Group Title: Historic St. Augustine: Permits, State Inspections, City Forms, HARB
Title: Construction Inspection Report for The Department of General Services
ALL VOLUMES CITATION MAP IT! THUMBNAILS PAGE IMAGE ZOOMABLE
Full Citation
STANDARD VIEW MARC VIEW
Permanent Link: http://ufdc.ufl.edu/UF00095503/00036
 Material Information
Title: Construction Inspection Report for The Department of General Services
Series Title: Historic St. Augustine: Permits, State Inspections, City Forms, HARB
Physical Description: Report
Language: English
Publication Date: 1989
Physical Location:
Box: 8
Divider: DOS 8449-A, Govt. House 87-88
Folder: Permits, State Inspections, City Forms, HARB
 Subjects
Subject: Saint Augustine (Fla.)
48 King Street (Saint Augustine, Fla.)
Government House (Saint Augustine, Fla.)
Spatial Coverage: North America -- United States of America -- Florida -- Saint Johns -- Saint Augustine -- 48 King Street
Coordinates: 29.892465 x -81.313142
 Record Information
Bibliographic ID: UF00095503
Volume ID: VID00036
Source Institution: University of Florida
Holding Location: University of Florida
Rights Management: All rights reserved by the source institution and holding location.

Full Text


Area: Cr


CONS'TRIJCTION INN
f
The Department of


ASPECT ION REPlORT 241989
or MAY 4 1989
General Services

H. S. A. P. B,


TO: Administrator FROM: Curtis C. Holmes, Jr., Inc.
Design Review and Permitting Section (Inspection Firm)
Department of General Services
Room 512, Larson Building
Tallahassee, FL 32399-0973
(904) 488-0220
DOS-84490010 Correct Life Safety Violations/Renovate East
State Project #: (8449-A) Project Name: Wing, Government House, St. Augustine

Type of Inspection: Electrical Performed by: Curtis C. Holmes, Jr."
(one type per report)
Date of Inspection: 05/04/89 Time in: 10:00 a.m. Time out: 11:30 a.m.

Prime/General Contractor: Historic St. Augustine Board SuperintendentI Dave Scott

Subcontractor: .Owen Electrical Company Foreman: Mickey Owen
Clerk of the Works .N/A Weather conditions: Clear warm


List work inspected, Code violations (including specific Code references) and
resolutions, other relevant comments: NOTE: A/E must resolve all code violations
otherwise a stop work order will be issued.

ACTIVITY

1) Inspection: Substantial Completion, Renovated Areas.

2) Observation: Operational ability of electrical, including functional devices.

WORK INSPECTED

1) Electrical distribution'system and devices.
(1) Panelboard A, East.Wing; Panelboard B, Auditorium.
(2) Air handling unit (.installed in floor trench).

(3) Lighting fixtures.

(4) Switches

(5) Receptacles
(6) Exposed conduit and boxes, display windows, Auditorium. ( (\
cc: A/E ` (Inspector's signature
Contractor
May 18, 1989
(date submitted)
Form I-5
page 1 of 2 Rev. 5/26/H7











TO: Administrator
Design Review and Permitting Section
Department of General Services
Room 512, Larson Building
Tallahassee, FL 32399-0973
(904) 488-0220


DOS-84490010
State Project # (8449-A)'


CONCLUSIONS

1) N.E.C. Violations:


FROM: Curtis C. Holmes, Jr., Inc.
(Inspection Firm)


Correct Life Safety Violations/Renovate East
Project name, Wing, Government House, St. Augustine ,


Auditorium and display areas, only.


(1) Conduits below panelboard B require support, per N.E.C. Article 348-12.

(2) Open holes (knockouts) in junction boxes require plugs, per N.E.C. Article 110-12(a).

(3) Old devices in old boxes With protruding conductors require protective enclosure,
or cover, to prevent contact with any conductor which may become energized, per
N.E.C. Article 110-3(a)(2)(8). This condition existed prior to the current
contract, and was not created by the current work.

2) Comments


(1) Smoke detector located in return air plenum (new floor trench)
appears to be exceptionally insensitive to large quantities of


functions, but it
smoke.


(2) The electrical foreman, Mr.Mickey Owen, slated that N.E.C. violations listed
in 1)(1) and 1)(2) above, would be corrected within the following working day.


(3) With assurance from 2)(2) above
satisfactory and suitable for i


, the new electrical system will be considered
ts intended use.


3) Recommendations

(1) State personnel at site should arrange to have old abandoned and exposed electrical
devices and wiring removed, or covered.

(2) State personnel at site should assure that proper operation 'f smoke detector in
floor trench plenum is verified by the manufacturer.


page 2 of 2


Area: Q [


CONSTJCT'IO N. INS!'ECTIION' R.IORT