Group Title: Historic St. Augustine: Permits, State Inspections, City Forms, HARB
Title: Construction Inspection Report for The Department of General Services
ALL VOLUMES CITATION MAP IT! THUMBNAILS PAGE IMAGE ZOOMABLE
Full Citation
STANDARD VIEW MARC VIEW
Permanent Link: http://ufdc.ufl.edu/UF00095503/00028
 Material Information
Title: Construction Inspection Report for The Department of General Services
Series Title: Historic St. Augustine: Permits, State Inspections, City Forms, HARB
Physical Description: Report
Language: English
Publication Date: 1989
Physical Location:
Box: 8
Divider: DOS 8449-A, Govt. House 87-88
Folder: Permits, State Inspections, City Forms, HARB
 Subjects
Subject: Saint Augustine (Fla.)
48 King Street (Saint Augustine, Fla.)
Government House (Saint Augustine, Fla.)
Spatial Coverage: North America -- United States of America -- Florida -- Saint Johns -- Saint Augustine -- 48 King Street
Coordinates: 29.892465 x -81.313142
 Record Information
Bibliographic ID: UF00095503
Volume ID: VID00028
Source Institution: University of Florida
Holding Location: University of Florida
Rights Management: All rights reserved by the source institution and holding location.

Full Text


CONS'TR'JCTION INC
fo
The Department of


'ICT1 ION i REPO RT
rGeneral S ices
(;oneral Services F' ... / .

'! ,h II ,


TO: Administrator FROM: Curtis L. Holmes, Jr.; Inc. -... ,
Design Review and Permitting Section (Inspection Firm)
Department of General Services
Room 512, Larson Building
Tallahassee, FL 32399-0973
(904) 488-0220

DOS-84490010 Correct Life Safety Violations/Renovate East
State Project #: (8449-A) Project Name: Wing, Government House, St. Augustine

Type of Inspection: Electrical Performed by: Curtis C. Holmes, Jr.
(one type per report)
Date of Inspection: 01/25/89 Time in: 10:30 a.m. Time out: 11:30 a.m.

Prime/General Contractor: Historic St. Augustine Board Superintendent: Dave Scott

Subcontractor: Owen Electrical Company Foreman: Ed Gaffney

Clerk of the Works: N/A Weather conditions: Fair Warm


List work inspected, Code violations (including specific Code references) and
resolutions, other relevant comments: NOTE: A/E must resolve all code violations
otherwise a stop work order will be issued.


ACTIVITY:

1) Inspection, Partial:


Conduit system, rough-in.

(1) Crawl space between"West and East wings.

(2) Wall, ceiling and floor plenum, East wing, only.


WORK INSPECTED:

1) Feeder circuit conduit, 2 inch, PVC, Schedule 40, 100 lineal feet.

2) Branch circuit conduits, 1/2 inch through 1 inch.

3) Wiring in conduits.

4) Panelboard;.

5) Device and outlet boxes mounted in plenum, walls and ceiling.


cc: A/E (Inspector's signature)
Contractor
February 7, 1989
(date submitted)


Form I-5
Rev. 5/26/h7


page 1 of 2


Area: r ,


__


. . . -(m i ,T,,





CONSTRUCTION INSPECTION REPORT
for
The Department of General Services


TO: Administrator
Design Review and Permitting Section
Department of General Services
Room 512, Larson Building
Tallahassee, FL 32301
(904) 488-0220


FROM: Curtis C. Holmes. Jr. Inc.
(Inspection Firm)


DOS-84490010
State Project #:(8449-A)


Project Name:


Correct Life Safety Violations/Renovate East
Wing, Government House, St. Auqustine


CONCLUSIONS:

1) Additional conduit straps and supports required in several locations.

2) The electrical foreman, Mr. Ed Gaffney, stated that all discrepancies in the conduit
installation would be corrected to comply with NEC support requirements.

3) VARIATION FROM SPECIFICATIONS: Feeder conduit to new panelboard in East wing is PVC.
Specifications do not provide for this method. Mr. David Scott will contact A/E,
Shepard Associates, for approval.

4) With assurance from 2) above, the current conduit installation is satisfactory and
ready for wall and ceiling cover.


page 2 of 2


Area: C /