the damaged area and
    prepare surface for a good
    quality paint.


    Painted plaster wiht 2x4
    suspended flourescent
    light fixtures. Two heated
    pipes extend into ceilin~
    and an a/c duct is sus-
    pended from the ceiling
    by three U-straps.


    Painted plaster with a
    door at its center. A
    wainscoat and picture
    frame moulding approx.
    4' and 10' above the
    floor respectively.


    A bay windoe covers most
    of the wall area with a
    varnished wood shelf ex-
    tending into the bay ap-
    prox. 4' above the floor.
    A small wall surface is
    located where a wall woul
    normally appear but ex-
    tends only to the shelf


    Paint is damaged just above the
    wainscoat.


    The wood is in good condition
    except for varnish is rough anc
    seams are slightly opening.Plas
    ter on the wall is in poor con-
    dition as is the paint. Chip-
    ping, cracking,nicks and .poor
    .plaster repairs are evident.


    __ __


    University of Florida

    " Survey of existing Construction "


    Area




    Ceiling


    Description


    WCood deck should be sanded and
    refinished.
    SPortion of the wall below shel:
    should be replastered and a
    coat of good quality paint
    applied.


    West Wall


    I


    r


    Final Exercise
    AE-683
    Spriing 1977


    School of Architecture-Department of Preservation
    University of Florida Gainesville,florida


    rioo0


    Room


    North Wall






    I_





    Prepare wall and apply a coat
    of good qaulity paint.


    ______~I~


    C_ ~


    South Wall


    level.Five windows are it
    the bay area which extend
    four feet out from the
    wall line.Electrical con-
    duit and outlets run
    along the lower portion
    of the wall.


    Painted plaster wall wit
    a doorway at its center
    and only the frame is
    present at this time.A
    picture frame moulding
    about 10' high above the
    floor along with a wainsl
    coat approx. 4' above thB
    floor.Electrical conduit
    and phone wiring runs
    around the door frame.
    Two shelves are mounted
    to the wall near the east
    end along with the cap-
    ped plumbing for a sink
    that has been removed
    with missing 2' section
    of wainscoat at this
    corner.


    The wall is in good condition
    with only minor paint chippin;


    Prepare surface and apply a
    coat of good quality paint.


    East wall


    A transom door is at the
    center of the wall with
    an a/c duct entering it
    near the north end.Pic-
    ture frame moulding and
    a wainscoat at the stan-
    dard -established height
    but the wainscoat stop
    about 2' from the south
    corner because of the
    old sink location.


    Wall and paint are in good
    condition with good plaster
    repair at the point where the
    sink was removed.





    L-~----~


    Moderate amount of damage due
    to heavy objects.



    Windows are in good condition
    and operating with all hardwal
    intact except for a few missia
    and broken sash cords. The
    varnish on the frame is in po<
    condition as is the window
    paint.Small holes are on the
    frame work and paper is stuf-
    fed in one window to attempt
    to fix a loose frame.


    The original varnished frame
    has been repainted to match
    walls. The paint is in fairly
    good condition.A 2"sq. piece
    of frame has been removed to
    allow clearance for the
    electrical conduit.


    Door is in good condition but
    varnish is cracking and the
    wood moulding for the grille
    does not match the door.


    Door is in good condition and
    operates well. Hardware is in
    tact and in good condition.
    The varnish is in poor condi-
    tion and small nail holes are
    evident on the door and frame





    Repair damaged areas or replace
    but maintain and protect
    finish regularly.


    Both window and frame must be
    i scrapped and repainted or var-
    ; nished. Missing sash cords mus
    be replaced. holes should be
    Repaired and loose frame se-
    cured. Windows must be proper-
    ly maintained to assure long
    life.


    Door and frame should be re-
    finished with good quality
    varnish. The moulding should
    be stained or replaced so


    Door and frame should have
    holes patched and surfaced
    prepared and and a good quality
    paint ( varnished) be applied./


    _~ II-~----


    Six foot wide sheet vin-
    yl in one solid color.



    A bay of 5 windows with
    each 2 panes wide except
    for the center one which
    is 3 panes wide and con-
    sist of 12 panes. Glass
    breeze deflectors are on
    all windows as well as
    blinds on the interior
    and sun screens on the
    exterior.


    The door is missing but
    the painted frame is in-
    tact.Electrical conduit
    and telephone wiring rune
    around the entire frame.


    Windows on
    East Wall


    Condition of paint is suitable
    for further use.Replace piece
    in frame and redesign electri-
    cal conduit route.


    Door on
    South Wall


    Varnish frame and two
    panel door With an a/c
    return air grille on the
    bottom portion.


    Varnished wood frame doo2
    with a translucent glass
    panel on the upper half
    of the door.A return.air
    grille is mounted on the
    lower portion of the
    door and a glass transom
    above.


    Door on
    North Wall



    Door on
    East wall


    Floor






    ..


    11


    The varnish must be stripped
    off to remove wall paint and to
    fill small holes. Relocate out-
    let to a wall mount location
    just above the base and install
    missing sections in corner.


    Varnished 3/4"x2" milled
    wood with a varnish fin-
    ish.


    The wood is in good condition
    as is the varnish but wall
    paint has been carelessly spla
    shed onit. Electrical outlets
    have been mounted on it in
    various places. Two 2' segment:
    are missing in the southeast
    corner fot the location of the
    sink one time.


    The condition is good except
    for wall paint stains on it in
    various places and a slight
    warp at the seam.


    _ _~~_ ~ 1


    WOOD :


    a)baseboard


    Varnished lx5" wood
    baseboard with clamshell
    moulding on top and a
    1x1/2" strip at the floor i
    Wiring and conduit are
    mounted to it in various
    places.


    Baseboard and varnish are in
    fairly good condition but var-
    nish is cracking in some areas
    Its use as an electrical mount
    has caused many holes in sever-
    al areas.


    Refinish base with good quality
    varnish, Fill holes' and reloca-
    te wiring and conduit to wall
    surface just above base.


    b)wainscoat


    Varnished 1x5" board
    about 4' above the floor,


    Picture
    Moulding
















    r ~ ~~ --




    9'






    IllB1













    1


    Description


    Painted plaster with 4
    flourescent light fixtu-
    res.One incandescent
    light fixture.An old
    mount with conduit is
    also on the ceiling.An
    8" sewer pipe is just
    below the ceiling along
    with an a/c duct.

    Acoustical tile is on the
    south end of the wall on
    the inside of the cubical
    Painted plaster is on the
    remainder of the wall.


    Conditions


    The plaster and paint are in
    good condition. A 1' long by
    1" wide hole runs along the
    junction with the south wall.


    Re comnen d a ti on s


    Repair hole and apply good
    quality paint.









    Repair minor damaged areas and
    apply good quality paint.The
    plywood repair should also be
    removed and plaster applied
    to match plaster of wall.


    The plaster and paint are in
    fairly good condition except
    for minor nicks, tape damage
    and a small area of poor plas-
    ter repair work.A 1x1 1/2'
    plywood square is at the center:
    of the wall.


    Plaster and paint is in good
    condition but dirty with a few
    poorly repaired holes.


    Painted plaster wall witt
    a4x12' blackboard and
    electrical conduit with
    outlets.


    ~--~-


    Area



    Ceiling


    East Wall


    Repaint wall with good quality
    paint.


    North Wall


    Final Exercise
    AE-683
    Spring 1977


    School of Architecture-Department of Preservation
    University of Florida -Gainesville,florida


    0 Room


    University of Florida

    " Survey of existing Con~struct~ion "





    I_


    __


    The plaster has cracks in some
    areas with a large crack above
    the electrical panel and from
    the hole where the electrical
    wire enters the wall.A 1x2'
    hole runs along the ceiling
    Joint with plaster damage
    -around it,


    Replace missing tiles and ins-
    tall the missing seal at the
    bottom of the heater pipe.Floot
    must be maintained regularly
    to assure a long useful life.



    Remove plywood sheets on the
    door and repair all holes.
    Remove old finish and apply
    good quality paint.


    I'


    Wood varnished frame
    door with a translucent
    glass panel on the uppe:
    half and a return air
    grille on the lower por
    tion. A glass transom
    above the door.


    The door and transom are in
    good condition with all hard-
    ware intact. The varnish is in
    poor condition with a green
    tint due to age.Plywood over
    glass .panel & some nicks and
    holes on door and frame.


    A transom door is in the
    center of a painted
    plaster wall with expose
    conduit and electrical
    outlets. A single heater
    pipe is in front of the
    wall and an a/c duct
    enters the upper portiori


    Acoustical tile is on
    the east portion inside
    a cubicle attached to
    this wall. The remainde
    of the wall is painted
    plaster. A 3x3' view
    window is in the center
    of the tile wall.An elet
    trical panel and elec-
    trical wiring runs into
    the wall surface.3 sewe2
    pipes about 6"in dia.ru
    into the wall near its
    top with an 1x3' ply-
    wood patch around the
    holes.


    An 8x8" vinyl asbestos
    tile floor with a heate:
    pipe intersecting the
    floor near the south-
    west corner.


    The paint and plaster are in
    good condition with with chair
    scratch marks and dirt on the
    lower portion.


    Clean wall then repaint with
    good quality paint.


    West Wall


    Locate source of cracks then
    repair to match wall and apply
    good quality paint.


    South wall


    Floor appears to be in good
    condition except with a mission
    section 2' long and the width
    of the North wall.The seal is
    missing on the pipe at the
    point were the pipe enters the
    floor.


    Floor


    Door on
    West wall


















    Cubical


    r I _- I


    __


    I


    _ 1_1__1_~__


    I__ II_ -----i~-LII-llsl~--IIPYI I


    Cleaning is all that is requi-
    ered.


    A 1x5" base with clam-
    shell moulding on the
    topand a 1x1/2" strip at
    the floor with a varnish
    finish.


    A 10x6x7' space made of
    painted particle board
    A flush door is used wit]
    a 1x5" base and 1/4
    round on the top and at
    the floor.Acoustical tile
    is on the ceiling.2 view
    windows are in the cubi-
    cle.


    RTemove old finish and revar-\


    The base is in good condition
    but the varnish has aged and
    has a green tint and white in
    some areas.


    Wood
    Base


    The cubicle is in very good
    good condition and built very
    well.Electrical outlets and
    conduits have been added to th
    exterior.






















































    le~c4

    1~
































































    Av












    0 gv






























    vtf


















    i \

















    Recommendations


    -1


    ROLP HALL
    University of Florida

    " Survey of existing Construction "


    ,,
    1


    4 4 a


    Final Exercise
    AE-683
    Fall -1977


    School of Architecture-Department of Preservation
    University of Florida -Gainesville,florida











    3 RD FLOOR












    i t-


    Description


    Suspended acoustical pan
    els with exposed tracks.
    2x4' panels .6 floures-
    cent recessed light fix-
    tures.Ceiling is install
    ed at level of picture
    moulding.


    Painted plaster wall wit
    2 window openings, pic-
    ture moulding, chairrail
    and baseboard. Radiator
    located below east window
    with vertical return
    piping. Room has 90.
    degrees "s" turn and wes
    end is 2' farther north.
    Small radiator is in
    crook serviced by same
    pipes.Exposed electrical
    conduit with outlets als
    telephone junction box.


    Conditions


    Added during remodeling in nos
    76. In new condition.


    Recommendations


    None


    Determine cause of cracking
    Sand peeling, correct problem
    ust repaint affected area. 0btaii
    -and install suitable face
    plate for phone cable entran<
    Remove paint from outlet
    1- receptacles and face plates.


    __


    _ ___11___1_______Crr______-~DI~0~--~~~


    __ _~ III~~-erETn~~I-~=I*F~-~


    __~P_ _~~


    Wall painted in nov.76. Paint
    is cracking and peeling several
    in two small areas above the a
    window opening, Total area
    is less than two sq. feet.
    Phone cable goes into open
    box. Electrical outlets paints
    over.


    L ______1__ ___ j


    Final Exercise
    AE-683
    Spring, 1977


    Schsoo of .Architlec ture-Devartment of preser-vation
    University ofZ Flor~i~da G-ainersvlle, florida


    University of Florida

    " S;urveyL of existing Cons~truction "


































    Scuff marks below 3' level
    from chairs and tables.



    Some roughness of finish alon
    L1 lower side of chairrail.
    Wiring appears to be obsolet
    phone wiring, Scuff marks
    from backs of chairs.

    Installed 6 to 8 months
    n ago and in good condition.


    .Painte~dplaster wall witl
    door opening, picture
    moulding,chairrail, and
    baseboard.Chalkboard frol
    door to north wall. Pro-
    jection screen mounted
    at center, below picture
    moulding.Exposed electric<
    onduit and outlets.Struc-
    tural column at south en<


    Painted plaster wall witl
    door opening,picture
    moulding,chairrail and
    baseboard. Sructural col
    umns at east end corner
    of wall. Column at center
    has false extension for
    service piping. Exposed
    electrical conduit for
    light switch and outlets
    West end has 90 degrees
    projection where corridor
    was added.


    Painted wall board with
    picture moulding and
    baseboard. No chairrail.


    Painted plaster wall wit1
    picture moulding, chairr
    and baseboard.Exposed
    wiring along baseboard.


    12" square vinyl tile.
    light brown with dark bra
    d white chips or flecks.


    Piaht is clean and free of
    scuff marks. Some blemishes
    are visible below the paint
    where old peeled areas were no
    feathered out before painting
    This is evident below Chalk-
    board. Outlets are painted.
    L1


    Remove paint below chalkboard
    sand out rough areas of old
    peeled paint. Use filler if
    necessary and repaint.
    Remove paint from outlet
    receptacles and face plates.


    East wall


    Clean scuff marks and
    retouch as .required. Remove an
    lower chairrail 7" to protect
    walls from chairs. Refinish 01
    line where charrail ran and
    paint to match wall.


    Paint is clean andlfree of ble
    mishes except for some scuff
    marks from tables and chairs
    too short for rail. Chairrail
    is non functional. Outlets
    are free of paint. Conduit has
    been painted to match wall.


    South wall


    Southwest
    corner
    partition


    West wall


    Clean and retouch paint.Add new
    chairrail at new lowered height,



    Remove wiring if it is obsolete
    Clean and retouch paint where
    scuffed.Lower chairrail 7" and
    refinish old lime where rail re


    Floor


    None


    01





    Good None


    c)
    Baseboard


    1x3" wood baseboard
    moulding at top and

















    Description



    Suspended acoustical
    ceiling with 2x4' tiles
    and exposed tracks and
    4 recessed luminaires.
    IBay above door has edge
    trimmed out with painted
    plaster.


    Recomimendations



    None








    Remove tacks from picture mould
    ing.Remove phone cable above
    suspended ceiling. ( about 4"
    higher than present location)





    Obtain and install face plate
    for light swtch. Clean paint
    from electrical outlet and
    plate.


    Conditions



    Recently added. condition like
    new.


    Paint is clean and free of ble-
    l1 mishes. wall is 90% covered
    by free standing book shelves
    and filing cabinets.
    Picture moulding has several
    thumb tacks in it.



    paint is clean and free of
    blemishes. Light switch has
    h no face plate. Electrical
    outlet on column is painted
    - over but is operable.


    Planted plaster with door
    picture moulding. chairra
    and baseboard.
    Strutural column at east
    end with extension to
    cover service piping.
    Grey phone cable along
    picture moulding.

    Painted plaster with door,
    picture moulding,chairrail
    and baseboard.Col. at nor
    end with extension for
    service piping.corner law~
    tory at col. Exposed elec-
    trical conduit from ceili
    to light switch by door.


    _ ______I__W________1_Y_


    ___ ____1___~^1_1____ __ _11_1_


    _ 9_ 1~1_ _II_____


    - ----


    University of Florida

    " Survey of existing Construction "


    Area


    Ceiling


    North wall


    East wall


    Final Exercise
    AE-683
    Spring, 1977


    School of Architctu~eDprte-Dptmn of Preservation
    University of Flor~ida G aine svi le ,f loriPda

















    Paint is clean except for ligh
    handprint near phone cables.


    1/4" hole bored in upper corne
    of upper panel.Operable,var-
    nished and has all hardware.


    Painted plaster wall
    with door,picture mould-
    ing chairrail and base-
    board. This is a stud
    wall partition. Exposed
    conduit and open juncti(
    box in wall at lower
    west corner.Chalkboard
    from door to west wall.


    Paint is clean and free of
    blemishes.


    ICover junctionr box with face


    West wall


    Clean handprints


    Clean and relatively free from
    gouges or marks.


    Panes intact and all hardware
    present. Units are operable
    as well as blinds.


    Floor


    None


    None


    Windows west
    wall


    Plug or fill hole,stain
    and varnish


    Nort door


    Painted plaster with on
    window opening, Picture
    moulding, chairrail and
    baseboard. Radiator
    below window with verti-
    cal supply and return
    pipes. 3x5' telephone
    service terminal at north
    end below chairrail wit1
    grey phone cables runnu:
    vertically to ceiling.


    Light brown vinyl tile
    12x12" with grey and
    white flecks.


    Cluster of 4 wood single
    hung 6/6 units.A/C unit
    in second window from
    north end.1/2 screens
    on unit except a/c.
    individual blinds on
    each unit.

    all wood door with wood
    Frame.


    South wal











    University of Florida

    " Survey of existing Construction "


    Description


    Acoustical tile suspended
    ceiling with exposed meta
    track, 2x4' tiles and 4
    recessed luminairs 1x2
    panels trim out east and
    west sides.


    Painted plaster wall witl
    one 3 unit window cluster
    Chairrail at 3' and base-
    board. 2-3" insulated
    pipes ( for supply and
    return) Service radiator
    below window.1" pipe fron
    floor to ceiling at west
    end. Exposed electrical
    conduit runs horizontal
    2" below window sill.2
    Phone cables run along
    baseboard.One outlet and
    exposed electrical con-
    duit at 13" level.Elec-
    trical outlet at 7' level
    1' east of window opening


    Conditions


    Ceiling is about 7 months old
    and is in very good condition
    Free of marks and blemishes.


    Recommendations


    None


    Clean and or touch up scuff
    mark.Check electrical outlet
    at 7' level to determine if it
    is hot. If it is functional,
    clean plate and receptacle of
    paint and replace. If outlet
    is dead, replace with brown
    plate.


    _~.~__- -- I~
    -- ------------ ------ I---..-~13-L--~T~-~,~~YZC=~


    '~`~-i--~~'~Ti4-r;ir--mru-mir~rrr~r;-


    Paint is 7 months old as part
    of remodeling Job. Paint is
    clean and free of blemishes
    except for one 6" scuff mark
    about 6=10" east of radiator.


    iC


    Final Exercise
    A1E-683
    SprinP, 1977


    School of rchtetur-e-Departmentl~ of Pr~eservation.
    Univ~ersity of F'lorida Gaine~s:i~l le::flor~ida



















    Clean handprint





    Determine cause of vertical
    compression crack and if no
    further cracking is anticipated
    repair and repaint cracked
    areas of wall.


    Strip ,wax and buff floor. Set
    up regular schedule of cleaning
    and waxing to prevent excessive
    wear and damage.


    Painted plaster wall wit
    one door opening and
    chairrail at 3'.Exposed
    electrical conduit at
    13" with 2 outlets.Grey
    telephone cables stapled
    along baseboard to phone
    connections. Column at
    south end has extension
    to hold utility piping.


    Painted plaster wall wit
    chairrail at 3' baseboard
    and one door opening.



    Painted plaster wall
    with chairrail at 3'
    baseboard and one door
    opening.Light switch at
    north side of door frame
    1" pipe runs from floor
    to ceiling about 18"
    from north wall.2 grey
    telephone cables run
    along baseboard from
    north end to center of
    wall .Cables serve two
    connections.


    12" square vinyl tile
    light brown with dark
    brown medium brown and
    white chips.


    Good condition but relatively
    scuffed for age. Not maintained
    sufficiently for traffic it
    gets.


    ea~st wall


    Paint is 7 months old.Part of]
    remodeling job.It is clean ang
    free from marks.Two or three
    compression cracks appear
    adjacent to the door.


    ~crac~-s adjacent to door.


    South wall


    Paint is clean and free of
    blemishes except for one hand-
    print near the center.No
    cracks.


    Paint is clean and free of
    marks. Cracks visible in
    plaster at lower south of
    door frame.Compression crack
    started at baseboard about 12'
    from south wall and ran verti
    cally to a point about 10"T cak
    above chairrail. Tecak
    seems to have been halted by
    a small hole drilled at the
    point of the advance.


    West wall


    Floor


    Cluster of 3 wood double All window panels are intact
    hung 6/6 units. An a/c 9 and operable. Paint of wood
    unit at bottom of center trim is same color as wall.
    unit.One full set of bl ds. Blinds are operable.


    North window


    .None


    01








    Good condition,operable.Some
    wear visible around knob under
    varnish.Transom hardware is in
    place but transom is stuck
    closed,probably due to last
    varnish coat.


    Strip and repaint worn area on
    door- revarnish.Determine caus
    of sticking transom and repair.


    _ _I _Y_


    2 panel wood framed door
    with transom top panel
    is translucent glass,
    bottom panel is wood.
    Hydraulic closing unit
    is attached at top of
    door.


    2 panel door all wood


    South door


    West Door


    Good appearance, varnished.
    door knob has been removed to
    prevent use as door is between
    department office and a class-
    room.


    WOOD:

    a)chairrail







    b)baseboard


    1x3" with beaded bottom
    and 3/8 x 3/4" trim plate
    cm top. Runs around
    perimeter of room.


    Good condition except for
    occasional mark where pencil
    sharpener had been attached,
    or small spots of paint from
    old painting of walls.Some
    secretaries use to tack up
    notes, etc.

    No apparent blemishes


    Fill screw and tack holes,
    strip, restain and varnish as
    necessary. Provide small bulliti
    N boards fo r se c re ta rie s as n eed s
    to prevent further damage.












    __


    Conditions


    Ceiling is about 7 months old
    and is very good condition
    clean and free of marks or
    blemishes.

    Panelling added with ceiling
    ,and is in new condition,


    Recommendations


    None,




    Remove exposed conduit along
    bottom of wall and or paint
    shade of brown which will blend
    with wall,






    None


    Acoustical tile suspend
    ded ceiling with exposed
    metal track 2x4' tiles
    and 2 recessed luminairs


    Playwood panel wall with
    '3 unit window cluster 0,
    Horizontal seam in pann-
    elling at 8' level.
    Drapery bracket mounted
    above windows.2-3" insu
    ated pipes for supply a
    return service radiater
    below window. Pipes run
    floor to ceiling
    Pannelled wall with one
    window unit.Seam in pan-
    el at 8' level. 6' of
    exposed metal electrical
    conduit to add 2nd.outle
    centered below window.
    Structural column at
    southend of wall.


    _ ___J ~-rr;il-i~al~;-~o^-~-rP~i~`---- -- --------


    _ _ _____1_I __ __~ll______a__ __~ __ __I____~ ~___ __ I


    ROLF8 1-1AL
    University of Florida
    " Survey of existing Construction "


    Area


    Description


    Ceiling


    North wall








    East wall


    Same as north wall


    '3)


    Final Exercise
    A1E-683
    Spring, 1977


    School of Architecture-Department of Preservation
    University of Fl~orida Gainesville,florida


    (























    None






    Maintain regular cleaning
    schedule to keep free of dirt
    and sand.


    Painted plaster wall wit
    door opening at center.
    hairrail is on south wal
    at 3' level. .
    light switch on west sid
    of door. Lavatory on
    west end of wall.


    Panelled as north and ea
    walls and has one door
    opening. Ends at column
    on south end and has
    lavatory at south end.


    Wall to wall carpeting
    with a commercial grade
    red and black carpet.


    3 Unit cluster of wood
    double hung windows.
    center unit is 6/6
    flanked by 2 4/4 units.


    1,8/8 wood double hung
    window with interior
    blinds.


    7 Months old, has no apparent
    damage or wear and seams in
    new condition.


    All window panels are intact
    and operable .Paint on wood
    ,trim is sound.
    Blinds and drapes on the
    interior are operable.

    Sound and operable.blinds are
    also operable.


    Clean door area near handle.
    Revarnish if necessary. Determj
    cuase for sticking transom and
    free it.


    11


    Good condition,varnished.Eithe
    soil buit up from handling or
    wear is evident around knob
    area. Transom has hardware but
    is stuck closed. Probably due
    to last varnish coat.


    __


    O


    Finish out plaster pFat~ch
    above lavatory and paint
    to match wall cover.


    Plaster was _painted at the,...- .3
    time of the remodeling 7 month
    ago. It is clean and free of
    blemishes,except for one small
    patch above the lavatory. It
    appears that a soap dispenser
    was removed.


    South wall


    West wall


    S-ame as north wall


    Floor


    North
    windows


    None


    East window


    None


    South door


    wood door with 2 panels
    top panel is translucent
    glass, but is wood. wood
    frame with transom.



















    2 panel all wood a modi-
    fication prior to the
    recent remodeling.





    1x3" beaded moulding
    topped by 1/4 x 3/4"
    trim plate along south
    wall and-on columns at
    the corners 3' high ,
    Wood baseboard


    2" moulding along panell
    ed walls at door.Corner
    porcelain lavatory-
    S.W. corner.


    !Well fitting and smoothly opera
    ting. Clean. and varnished.
    Stain matches other door trim
    and blends with panelling.


    None


    West Door


    Wood:

    ) Chairrail




    ) baseboard
    South

    )baseboard
    north,
    east,
    west


    Clean, varnished, no apparent
    blemishes.



    No apparent blemishes.


    Stained cold water operable
    only.


    None


    SNone


    Determine
    clean'.





    Recommendations


    Determine cause of cracking
    to see if a present of past
    condition caused it. Install
    a suspended acoustical ceiling
    with 2x4' panels and exposed
    tracks to match ceilings ins-
    talled in recently remodell-
    ed rooms.

    Clean scuff marks, repaint as
    required to cover.


    Conditions


    Clean with 2 minor compression
    cracks.


    Painted plaster with 2

    ing flourescent light
    fixtures.Fixtures are nt
    original and are served
    by exposed conduit from
    points where 4 original
    fixtures hung.


    Painted drywall partition
    a later addition to devid
    herbarium into classrooms
    one door opening and 3 1/
    x 10' chalboard running
    from door to west wall.
    Picture moulding 18" fronr
    ceiling, chairrail 36"
    from floor and baseboard
    Projection screen attache
    to wall below picture
    mulding. Exposed conduit
    and outlet near baseboard


    Clean and free of blemishes,
    except for large scuff.Marks
    !near electrical outlet.


    __


    _ --__~1_1_---__ 1--~--_---~-----^---r__~1l-.111~----_-1 ---l-IL- ___


    ROLF8~ 1-1ALL
    University of Florida

    " Survey of existing Construction "


    Area .



    Ceiling


    Description


    North wall


    Final Exercise
    A~E-683
    SarinR 1977


    School of Architecture-Department of Preservation
    University of Florida -Gainesville,florida






















    Translucent glass panels have
    been painted on the north side
    an opaque brown color. Some
    scratches in this paint let
    light through.Allso paint is
    insufficient to cover fully in
    some places.Wood is free of
    marks and is varnished.


    Paint is clean with minor
    scuffs between window openings
    below chairrail.


    Place exposed wire in conduit
    clean scuffs from paint and
    retouch as required.


    Some scuff marks on paint belo
    chairrail, especially on the
    face of the columns. South
    column has combination of foot
    -scuffs and desks masrks. Line
    -about 18" from floor is caused
    by lip of sliding metal trash
    can.Outlets have been painted
    over and a 3 switch plate by
    door has only one switch.


    Clean wall below chairrail
    and repaint to cover to cover
    as required. Determine if
    outlets work and either clean
    paint off or replace with soli
    plates. Replace light switch
    plate with appropriate type.


    East wall


    South wall


    Clean paint from glass and
    install opaque curtains which
    can admit or block light.


    West wall


    Painted plaster wall wit
    picture moulding, chair-
    rail and baseboard. One
    door opening with light
    switch adjacent.Two stru
    tural columns and a stru
    tural beam project from
    the wall and are plas-
    tered and painted.Single
    electrical outlet on
    north column and double
    outlet with chain pull
    switch is on south col-
    umn both about 7'high.


    A translucent glass and
    wood panel partition wit
    door opening and transom
    at east end.This parti-
    tion extends from west
    walls and 4 unit window
    cluster in half at the
    west wall.


    Painted plaster with 2
    window opening,picture
    moulding, chairrail and
    baseboard. Radiator below
    north window served by
    vertical supply/return
    pipes.3" vertical pipe
    formerly serviced radia-
    tor at south window. Rad
    iator was removed for
    partition and pipe is
    capped. 2 Exposed con-
    duits and exposed wires
    along baseboard. 4 doublE
    plug electrical outlets
    one blank plate and one
    open outlet box.


















    All glass panes intact but
    dirty. Handles are missing
    from north unit. Wood trim is
    sound and units are operable.
    Blinds and drapes are operable



    Sound condition and operable.
    One broken pane in center
    bottom of south unit.Blinds
    and drapes are operable.


    Clean glass and replace miss-
    ing handles.


    Replace broken pane. Clean gla


    Varnished and free of blemishe
    Knobs have been removed to
    prevent use.

    Hardware in place,operable. I
    Glass panel is painted.


    Floor is old and badly scrate
    and scuffed. Numerous dents or
    depressions from heavy pointe
    objects an area 6 tiles square
    is solid dark brown.


    SRemove tiles and replace
    with some grade and color
    used is latest remodeling.


    Floor


    North
    window






    South window


    North door


    Replace knobs


    East door


    9x9" tiles. Colors are
    dark and light brown and
    pattern is checkerboard
    with one dark brown row
    around perimeter. Perime
    ter tiles are about 6x24
    -laid end to end.


    Cluster of 3 wood single
    hung window units.6/6
    Individual blinds for
    each unit, sill length
    drapes and 1/2 screens
    on exterior.


    2 wood single hung 6/6 h
    units are north of south
    wall. These units are .
    part of a 4 unit cluster
    which is in half by the
    south wall.An a/c unit
    norht unit. Set of blind
    for each unit, sill
    length drapes, 1/2
    screen unit only.


    2 panel all wood with
    wood frame.


    2 panel wood door with
    transom. Top and transom
    panels are translucent
    glass bottom is wood.
    Transom is not part of
    door.


    None


























    None




    If scufffing is anticipated,
    lower chairrail and refinish
    old line of rail.


    None


    panel wood door.Top
    panel is tasuet
    glass, bottom is wood.
    Transom is not part of
    door.


    Hardware in place,operable.
    Glass panel is painted.


    None.


    Clean, varnished, free of mark


    Beaded wood moulding
    around perimeter of nortl
    east and west walls.18"
    from ceiling.

    Wood rail with beaded
    bottom and 3/8"x 3/4"
    trim plate on top. 36"
    from floor. North, East
    and west walls only.
    1x3" wood board with
    mouldings at top and
    floor.North, East ,West
    walls only.


    Clean, varnished, free of marks
    Now functional at present
    height due to shorter desks
    used.

    good


















    Recormmendations


    Conditions


    Clean and free of marks.Slight
    roughness in finish where drail/
    comes through.


    Visible area seams sound, cleal
    and smooth.


    Description


    Painted plaster with ex-
    posed structural beams at
    north and east edges.
    Exposed conduit to one
    two bulb flourescent
    light fixtures. Drain
    pipe comes from floor
    above.


    Painted plaster wall wit1
    door, baseboard and strue
    tural beam along ceiling.
    Combination light swtch
    and electrical outlet by
    door. Structural column
    at west corner.Exposed
    cojduit and outlet west
    of door.

    Painted plaster wall wit1
    baseboard.Drain pipe fron
    ceiling exists through
    top of wall.Exposed condt
    with outlet.85% of surf ac
    concealed by storage cab.


    I _I _I~


    None


    North wall


    Paint is clean. Several slight
    gouges inplaster,


    Fill grooves or pits, smooth
    and repaint.


    None


    East wall


    University of Florida

    " Survey of existing Construction "


    Area


    Ceiling





















    --~--~----- 11


    Few spots and stains minor
    scratches.



    Varnished but faded or discolo
    Frame has been painted non-
    gloss brown.


    12/12" Light brown vinyl
    tiles with white and gre
    flecks.


    2 panel wood door without
    :ransom Top panel is
    translucent glass, bottom
    is flat,offset slats for
    ventilation.Wood frame.


    Painted non-glass brown as
    ; door frame.


    ed Determine if discoloration
    is due to present or past
    use of chemicals or other
    cause. Refinish all wood wit
    appropriate material to resis
    discoloration if present
    usage warrants this. Stain
    and varnish is desired. Fini
    if possible.



    Refinish consistent with door
    woodwork.


    Painted plaster wall wit.
    baseboard.Exposed condui
    from ceiling runs down t<
    5' level and branches
    horizontally both direc-
    tions providing wall
    Outlets.


    Paint is clean but poor finish(
    work shows plaster lines,
    runny paint are.


    Room is work room.Correction
    of plaster finish and painting
    is optional,


    South wall


    Floor,


    Strip, re-wax and buff


    Door


    rOOD :

    a)baseboard


    Wood trim at baseboard
    70-80 % hidden by cabine
    and counters.













    Conditions


    Recent addition in good con-
    dition






    Irregular surface along wall
    where cahirrail was original
    Slight cracks.


    Recommendations



    None






    Refinish area where cairrail
    was removed to eliminate cracks
    and bulges. Repaint



    Clean scuffs on paints. Fill
    and feather small holes and
    ,repaint.


    _ 1 I 1 1
    __ __ ~__I____~ __~


    ( )


    FIC3L S HAL
    University of Florida

    " Survey ofE existing Construction "


    Area



    Ceiling


    North wall





    East wall


    Description


    Suspended acoustical wit
    2x4' tiles and exposed
    tracks and one recessed
    light fixture.Sits on
    yitue LU toIIulding." ~"1]'" Tr immE
    on east side with paint-
    ed plaster about 8'-10"

    Painted plaster with
    picture moulding and
    baseboard. Exposed con-
    duit below picture mould
    ing.

    Painted plaster with doc
    picture moulding and
    baseboard.Exposed condui
    connects old outlet high
    on wall with new outlet
    at floor.


    Some scuffs and prints near
    door.Two partially filled
    holes in plaster south of doo2
    Irregularity of surface and
    slight cracks from removal
    of chairrail.


    Final Exercise
    AE-683
    Sprinp, 1977


    School of Architecture-Department of Preservation
    University of Florida Gainesville,florida