Group Title: Historic St. Augustine: Permits, State Inspections, City Forms, HARB
Title: [Letter to Thomas B. King]
ALL VOLUMES CITATION MAP IT! THUMBNAILS PAGE IMAGE ZOOMABLE
Full Citation
STANDARD VIEW MARC VIEW
Permanent Link: http://ufdc.ufl.edu/UF00095503/00008
 Material Information
Title: Letter to Thomas B. King
Series Title: Historic St. Augustine: Permits, State Inspections, City Forms, HARB
Physical Description: Correspondence
Language: English
Creator: Miron, Hector
Publication Date: 1987
Physical Location:
Box: 8
Divider: DOS 8449-A, Govt. House 87-88
Folder: Permits, State Inspections, City Forms, HARB
 Subjects
Subject: Saint Augustine (Fla.)
48 King Street (Saint Augustine, Fla.)
Government House (Saint Augustine, Fla.)
Spatial Coverage: North America -- United States of America -- Florida -- Saint Johns -- Saint Augustine -- 48 King Street
Coordinates: 29.892465 x -81.313142
 Record Information
Bibliographic ID: UF00095503
Volume ID: VID00008
Source Institution: University of Florida
Holding Location: University of Florida
Rights Management: All rights reserved by the source institution and holding location.

Full Text



S Ji toric StAuuUine
? fre ep rvaUoin board

The State of Florida
June 12, 1987


Mr. Thomas B. King
State Fire Protection Specialist
111 Coastline Drive East, Box 39
Jacksonville, FL 32203
Dear Mr. King:

In reply to your inspection report dated May 13, 1987, covering only
those of our buildings classified as "high hazard occupancies," here
follows our reply.
Government House

1. Stairwells

Barriers will either be installed or their use enforced to prevent
occupants from going to the basement in search of an exit.
2. Stairwells and Corridors

Self-closing, positive latch hardware will be installed on all
doors opening into exit egresses/access.

3. Administrative Offices

We will ask the legislature to provide funding so that a second
exit can be installed in the administrative offices.
4. First Floor Foyer Area
Fire rated window boxes will be installed in the lobby and the wood
area above the boxes changed to fire rated material, once we receive
the expected appropriation from the legislature. The same applies
to the East Wing door.
5. Southwest Stairs at Basement
The combustibles have been removed.

6. Northwest Stairs First Floor
The combustibles have been removed.





POST OFFICE BOX 1987 ST. AUGUSTINE, FLORIDA 32085
(904) 824-3355 (SUNCOM) 620-5455








7. Southwest Basement

The flammable liquids stored in the fume hood will be removed.

8. Auditorium West Side

The latch has been repaired so that the door closes and latches
automatically.

9. General

If the fire safety appropriation allows us, we will install a
manual fire alarm system. Otherwise, we will request funding
from the legislature.

10. Fire Sprinkler System

A monthly service to the sprinkler system has been established
and documented by a logbook hanging near the valves.

11. Room 206

An illuminated exit sign will be installed.

12. Room C-2

Instructions have been given not to chock the door open.

13. Southwest Second Floor Access From Room 206

Emergency light bulb will be replaced.

14. Southwest Second Floor Access From Room 206

Library door will hav "Not an Exit" sign painted on it.

15. Southwest Second Floor Library

Obstruction to exit will be cleared.

16. Northwest Stairwell at Basement Level

A self-closing, positive latch will be installed on door.

17. Auditorium West Exit

Obstructing items have been removed.

18. Auditorium Platform West Side

Obstructing items have been removed.

19. Auditorium Raised Floor Area

Flagler College is investigating several possibilities and will be
conferring with their architect about this problem. Once they have
a firm plan of action they will inform us and we will, in turn, inform you.








-3-


Building 32, The Haas House

1. First Floor Main Entry/Exit (interior stair)

The door is a fire rated door. The closing mechanism will be checked
to assure that it is self-closing positive latching. If it is not,
it will be changed. Regarding the enclosed space under the stairs,
the door will be sealed so that the space becomes unusable.

2. First Floor Entry

Doors will not be blocked open

3. First Floor Entry

Combustibles will be removed

4. General

We will request funds from the legislature to provide the house with
an approved fire alarm system.

5. General

We will request funds from the legislature to provide the house with
an approved smoke detector system.

6. General

We will request funds from the legislature to provide the house with
walls and doors that are smoke resistant and to provide the doors with
self-closing mechanisms.

7. Second Floor

The electric extension cord will be removed.



Sin erely,



ecotr i. ron
Deputy Director


HLM:jf







Ji tLoric stAuuStine

Sf6 refea Viion Boa fc

The State of Florida
June 12, 1987


Mr. Thomas B. King
State Fire Protection Specialist
111 Coastline Drive East, Box 39
Jacksonville, FL 32203

Dear Mr. King:

In reply to your inspection report dated May 13, 1987, covering only
those of our buildings classified as "high hazard occupancies," here
follows our reply.

Government House

1. Stairwells

Barriers will either be installed or their use enforced to prevent
occupants from going to the basement in search of an exit.
2. Stairwells and Corridors

Self-closing, positive latch hardware will be installed on all
doors opening into exit egresses/access.

3. Administrative Offices

We will ask the legislature to provide funding so that a second
exit can be installed in the administrative offices.

4. First Floor Foyer Area

Fire rated window boxes will be installed in the lobby and the wood
area above the boxes changed to fire rated material, once we receive
the expected appropriation from the legislature. The same applies
to the East Wing door.
5. Southwest Stairs at Basement

The combustibles have been removed.

6. Northwest Stairs First Floor

The combustibles have been removed.





POST OFFICE BOX 1987 ST. AUGUSTINE, FLORIDA 32085
(904) 824-3355 (SUNCOM) 620-5455





-2-


7. Southwest Basement

The flammable liquids stored in the fume hood will be removed.

8. Auditorium West Side

The latch has been repaired so that the door closes and latches
automatically.

9. General

If the fire safety appropriation allows us, we will install a
manual fire alarm system. Otherwise, we will request funding
from the legislature.

10. Fire Sprinkler System

A monthly service to the sprinkler system has been established
and documented by a logbook hanging near the valves.

11. Room 206

An illuminated exit sign will be installed.

12. Room C-2

Instructions have been given not to chock the door open.

13. Southwest Second Floor Access From Room 206

Emergency light bulb will be replaced.

14. Southwest Second Floor Access From Room 206

Library door will hav "Not an Exit" sign painted on it.

15. Southwest Second Floor Library

Obstruction to exit will be cleared.

16. Northwest Stairwell at Basement Level

A self-closing, positive latch will be installed on door.

17. Auditorium West Exit

Obstructing items have been removed.

18. Auditorium Platform West Side

Obstructing items have been removed.

19. Auditorium Raised Floor Area

Flagler College is investigating several possibilities and will be
conferring with their architect about this problem. Once they have
a firm plan of action they will inform us and we will, in turn, inform you.











Building 32, The Haas House

1. First Floor Main Entry/Exit (interior stair)

The door is a fire rated door. The closing mechanism will be checked
to assure that it is self-closing positive latching. If it is not,
it will be changed. Regarding the enclosed space under the stairs,
the door will be sealed so that the space becomes unusable.

2. First Floor Entry

Doors will not be blocked open

3. First Floor Entry

Combustibles will be removed

4. General

We will request funds from the legislature to provide the house with
an approved fire alarm system.

5. General

We will request funds from the legislature to provide the house with
an approved smoke detector system.

6. General

We will request funds from the legislature to provide the house with
walls and doors that are smoke resistant and to provide the doors with
self-closing mechanisms.

7. Second Floor

The electric extension cord will be removed.



Si.n erely,



Deputy Director
Deputy Director


HLM:jf







Jlh toric 6StAu u6 inc

Sfrcd ervea tion boa rcL

The State of Florida
June 12, 1987


Mr. Thomas B. King
State Fire Protection Specialist
111 Coastline Drive East, Box 39
Jacksonville, FL 32203

Dear Mr. King:

In reply to your inspection report dated May 13, 1987, covering only
those of our buildings classified as "high hazard occupancies," here
follows our reply.
Government House

1. Stairwells

Barriers will either be installed or their use enforced to prevent
occupants from going to the basement in search of an exit.
2. Stairwells and Corridors

Self-closing, positive latch hardware will be installed on all
doors opening into exit egresses/access.

3. Administrative Offices

We will ask the legislature to provide funding so that a second
exit can be installed in the administrative offices.
4. First Floor Foyer Area

Fire rated window boxes will be installed in the lobby and the wood
area above the boxes changed to fire rated material, once we receive
the expected appropriation from the legislature. The same applies
to the East Wing door.

5. Southwest Stairs at Basement

The combustibles have been removed.

6. Northwest Stairs First Floor

The combustibles have been removed.





POST OFFICE BOX 1987 ST. AUGUSTINE, FLORIDA 32085
(904) 824-3355 (SUNCOM) 620-5455








7. Southwest Basement

The flammable liquids stored in the fume hood will be removed.

8. Auditorium West Side

The latch has been repaired so that the door closes and latches
automatically.

9. General

If the fire safety appropriation allows us, we will install a
manual fire alarm system. Otherwise, we will request funding
from the legislature.

10. Fire Sprinkler System

A monthly service to the sprinkler system has been established
and documented by a logbook hanging near the valves.

11. Room 206

An illuminated exit sign will be installed.

12. Room C-2

Instructions have been given not to chock the door open.

13. Southwest Second Floor Access From Room 206

Emergency light bulb will be replaced.

14. Southwest Second Floor Access From Room 206

Library door will hav "Not an Exit" sign painted on it.

15. Southwest Second Floor Library

Obstruction to exit will be cleared.

16. Northwest Stairwell at Basement Level

A self-closing, positive latch will be installed on door.

17. Auditorium West Exit

Obstructing items have been removed.

18. Auditorium Platform West Side

Obstructing items have been removed.

19. Auditorium Raised Floor Area

Flagler College is investigating several possibilities and will be
conferring with their architect about this problem. Once they have
a firm plan of action they will inform us and we will, in turn, inform you.










Building 32, The Haas House

1. First Floor Main Entry/Exit (interior stair)

The door is a fire rated door. The closing mechanism will be checked
to assure that it is self-closing positive latching. If it is not,
it will be changed. Regarding the enclosed space under the stairs,
the door will be sealed so that the space becomes unusable.

2. First Floor Entry

Doors will not be blocked open

3. First Floor Entry

Combustibles will be removed

4. General

We will request funds from the legislature to provide the house with
an approved fire alarm system.

5. General

We will request funds from the legislature to provide the house with
an approved smoke detector system.

6. General

We will request funds from the legislature to provide the house with
walls and doors that are smoke resistant and to provide the doors with
self-closing mechanisms.

7. Second Floor

The electric extension cord will be removed.



Sin erely,



/ Deputyr e. ron
Deputy Director


HLM:jf