Group Title: Historic St. Augustine: Sprinkling System - Government House
Title: [Correspondence re: Government House]
ALL VOLUMES CITATION MAP IT! THUMBNAILS PAGE IMAGE ZOOMABLE
Full Citation
STANDARD VIEW MARC VIEW
Permanent Link: http://ufdc.ufl.edu/UF00095496/00005
 Material Information
Title: Correspondence re: Government House
Series Title: Historic St. Augustine: Sprinkling System - Government House
Physical Description: Correspondence
Language: English
Publication Date: 1986
Physical Location:
Box: 8
Divider: Government House Maintenance
Folder: Sprinkling system - Government House
 Subjects
Subject: Saint Augustine (Fla.)
48 King Street (Saint Augustine, Fla.)
Government House (Saint Augustine, Fla.)
Spatial Coverage: North America -- United States of America -- Florida -- Saint Johns -- Saint Augustine -- 48 King Street
Coordinates: 29.892465 x -81.313142
 Record Information
Bibliographic ID: UF00095496
Volume ID: VID00005
Source Institution: University of Florida
Holding Location: University of Florida
Rights Management: All rights reserved by the source institution and holding location.

Full Text







TRANSMITTAL LITER


DEPARTMENT OF GENERAL SERVICES
BUREAU OF CONSTRUCTION
PROJECT DEVELOPMENT SECTION
ROOM 512 ARSON BUILDING
TALLAHASSEE, FLORIDA 32301
488- 5885


TO: Mr. Hector Miron
Deputy Director
St. Augustine Preservation Board
Department of State
State of Florida
P. O. Box 1987
St. Augustine, Fl. 32084


DATE: March 21, 1986

RE: DOE-UPN


ITEMS COPIES SUBJECT PREPARED BY



FOR YOUR INFORMATION








.2




MAR 2 A 1986


H.S.A.P,B,


MN/ab
xc: Bureau File
Joe Johnston


Very trulyours,



Project Director
Project Development Section





S\TE OF FLORJDA
DEPARTMENT OF

GENERAL SERVICES
Larson Building, Tallahassee 32301
Ronald W. Thomas, Executive Director
March 19, 1986


DIVISIONS
* ADMINISTRATION INFORMATION
* BOND FINANCE SERVICES
* BUILDING CONSTRUCTION MOTOR POOL
AND PROPERTY MANAGEMENT PURCHASING
* COMMUNICATIONS SECURITY
SURPLUS PROPERTY


Please address reply to.


MEMORANDUM


TO: Nat Nadler
Project Director

FROM: Thomas A. Sechler, P.E.Z JJ
Administrator
Design Review and Permitting Section


Project Name: Sprinklers-Govt. House, St. Augustine Preservation Bd.


Project No.:


DOE-UPN


Project Phase: As-Built Drawings


The subject document has been reviewed and is:


D Approved


1 Approved with attached comments


No comment


Disapproved.


Requires Fire Marshal approval. We did not review.
NAT, PLEASE FORWARD ATTACHED COMMENTS TO MR. HECTOR MIRON.


TAS/srn


Form D-7
7/01/85


George Firestone
Secretary of State
Doyle Conner
Commissioner of Agriculture


Gerald A. Lewis
Comptroller
Ralph D Turlington
Commissioner of Education


El


El~


Bob Graham
Governor


Jim Smith
Attorney General


Bill Gunter
State Treasurer








STATE TREASURER
STATE FIRE MARSHAL
INSURANCE COMMISSIONER



March 17, 1986




Mr. Thomas A. Sechler, P.E.
Administrator
Design Review and Permitting Section
Department of General Services
Larson Building, Suite 512
Tallahassee, Florida 32301


Larson Building
STATE OF FLORIDA
TALLAHASSEE 32304


RE: Plans Review for Fire Protection
and Safety
Flagler College
Government House
Project No.: DOE-UPN
Project Phase: As-Built Drawings

Dear Mr. Sechler:

Pursuant to the provisions of Section 255.25, Florida Statutes, a comprehensive
review of the plans for construction, renovation, alteration or change of occupancy
was conducted by the undersigned and the results are as indicated on the attached
reportss.

The item(s) noted will violate the Florida Statutes, Chapter 4A, Florida
Administrative Code, or the various codes and standards adopted by this office.
Corrective action is required prior to verifying whether the plans comply with
the Uniform Fire Safety Standards.

Please provide me with your reply or input as soon as practical.

Sincerely,

BILL GUNTER
STATE TREASURER
STATE FIRE MARSHAL




Richard Ruh
State Fire Protection Specialist
Bureau of Fire Prevention
Plans Review Section


RR/af
cc: W.W. Gay Fire Protection, Inc.
524 Stockton Street
Jacksonville, Florida 32204


Nat Nadler, Project Director
Department of General Services
Larson Building, Suite 512
Tallahassee, Florida 32301








PLANS REVIEw SECTION

TECHNICAL EVALUATION OF PLA:S



VIOLATION: Sprinkler System


COMMENT: (1)


N.F.P.A. 13, 1983 Edition, (a.a.). All ccr:l v.lv,,
check valves, drain pipes and test equipment.


(2) Provision for Flushing

(3) Section 1-10.1. The installer shall perform a required
test (Section 1-11), complete the contrator's material
and test certificates (see Section'1-12), and forward
the certificates to the authority having jurisdiction
to ask for approval of the installation.








Richard Ruh'
State Fire Protection Specialist




University of Florida Home Page
© 2004 - 2010 University of Florida George A. Smathers Libraries.
All rights reserved.

Acceptable Use, Copyright, and Disclaimer Statement
Last updated October 10, 2010 - - mvs