Group Title: Historic St. Augustine: East Wing Costs Delegation Reports / Statement of Condition, etc.
Title: Subcontractor's Application for Payment
ALL VOLUMES CITATION MAP IT! THUMBNAILS PAGE IMAGE ZOOMABLE
Full Citation
STANDARD VIEW MARC VIEW
Permanent Link: http://ufdc.ufl.edu/UF00095486/00031
 Material Information
Title: Subcontractor's Application for Payment
Series Title: Historic St. Augustine: East Wing Costs Delegation Reports / Statement of Condition, etc.
Physical Description: Maintenance record
Language: English
Publication Date: 1989
Physical Location:
Box: 8
Divider: Government House Maintenance
Folder: East Wing Costs Delegation Reports / Statement of Condition, etc.
 Subjects
Subject: Saint Augustine (Fla.)
48 King Street (Saint Augustine, Fla.)
Government House (Saint Augustine, Fla.)
Spatial Coverage: North America -- United States of America -- Florida -- Saint Johns -- Saint Augustine -- 48 King Street
Coordinates: 29.892465 x -81.313142
 Record Information
Bibliographic ID: UF00095486
Volume ID: VID00031
Source Institution: University of Florida
Holding Location: University of Florida
Rights Management: All rights reserved by the source institution and holding location.

Full Text





SUBCONTRACTOR'S APPLICATION FOR PAYMENT

TO: Historic St. Augustine Preseryq n Owen Electric Co.
Board
,_P Rn x 1927 3061 Mac Road

St-. Angustine. Florida 32085 St. Augustine, Florida 32086

JOB NUMBER: DATE: 3-22-89

PROJECT NAME: RENOVATIONS TO THE GOVERNMENT HOUSE
2-22-89 3-22-89
INVOICE PERIOD: 2-22-89 19 TO 3-22-89 ,19

STATEMENT OF CONTRACT:

1. ORIGINAL CONTRACT'AMOONT -------------------------- $10,860.00
-0-
2. APPROVED CHANGE ORDER NOS.-------------------------$

3. ADJUSTED CONTRACT AMOUNT-------------------------- $ 10,860.00

4. VALUE OF WORK COMPLETED TO DATE--------------------$ 10,860.00

5. .VALUE OF APPROVED C.O.'s COMPLETED----------------- $ -0-

6. MATERIALS' SUITABLY STORED ON SITE----------------- $ -0-

7. TOTAL COMPLETED AND SUITABLY STORED TO DATE--------$ 10,860.00

8. LESS 10% RETAINAGE---------------------------------$ N/A

9. TOTAL LESS RETAINAGE-------------------------------$ 10,860.00

10. AMOUNT PREVIOUS PAID TO DATE----------------------- 8,503.00

11. AMOUNT DUE THIS REQUEST----------------------------$ 2,357.00













i HS 'AR 1989IL





Ji6oLric 6t-Au6minc
SPr c.erV ,of'


The State of Florida

April 6, 1989


Mr. Mickey Owen
Owen Electric Company
3061 Mac Road
St. Augustine, FL 32086

Dear Mickey:
I have received your final billing for the electrical contract for the
renovation at Government House (DOS-84490010). Before I progress with the
final payment process I would like you to take,care of the following details
that were included in your contract:

1. Panel "B" is not labeled as such.
2. Two corners on the cover for Panel "B" are bent.
3. All the outlets you installed do not meet the specifications for
the job. You installed 15 amp. residential outlets, and 20 amp.
commercial grade outlets are required.
4. The conduit that feeds the small case outlets should be strapped
and bent to follow the configuration of the wall.
5. We require proof that the shields supplied for the fluorescent
fixtures are UV shielded.
6. Many of the outlets are crooked and not securely attached to the
walls.
7. The exit sign in the southeast corner is not set up straight and
screws are exposed at the top.
8. Panel "A" is not labeled as such.
9. The specifications call for a separate circuit for the microwave
unit in the vault and there isn't one.
10. Panel "A" lacks washers for the face.
11. Button missing from one of the rheostat switches in the East Wing.
12. PVC main feed is required by code to be strapped up every five feet,
and it should be straight and level to avoid future stress from sagging.
13. The switch that controlled the lights outside under the loggia was
covered up and we have no way of switching on those lights.




POST OFFICE BOX 1987 ST. AUGUSTINE, FLORIDA 32085
(904) 824-3355 (SUNCOM) 821-5455







April 6, 1989


I am sure that we can work out all these details and that the contract
completion forms can be processed. I am sure that you will want to complete
this job in a professional and workmanlike manner and I look forward to
hearing from you.

Sincerely,



David Scott
Research and Construction Director

DS/jh

c: Hector Miron
Herschel Shepard
Len Weeks


Mr. Owen