Group Title: Historic St. Augustine: Permits, State Inspections, City Forms, HARB
Title: Division 1 - General Requirements
ALL VOLUMES CITATION MAP IT! THUMBNAILS PAGE IMAGE ZOOMABLE
Full Citation
STANDARD VIEW MARC VIEW
Permanent Link: http://ufdc.ufl.edu/UF00095503/00002
 Material Information
Title: Division 1 - General Requirements
Series Title: Historic St. Augustine: Permits, State Inspections, City Forms, HARB
Physical Description: Maintenance record
Language: English
Physical Location:
Box: 8
Divider: DOS 8449-A, Govt. House 87-88
Folder: Permits, State Inspections, City Forms, HARB
 Subjects
Subject: Saint Augustine (Fla.)
48 King Street (Saint Augustine, Fla.)
Government House (Saint Augustine, Fla.)
Spatial Coverage: North America -- United States of America -- Florida -- Saint Johns -- Saint Augustine -- 48 King Street
Coordinates: 29.892465 x -81.313142
 Record Information
Bibliographic ID: UF00095503
Volume ID: VID00002
Source Institution: University of Florida
Holding Location: University of Florida
Rights Management: All rights reserved by the source institution and holding location.

Full Text



DIVISION 1 GIIERAL RIBIRMES


01015 BASE BID, ALTERNATES, ANM ALLOWANCES

BASE BID WORK shall include the following:

a. Exterior:

(1) Provide new handicapped ramp to the southernmost entry to
the Main Lobby from the east.

(2) Relocate one existing condensing unit and provide one new
condensing unit, respectively (and as described below), on the flat roof
above the HSAPB offices.

b. First Floor East Wing Multipurpose Room:

(1) Provide new veneer plaster at existing exterior walls and
interior columns, new portions of suspended ceilings, on one wall of the
vault converted to Staff Room, and new partition under stair.

(2) Repair existing and provide new ornamental plaster. In-
stall existing ornamental plaster brackets.

(3) Provide new floor slab over existing tunnels and fill.
S-... Provide new tunnel below floor connecting new HVAC equipment with exis-
ting tunnel. Provide new CMU partitions in tunnels separating supply
from return; partitions shall be provided with access doors.

(4) Provide new landing at steps from Main Lobby into East
Wing. Relocate existing steps. Provide new handrails.

(5) Provide new surface-mounted vertical rod exit devices, new
thresholds, and new coordinators on south doors of East Wing. Install
existing historic hardware lever handles in fixed position for use as
pulls on the exterior of these doors. Provide new doors at entrance from
Main Lobby and at new equipment area below stairs. If possible utilize
historic hardware lever handles on these doors also. Coordinate keying
of new hardware with the Owner.

(6) Provide reconstructed baseboards and other millwork as
required.

(7) Provide new sheet vinyl flooring in Staff Room. See
Alternate for carpet in Multipurpose Room.

(8) Paint existing and new surfaces not otherwise finished.

(9) Provide a new 5-ton (size to be verified) HVAC unit to
serve the East Wing through existing tunnels ndj new tunnel below the
floor. The air handler shall be located in a(-V h6ur rated space
below the stair to the second floor. The supply side shall be ducted to
floor registers located above existing tunnel branches on the north side
of the room. The return side shall use the existing tunnel as a plenum;
return air registers shall be located above existing tunnel branches on
the south side of the room. The new condensing section shall be located






DIVISION 1 PAGE 2


on the flat roof above the HSAPB offices. The existing condensing sec-
tion serving the second floor of the East Wing shall be relocated adja-
cent to the new unit on the flat roof.

(10) Provide a new 150-amp panel served from the existing main
panel located in the basement. Locate the panel in the new HVAC space
below the stair to the second floor. Provide new power circuits to
convenience outlets in the Multipurpose Room and Staff Room and to the
new HVAC equipment. Provide a new weatherproof disconnect at the new
condensing unit on the roof. Provide new lighting circuits to the Staff
Room and Multipurpose Room, including circuits for future track lighting
in the ceiling. Provide new light fixture in the Staff Room. Reuse
existing light fixtures in the Multipurpose Room; existing fixtures
shall be on diners.

S (11 ) Provide exit signs, smoke detectors, and an intrusion
alai system coordinated with existing systems as necessary.

c. First Floor Auditorium Area:

(1) As described in detail below, provide a continuous C-l
hour separation between the Main and South Lobbies and the Auditorium.

(a) Remove the existing partition on east side of Audito-
rium and replace with a -1/)hour rated partition. Remove, store, and
reinstall acoustical curtain. Provide new fire-rated doors in the new
east partition, including doors providing access to the rear of each
display case. Provide new support channels in the east partition for new
portable display cases to be provided by others. Existing display win-
dows and ticket window shall remain. Provide fire-rated rolling fire
shutter above ticket window; remove and reinstall cabinets and counter-
top at ticket window. If possible, reinstall existing marble on Lobby
side of existing partition where marble was replaced by later finishes.

(b) On the east and south sides of the Stage provide a
new -/ hour partition located 3'-4" away from the existing partition,
thus forming a corridor providing rear access to existing display areas.
Remove existing stage floor in the area of the new corridor. Remove the
existing glass and plywood fronts of the display cases and enlarge the
fronts to the full area available. Provide access to the rear of new
cases provided under this contract.

\ (c) Existing ductwork above the new east partition shall
be removed and replaced with new ductwork shaped to be located entirely
to the east of the new rated partition. Existing diffusers serving the
Main Lobby shall remain, but diffusers with fire dampers shall be pro-
vided to serve the Auditorium west of the partition. Existing ductwork
above the new corridor at the east and south of the Stage shall remain,
but diffusers serving the Stage shall be fire-dampered. New diffusers
shall be provided in the new and existing ductwork to serve all display
cases and new corridor areas; return air shall pass through new grilles
into the Lobbies.

(d) New convenience outlets shall be located adjacent to
each display case for power and for lighting provided by others. Elec-
trical work for display cases and new corridor to be served by existing


/s37r~~







DIVISION 1 PAGE 3


circuits from existing panel.

c. Second Floor Corridor and East Wing Office Area:

(1) Drop condensate line through floor at existing air handler
in East Wing offices and run above new ceiling in first floor Multipur-
pose Room to closest hub in an existing sanitary drain. Line shall be
insulated.

(2) The existing circuit from the existing second floor panel
serving the existing HVAC condensing unit located on the balcony shall
be rerouted to the same unit after it is relocated on the flat roof
above the HSAPB offices. Relocate the disconnect serving the unit.

ALTERNATE 1 SHALL INCLUDE THE FOLLOWING:

Under an allowance of $30.00 per square yard, provide new carpeting in
the Multipurpose Room. Carpet shall be selected by the Owner from
samples submitted by the Contractor. Allowance shall include all costs,
including overhead, profit, installation, material, labor, delivery, and
storage (if required).

01040 SPECIAL PROVISIONS

Contractor shall prepare, file and post a Notice of Commencement as
required by the Mechanics' Lien Law, Chapter 713, Florida Statutes.

Preconstruction, safety and progress conferences shall be required.

Contractor shall be required to secure all construction materials and
building equipment during periods designated by US Weather Bureau as
hurricane warnings or alerts.

All historic materials and artifacts discovered at the site shall remain
the property of the Owner.

01050 MISCE.LANEOUS RQUIMI NTS

All work shall conform with applicable local and state codes.

01060 QUALITY CONTJR, MATERIALS AND SUBSTITUTIONS

Inspection and testing of construction materials and activities by an
approved engineering testing company may be required. If required, all
testing costs will be paid by the Owner.

No substitutions will be considered unless written request has been
submitted to the Architect for approval. Any substitutions approved by
the Architect will be set forth in a change order.

01300 SUBMITTALS

SHOP DRAWINGS: Complete shop drawings shll be required to be submitted
to the Architect for approval for all fabricated items prior to
fabrication.













DIVISION 1 PAGE 4


MATERIALS: A complete list of all materials, equipment, etc., together
with manufacturers' drawings and catalog information shall be submitted
to the Architect for approval prior to ordering material or equipment.

COST BREAKDOWN: An itemized cost breakdown shall be required to be
submitted to the Architect for approval within 30 days of Notice to
Proceed.

PROJECT SCHEDULE: An itemized project schedule shall be required to be
submitted to the Architect for approval within 30 days of Notice to
Proceed.

01500 TIMORAR! FACILITIES

GENERAL: Owner shall provide drinking water and temporary toilets
for use during construction in compliance with local codes. Facilities
shall be located at the discretion of the Owner. A job telephone will be
provided by the Owner.

TEMPORARY UTILITIES: Temporary services are not required except within
the building; Contractor shall make all necessary connections and remove
all evidence of temporary services at completion of work.

PROTECTIONS: Contractor shall protect existing site improvements around
existing building from damage during construction activities. Contractor
shall be required to replace o repair construction related damage, at no
additional cost to Owner, to condition existing at start of construction.

PROJECT SIGN: Contractor shall provide a project sign if required by
funding source. If required, provide 4' x 8' painted sign located as
directed by the Owner. Sign shall include project name, Owner's name,
Agency's name, General Contractor's name, and Architect's name.

01700 PRIJ~EC CLO SXUT

FINAL CLEANING: Clean new and adjacent construction; provide final
painting.

PUNCH LIST: Complete all items noted on the Substantial Completion Punch
List.

FINAL SUBMITTALS: Provide all equipment and operational manuals,
guarantees, releases of lien, and as-built drawings.




























DIVISION 2 SI1E WOM

02040 SIE WORK

SCOPE: As required for new handicap ramp.

FILL: Clean sand, free of organic material.

TOPSOIL: Clean, suitable for plantings.

COMPACTION: Subgrade under walks and new construction shall be compacted
toa density fo 95% modified Proctor inaccordance with ASIM D1557.

CONCRETE: Structural concrete as specified under Division 3. Walks shall
be 5" thick, 3,000 psi concrete reinforced with 6x6 10/10 wwm.























DIVISION 3 CONCREBT


03310 CONCRETE WORK

MATERIALS: Aggregate to ASTM C-33, cement to ASTM C-150, reinforcing to
ASTM A-615 Grade 60, welded wire mesh to ASTM A-185.

FORMS: Plywood: 5-ply 5/8" form plywood. Form coating: penetrating,
sprayable chemical sealer Fed. Spec. P-0-361. Expansion Joint Fiber
Filler: ASTM D-175. Joint Sealer: Rubberized Asphalt Fed. Spec. SSS-
164. Curing compound: Membrane forming, resin base ASTM C-309.

READY-MIXED CONCRETE: ASTM Serial Designation C-94.

CONCRETE TESTING: Mix design not required; field testing by an approved
engineering testing laboratory if required by Owner.

PROTECTION: Protect from injurious action by rain, sun, and mechanical
injury.

CURING: Start as soon as concrete has hardened, or as soon as forms are
removed.

CLEANING: Remove from premises all drippings, wasted concrete, or other
concrete not incorporated in the work.
























DIVISION 4 MASON:


Not required.

DIVISION 5 -. MEMLS

05500 METAL FABRICATIONS

MATERIALS: Structural steel to ASTM A-36. Pipe to ASTM A-53, Schedule
40. Reinforcing Steel to ASTM A-615, Deformed, Grade 40. Hot-Dip Zinc
Galvanizing to ASTM A-123. Fastenings as required, complying with
standard ASTM specifications. Primer: red lead or zinc chromate.

SHOP TREATMENT: Hot dip galvanize all ferrous metal items to be exposed
to the weather; coat all other metal fffms with one heavy coat of metal
primer.

FABRICATION: Fabricate using best current practices and to applicable
industry standards.

DETAIL REQUIREMENTS: Pipe railings and handrails shall be welded steel
with joints ground smooth.


















06100 RIUSJ CARZPENTR


MATERIALS:

Structural timber: grade-marked SYP.
Studs: grade-marked Douglas fir or western red cedar.
Plywood: Douglas fir, US Commercial Standard CS 45.
Adhesives: Fed. Spec. MMM-A-125.
Lag Bolts: Fed. Spec. FF-B-561.
Nails and Spikes: Fed. Spec. FF-N-105, FF-S-606.
Bolts: Fed. Spec. FF-B-571, FF-B-575.
Wood Screws: Fed. Spec. FF-S-111.
Preservative Treatment: Fed. Spec. TTIW-571, TT-W-572.
Flameproof Treatment (if required): AWPA No. C-20B.
Rough hardware: provide as required.

TREATMENT: All wood in contact with concrete, steel or masonry shall be
pressure-treated. Lumber shall be fire-retardant treated in areas as
required by code.

TEMPORARY SHORES AND BRACING: Provide for all work adequate for safety
of the project and safety for workmen.

06200 FINISH CARPENTY

QUALITY STANDARDS: Architectural Woodwork Institute, "Quality Standards
of te Architectural Woodwork Industry." Custom grade.

MATERIALS: Work to match original shall match original grades and
species as closely as possible. Contemporary base and wall cabinets in
Staff Room shall be finished with plastic laminate, 1/16" thick for
horizontal surfaces and 1/32" thick for vertical surfaces. Display cases
in contract shall be painted plywood.

HARDWARE: Provide cabinet hardware as noted.


FABRICATION: Meet AWI Section 400.


























DIVISION 7 7HERM. & MDISTRB PREHE RTCN

07920 SEALING A) CMJLKING

APPLICATION: Use sealants at exterior, caulking at interior.

MATERIALS:

Sealant: gun grade, polyurethane-based elastomeric material
conforming to FS-TT-S-00227E, Class A, Type 2 (non-sag).
Caulking: one-part acrylic latex gun grade caulking compound.
Backup materials, joint cleaner, joint primer-sealer: as
recommended by sealant and caulking manufacturers.

INSTALLATION: Clean joints, install backer rods and sealant or caulking
as recommended by the manufacturer. Remove excess and spillage. Complete
caulking prior to final coat of paint.



















DIVISION 8 DOORS AND WIN S

08220 WOOD AN) METAL DOORS AN) METAL FRAMES

MATERIALS:

Wood doors: Stock doors as indicated.

Metal doors and frames: Comply with SDI "Recommended Specification
Standards for Standard Steel Doors and Frames," SDI-100. Provide UL
labels. Install in accordance with NFPA 80.

08800 GLASS AN GLAZING

STANDARDS: Comply with Florida Safety Galzing Standards and ANSI Z-97.1.

MATERIALS AND INSTALLATION:

Material: 1/4" thick polished plate glass and laminated safety
glass.

Installation: In accordance with Flat Glass Jobbers Association
Glazing Manual specifications.

08710 FINISH HARiMARE

APPLICATION: As required for proper operation, fastening and locking at
new and existing doors where indicated.

MATERIALS: Commercial grade stock hardware compatible with the remaining
original hardware. Key into the existing system. Provide panic devices
at required exits as indicated.










09220 PLASTER AND VENEER PLASTER

APPLICATION: Where necessary, patch existing plaster with new three-coat
plaster. Install existing decorative brackets which have been removed
and stored. Provide veneer plaster as indicated.

FIRE RATINGS: Where indicated, construct assemblies to obtain fire-
rating as required by applicable codes, and provide manufacturers' test
certificates.

STANDARDS: Plaster to ANSI A421, "Specifications for Gypsum
Plastering." Veneer plaster to Gypsum Association GA-150, "Application
of Gypsum Base for Veneer Plasters and Application of Gypsum Veneer
Plaster."

THICKNESS: Plaster patching shall match existing but not less than 3/4".
Veneer plaster: 3/32".

MIX: Plaster to ANSI A421. Veneer plaster as recommended by
manufacturer.

INSTALLATION: Plaster to ANSI A42.. Veneer plaster on metal studs or
metal or wood furring with one layer of gypsum base board and two coats
of plaster.

09260 GYPSOM WALB(ARD AND SHAFTWALL

APPLICATION: Shaftwall at Auditorium east wall partition, gypsum
wallboard at new partition behind stage.

STANDARDS: Gypsum Association Specification GA-216 and ANSI A42.4.

FIRE RATED ASSEMBLIES: Provide materials and installations identical
with applicable assemblies which have been tested and listed by
recognized authorities.

MATERIALS: Gypsum board to ASTM C-36, Type "X" and 5/8" thick where fire
rated, 1/2" elsewhere, water-resistant in Staff Room. Shaftwall to
applicable Gypsum Association specifications. Joint treatment:
perforated type joint tape and ready-mixed vinyl type joint compound.
Support systems shall be metal studs and metal suspension systems to
industry standards.

09650 RESILIENT FLOORING

MATERIAL AND INSTALLATION: Sheet vinyl, Armstrong Corlon or approved, as
selected for Staff floor. Vinyl base: 4" high, premolded corners, cove
type, installed to manufacturer's standards.

09900 PAINTING

COLORS: Colors and gloss shall match existing or shall be compatible
with existing as determined.


DIVISION 9 FINISHES























DIVISION 9 PAGE 2


MATERIALS: First-line products of Glidden, Sherwin-Williams, Devoe, or
other approved national manufacturers.

INSTALLATION: In strict accordance with manufacturers' instructions.

SCHIDULE:

Exterior:

Metals: Primer and two coats alkyd industrial enamel.
Wood: Primer and two coats alkyd gloss or semigloss enamel.

Interior:

Gypsum board and shaftwall: Two coats lowgloss latex enamel.
Plaster and veneer plaster: Two coats of flat latex or alkyd
to match existing.
Metals: Primer and two coats alkyd enamel.
Painted wood: One coat undercoater, two coats semigloss alkyd
enamel.
Stained wood: Stain, one coat snading sealer unless other
finishes are documented or selected.



























DIVISION SCIATIES

Not required.

DIVISION 11 -= b XIMWIT

11040 STAFF ROXM EQUIPMEIR

Provide KitchenAid residential dishwasher. Refrigerator and microwave
oven are not in contract.

DIVISION 12 14

Not required.











test data

fire-rated construction acoustical performance
rating description A test no. STC description & test no.
Lo)
1 hr. Cavity Shaft Wall--4" SHEETROCK Brand FIRECODE "C" gypsum panels one N/A A
side-1" USG shaft wall liner panels set betw USG steel C-H studs 24" o.c.-panels apple
vert to side opp liner panels & screw att-joints fin-U of C 4-3-75t wt 8 width 31/"
2 hr. Cavity Shaft Wall-2 layers W" SHEETROCK Brand FIRECODE "C" gypsum panels one 39 USG-750302 B
side--" USG shaft wall liner panels set betw USG steel C-H studs 24" o.c.-panels appi 47 Based on 1" sound attend. fire blankets in
vert to side opp liner panels & screw att-joints fin-U of C 4.2-75-UL Des U438f cavity-BBN-750706
wt 9 width 31"
2 hr. Cavity Shaft Wall--/" SHEETROCK Brand FIRECODE "C" gypsum panels-1" USG N/A C
shaft wall liner panels set betw USG steel C-H studs 24" o.c.-single layer panels ea side
appi vert & screw att-joints stag on opp sides & fin-U of C 6-23-751 wt 9 width 3V2"
2 hr. est Cavity Shaft Wall-2 layers W SHEETROCK Brand FIRECODE "C" gypsum panels one 51 BBN-750412 D
side-1" USG shaft wall liner panels set betw USG steel C-H studs 24" o.c.-RC-1 chan
spaced 24" o.c.-1W THERMAFIBER sound atten fire blkts-panels & RC-1 chan screw aft
to side opp liner panels-base layer appi horiz-face layer apple vert-joints fin-est, fire
rating based on U of C 2-8-72 and U of C 6-23-75t wt 10 width 4"
3 hr. est Cavity Shaft Wall-3 layers %" SHEETROCK Brand FIRECODE "C" gypsum panels one N/A E
side-1" USG shaft wall liner panels set betw USG steel C-H studs 24" o.c.-panels screw
att to side opp liner panels with joints stag-base & face layers apple vert-mid layer appi
horiz-joints fin-est. fire rating based on U of C 2-16-72t wt 12 width 4%"
4 hr. est Cavity Shaft Wall-2 layers W SHEEETROCK Brand FIRECODE "C" gypsum panels N/A F
face side-1" USG shaft wall liner panels set betw USG steel C-H studs 24" o.c.-1" liner
panels & W gypsum panel core screw att to studs-horiz USG met fur chan 24" o.c.
-face side panels screw att to fur chan-panels apple vert with joints stag-joints
fin-est. fire rating based on U of C 5-24-74t wt 16 width 61/4"
tFire rating also applies with IMPERIAL FIRECODE "C" Base and veneer finish surface.



sound transmission loss-db

band center frequency-Hz
test no. method 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 STC
BBN-750412 Lab 27 30 38 42 47 50 53 54 55 57 57 58 59 56 55 58 51
BBN-750706 Lab 24 26 36 40 44 46 48 50 52 53 54 54 55 54 50 52 47
USG-750302 Lab 20 22 25 33 32 35 36 39 41 43 43 45 41 40 43 46 39


rated assemblies


:-^ ||t -- I



test A-1 Hr.
U of C 4-3-75









I I, 1
"i 1i
-'- f .-;--


test D-2 Hr. est.
51 STC-BBN-750412


7< 'Xi11 -I -/


test B-2 Hr.
U of C 4-2-75
UL Des U438
39 STC USG-750302


test B-2 Hr. est.
Based on U of C tests
47 STC-BBN-750706


--~- -- r----'- I





test E-3 Hr. est.
Based on U of C 2-16-72


test F-4 Hr. est.
Based on U of C 5-24-74


UNITED STATES GYPSUM 3








partitions/test data


fire fire-rated construction acoustical performance
rating description & test no. STC descdrption A test no.
1 hr. Steel Stud-W SHEETROCK brand FIRECODE "C" gypsum panels-2W" USG studs 24" o.c.- 45 TL6-42 A
single layer panels ea side appi vert & screw att--1" THERMAFIBER sound atten fire blkts- 48 Based on 3W studs & 2" blankets-
joints fin-perimeter caulked-T-3362-OSU wt 5 width 3W SA-800422
1 hr. est Steel Stud-%" SHEETROCK brand FIRECODE gypsum panels-2%" USG studs 24" o.c.--1" 55 CK-684-14 B
THERMAFIBER sound atten fire blkts-2 layer-base layer y" SHEETROCK brand panels 53 Based on W thick panels-CK-64-13
screw att-%" face layer screw att-joints fin-perimeter caulked-est. fire rating based on
T-1174-OSU wt 7 width 44"
1 hr. est Steel Stud--h" SHEETROCK brand FIRECODE "C" gypsum panels--2z" USG studs 24" o.c. 50 SA-800504 C
-single layer panels one side apple vert & screw att--1" THERMAFIBER sound atten fire bikts 41 Based on same construction without
-2 layers opp side-panels appi vert & screw att-joints stag & fin-perimeter caulked blankets-TL-69-148
-est. fire rating based on T-3362-OSU wt 7 width 4"
1 hr. est Steel Stud-%" SHEETROCK brand FIRECOpE "C" gypsum panels-3%" USG studs 24" o.c. 50 SA-800417 D
-single layer panels one side apple vert & screw att-2" THERMAFIBER sound atten fire blkts
-2 layers opp side-panels appi vert & screw att-joints stag & fin-perimeter caulked
-est. fire rating based on T-3362-OSU wt 8 width 5W
1 hr. Steel Stud-2 layers W SHEETROCK brand gypsum panels ea side-1l" USG studs 24" o.c. 53 Based on SHEETROCK brand E
-panels apple vert & screw att-joints stag & fin-perimeter caulked-U of C 9-21-64 FIRECODE "C" panels, 2W' studs & 1"
wt 9 width 3%" sound atten. fire blankets-CK-54-40
1 hr. Steel Stud-%" SHEETROCK brand FIRECODE gypsum panels-3%" USG studs 24" o.c. 42t USG-17FT-&H F
-single layer panels vert or horiz appi & screw att-joints stag & fin-perimeter caulked- 48 Based on 3" sound attend. fire blankets in
T-1174-OSU-based on panels horiz appl-GA-WP-1200 wt 6 width 4W cavity and FIRECODE "C" Panels-
SA-800415
51 Based on 3" sound attend. fire blankets 25"
wide, creased to fit cavity-SA-82010
1 hr. Steel Stud-W SHEETROCK brand FIRECODE gypsum panels-lW USG studs 24" o.c. 381 TL-64-29 G
-single layer panels vert apple & screw att 12' o.c.-joints fin-perimeter caulked
-Uof C 7-31-62 wt 5 width 2W7
1 hr. Steel Stud-%" SHEETROCK brand FIRECODE gypsum panels-2W USG studs 24" o.c.- N/A H
1W THERMAFIBER sound atten fire bikts-panels apply horiz & screw-att-joints opp-vert
joints unfin-horiz joints fin-CEG 7-13-83 wt 6 width 3%"
1 hr. Steel Stud Chase Wall-" SHEETROCK brand FIRECODE gypsum panels ea side-1%" N/A I
USG studs 24" o.c. In 2 rows spaced 64" apart-%" gypsum panel gussets or sti run braces
spanning chase screw-att to studs-panels apple vert & screw att-joints stag & fin-
-UL Des U420 wt 6 width 10%"
2 hr. Steel Stud-2 layers W SHEETROCK brand FIRECODE "C" gypsum panels ea side-2W or 55 Based on 3W studs and 1W J
3W USG studs 24" o.c.-1", 1W or 2" THERMAFIBER sound atten fire blkts stapled-panels appi blankets-SA-800421
vert & joints stag-base layer screw att-face layer strip lamin or screw att-joints fin- 541 Based on lamin. face layer-
perimeter caulked-rating based on assembly with or without sound atten blankets USG-114-FT-G&H
-UL Dee U412 wt 10 width 4W 53 Based on 24" studs, screw-att face layer
and 1W" blankets-CK-54-40
2 hr. Steel Stud-2 layers SHEETROCK brand FIRECODE gypsum panels plain or vinyl faced vert 48 Based on 3%" studs and W" SHEETROCK K
appi ea side--2V or 3%" USG studs 24" o.c.-base layer screw att-face layer lamin or screw Brand FIRECODE "C" panels-BBN-770400
att-joints fin or unfin-perimeter caulked-UL Des U411 wt 12 width 6W
2 hr. Steel Stud-2 layers W SHEETROCK brand FIRECODE gypsum panels ea side-2" USG studs 51 Based on 2W blankets in cavity- L
24" o.c.-panels appi horiz & joints stag-base and face layers screw att-joints fin GA-WP-1548
-GA-WP-1548 wt 12 width 5"

2 hr. Steel Stud-2 layers W SHEETROCK brand FIRECODE "C" gypsum panels-1W USG studs N/A M
24" o.c.-2 layers ea side vert appi & screw att-joints fin-U of C 6-15-65 wt 9 width 3%"

2 hr. Steel Stud Chase Wall-2 layers SHEETROCK brand FIRECODE gypsum panels ea side- N/A N
1%" USG studs 24" o.c. in 2 rows spaced 6V" apart-%" gypsum panel gussets or sti run braces
spanning chase screw-att to studs-panels appi vert & screw att-joints stag & fin-
UL Des U420 wt 13 width 12"
2 hr. est Steel Stud Chase Wall-2 layers SHEETROCK brand FIRECODE "C" gypsum panels ea side- 55t USG-134-FT-G&H O
1%" USG studs 24" o.c. In 2 rows spaced 5W apart--W gypsum panel gussets spanning chase
att to studs at qtr points-panels appi vert& screw att-1 THERMAFIBER sound atten fire bikts
-joints stag & fin-perimeter caulked-est. fire rating based on UL Des U412 wt 11 width 11"

3 hr. Steel Stud-3 layers W SHEETROCK brand FIRECODE "C" gypsum panels ea side-1W USG 59 Based on assembly with 1W P
studs 24" o.c.-base layers apple vert-face layer apple horiz-panels screw-att with joints stag sound attend. fire blkts. in
& fin-perimeter caulked-rating based on assembly with or without sound atten fire blankets cavity-SA-830112
-UL Des U435 wt 13 width 4%"

3 hr. Steel Stud-%" SHEETROCK brand FIRECODE "C" panels ea side-fireproofed steel truss N/A Q
-2" USG studs 24" o.c. In 2 rows spaced 8" apart-%" gypsum panel gussets spanning chase
att to stud at qtr & ctr points-panels appi vert & screw-att-joints stag & fin
-UL Des 1805 wt 6 width 14%"
3 hr. Steel Stud-3 layers Y" SHEETROCK brand FIRECODE "C" gypsum panels ea side--%" USG N/A R
studs 24" o.c. In 2 rows spaced 3" apart-steel truss member-gypsum panel gussets or
sti run braces spanning chase screw-att to studs-panels appi vert & screw att-joints stag & fin-
2 hr, rating applies with 2 layers panels ea side-UL Des U438 wt 13 width 9Y
4 hr. Steel Stud-4 layers W SHEETROCK brand FIRECODE "C" gypsum panels ea side-1%" USG 62 Based on assembly with 1" sound S
studs 24" o.c.-base layers apple vert-face layer appi horiz-panels screw att with joints stag attend. fire blankets in cavity-SA-830113
& fin-perimeter caulked-rating based on assembly with or without sound atten fire blankets
-UL Des U435 wt 17 width 5W%
USG Steel Stud styles ST and STL will provide above fire and sound ratings. fBased on 11-freq.


2 Copyright 1984, United States Gypsum Company







IUS Ste-Fa e Drw l S ytm SA.- 923


partitions


description
These lightweight, fire and sound-resistant assemblies consist of one
or two layers of SHEETROCK Brand Gypsum Panels screw-attached to
steel framing. A specially designed self-tapping steel screw with a rust
inhibitive coating is used to attach the panels to the framing. The
systems are completed with a U.S.G. joint system and decorating-
both steps unnecessary in walls when predecorated vinyl-surfaced
TEXTONE Gypsum Panels are used.
Gypsum panels for these assemblies are available in three thick-
nesses and seven types (see Specifications). Systems using
SHEETROCK Brand FIRECODE and FIRECODE "C" Gypsum Panels, with a
specially formulated core, obtain higher fire ratings than regular gyp-
sum panels (see table page 2). These versatile panels are applied to
USG Steel Studs or Metal Furring Channels to meet design require-
ments for fixed interior partitions-divider, corridor, party and chase
walls; furred and suspended ceilings; wall furring and column firep-
roofing, as outlined below:
1. Partitions-Single-layer %" SHEETROCK Brand FIRECODE "C"
Panels applied to USG Steel Studs, set in runners, provide eco-
nomical 1-hour fire-rated partitioning for corridors or within units.tA
1-hour rating is also available with /2" thick panels and 1V2"
THERMAFBER Sound Attenuation Fire Blankets installed in the stud
cavity. The studs are available in several widths and types (see Specifi-
cations, page 16) and cut to lengths required for the job. Double-layer
/2" SHEETROCK Brand FIRECODE "C" Panels attached to 21/2" or 3W
studs spaced 24" o.c. provide a 2-hour fire rating plus sound control
suitable for party walls. Multi-layer V2 SHEETROCK Brand FIRECODE "C"
Panel assemblies offer 3- and 4-hour fire ratings and up to 62 STC
sound control, yet are much lighter weight and thinner than concrete
block. These assemblies also provide a 3-hour fire-resistant enclosure
for steel trusses in staggered truss systems. Where added partition
width is required, double rows of studs are erected to provide chase
walls with up to 2034" net pipe chase width (see page 7).
Shaft Walls-Gypsum panels, assembled with gypsum shaft wall
liner and specially shaped C-H Studs, offer systems ideally suited for
enclosing elevator shafts, stairwells and other vertical shafts in core
areas of multi-story buildings (see separate Shaft Wall Folder SA-922
for applications).
2. Ceilings-Single-layer %" SHEETROCK Brand FIRECODE "C"
Panels screw-attached to furred or suspended USG Metal Furring
Channels 24" o.c. provide a 3-hour fire rating including beam protec-


sound-tested assemblies
single layer double layer







test F-42 STC test B-55 STC
USG-17-FT-G & H CK-684-14







i '/

test F-48 STC test C-50 STC
SA-800415 SA-800504


tion (see page 13). The systems are also suitable for separate beam
protection and for exterior ceilings and soffits with USG Exterior Gyp-
sum Ceiling Board facings.
3. Wall Furring-With Foil-Back Gypsum Panels screwed to USG
Metal Furring Channels, this construction provides an excellent vapor
retarder as exteriorwall furring (see page 10). Panel application to USG
Z-Furring Channels with semi-rigid insulation provides afully insulated
wall at a cost competitive with many non-insulated furred walls.
4. Column Freproofing-SHEETROCK Brand FIRECODE "C" Panels
screw-attached to steel studs at column comers and finished with
comer bead and joint compound, offer lightweight, compact fire pro-
tection for steel columns (see page 9).

function and utility
Adaptable to virtually every type of new construction-commercial,
institutional, industrial and residential-or in modernization to provide
smooth, durable interior surfaces.
Fire Resistant-Constructed of noncombustible components. Es-
tablished fire ratings available to meet design requirements; partitions
up to 4 hours, ceilings up to 3 hours including beam, column fireproof-
ing up to 4 hours.
Sound Isolatlon-STC ratings up to 62 for multi-layer, 55 for double-
layer and 48 for single-layer partitions; 54 for single-layer ceilings.
THERMAFIBER Sound Attenuation Fire Blankets improve sound control.
Lightweight-These thin, drywall assemblies weigh only 5 to 17 psf,
reduce dead load and save floor area.
Economical-Low material cost and speed of erection provide
realistic and competitive construction costs.

limitations
1. Non-load bearing.
2. Exposure to excessive or continuous moisture and extreme tem-
peratures should be avoided.
3. Maximum frame spacing is 24" o.c., except when single-layer ceil-
ing panels are applied with long edges parallel to joists and used as a
base for spray-applied texture finish, max. frame spacing is 16" o.c.
4. In ceiling design, certain precautions concerning construction,
isolation and ventilation are necessary for good performance (see
_S~gcifications, page 16).


multi-layer


test E-53 STC
CK-654-40


test 1-55 STC
SA-800421
chase wall








test N-55 STC
USG-134-FT-G & H


test R-62 STC
SA-830113


test 0-59 STC
SA-830112


UNITED STATES GYPSUM 3